CITY OF ZEPHYRHILLS
5335 - 8TH STREET
(813)780-0020
FIRE SPRINKLER SYSTEM PERMIT
7096
Permit Number: 7096
Permit Type: FIRE SPRINKLER SYSTEM
Class of Work: FIRE-SPRINKLER SYS
Proposed Use: COMMERCIAL
Square Feet:
Est. Value:
Improv. Cost: 1,583,00
Date Issued:
Total Fees: 260.00
Amount Paid: 260.00
Date Paid: 10/15/2007
Work Desc: REPLACE & ADD FIRE SPRINKLERS
Address: 5048 AIRPORT RD
ZEPHYRHILLS, FL.
Township: Range: Book:
Lot(s): Block: Section:
Subdivision: CITY OF ZEPHYRHILLS
Parcel Number: 12-26-21-0000-04900-0010
Name: ZEPHYR DEVELOPMENT LLC
Address: 1414 W. SWANN
TAMPA, FL
Phone: 813 579-2011
I
FIRE INSPECTION FEES
110.00
r
't . \,1: l~
FIRE SYSTEM ACCEPTANCE Fina
Chapter 633, Florida statutes, authorizes the City to charge and collect user fees to pay for the costs of fire
prevention and protection related activities such as inspections, plan review, administrative fees, and other
costs related to the aforementioned.
Complete Plans, Specifications and Fee Must Accompany Application. Commencement of work without written approval of
the Fire Department's Fire Marshal or required permits or opening up for commercial activity without an approved final
inspection shall be charged double permit fee per day of operation or a minimum of $100.00, whichever is greater. All
work shall be performed in accordance with City Codes and Ordinances.
"WARNING TO OWNER: YOUR FAILURE TO RECORD A NOTICE OF
COMMENCEMENT MAY RESULT IN YOUR PAYING TWICE FOR
IMPROVEMENTS TO YOUR PROPERTY. IF YOU INTEND TO OBTAIN
FINANCING, CONSULT WITH YOUR LENDER OR AN ATTORNEY BEFORE
RECORDING Y UR NOTIC OF COMMENCEMENT."
....~-^".-
CONTRACTOR SIGNA TUR I
PERMIT EXPIRES IN 30 DAYS WITHOUT APPROVED INSPECTION
CALL FOR INSPECTION - 8 HOURS NOTICE REQUIRED
ZEPHYRHILLS FIRE RESCUE DEPT - Fire Marshal Office - 813-780-0041
F']re ;:;lier t\a!til \J'iHHarns
Z~P~"f;t'RtH~LLS F]R!~ DE? ~~~q'T~!E~\fT
690- Cairl Fioad. =eonyrhiils. :='.. J::SiJ.:,
3U5 ;3"] 3)~30-~:'~>4'i
,- a~~
8~; 3~ 7'3C-.~: G~.-.l.
. '
Occupancy No.:
Plan No.:
Business Name:
Business Address:
Business Phone No.:
Business Fax No.:
Contact:
PLAN REVIEW FEES
B Site Plan N/C
Multi-Family/Commercial ,06 sf
(Minimum Charge $25.00
o Plan Revisions DBl
SPRINKLER SYSTEMS
[)6 - 25 Heads $50
~ 26 plus Heads $100
STANDPIPE SYSTEM
o Per Riser $50
FIRE PUMP
o Per Pump
FIRE ALARM SYSTEM
o 0 - 25 Devices $50
026 plus Devices $100
SUPPRESSION SYSTEMS
R~i: ::
BOther $50
KITCHEN EXHAUST
o Hood/Ducts
OTHER
~LP Installation per tank
Fuel Tank Installation
Natural Gas Installation
Spray Booth
Comments:
$tOO
INSPECTION FEES
Annual N/C
1 st Re-inspection N/C
2nd Re-inspection $100
3rd Re-inspection $250
4th Re-Inspection $500
(Business closed until
violations corrected)
SPRINKLER SYSTEMS
Hydro Undergrounds $45
ydrostatic System $65
Wet Acceptance $45
Dry Acceptance $45
Hydrant Flow $75
FIRE ALARM SYSTEM
B System Acceptance $50
Recall Acceptance $50
OTHER
Billing Address:
BilliRg P!;1QR8 ~~:
Billing Fax No. '
Contact:
PERMIT FEE
Sprinkler $50
Standpipes $50
Fire Pump $50
Hoods $50
Detection $15
lP Gas $50
Natural Gas $50
Fuel Tanks $50
Sparklers $100
Fire Works $500
Camp Fire $25
Controlled Bul'!l $25
Hood/Duct $50
Place of Assembly $50
Fire Protection $25
Aammable Application $50
Waste Tire Storage $50
Generator < f0/IJ $100
Generator >30 f0/IJ 150
Bic-Hazard Waste $100
Fumigation Tenting $50
Torch Pot/Applied $50
Haz. Materials $100
B
(I ,-
PERMIT TOTAL~
't/1O ~ ~
FALSE ALARM FEE
1 st Alarm N/C
2nd Alarm N/C
3rd Alarm NlC
4th Alarm $100
5th Alarm $150
6th Alarm $200
NON COMPLIANCE $150
FALSE ALARM
TOTAL i
Tent 1 O'x1 0' or greater
Fire Pump
Fire Suppression
System Acceptance
B Exhaust Hood/Duct
Re-inspection
(other than annual)
D Inspection scheduled DBl
and cancelled less than
24 hours
Bconstruction Insp, N/C
./ Emergency Vehicle Ace rm1
PLANS TOTAL~ INSPECTION TOTAL~
GRAND TOTAL
Fire WalllSmoke Wall
lP Gas
Natural Gas
Fuel Tanks
$15
$25
$25
$25
$15
$45
$30
$50
$50
$50
$50
$50
$30
DBl
Date:
/of,s-/()7
Jllh
Page 1 of 1
Jacqueline Boges
From: Kerry Barnett
Sent: Monday, October 22, 2007 12:29 PM
To: Jacqueline Boges
Subject: RE: final inspection for install fire sprinkler
D1if1~
The sprinkler company needs to have the alarm company present so we can conduct flow and tamper tests. Can
you inform them of that. This may change the date. I also did not perform a pressure teste w'ch needs to be ~
completed before the final. They may need to contact me first. If so you can give them m~ cell p,hone number. ,
1ltf~ ~3 2-t
Hello Mr. Kerry,
I have put on your schedule a final inspection needed for the Wiginton Fire Sprinkler Inc company for
the install of sprinklers @ 5048 Airport Rd. Scheduled for Tuesday, 23rd no time given.
Jackie
'3{3-'~Z6-?~33
~
v~~
10/22/2007
813-780-0020
Date Received
City of Zephyrhills Permit Application
Building Depar1menl
Fax-813-700.0021
Owne,.. N_
I?IJ
I /II
I
I J?Dl-iCd A!a.fO(l:r (Z.,O. I LOTtI I I
I PARCELIDtJI il.- U- ll-o(X() -OtIq(x)-oo~OI1
(OIn'-~..-rtTAXN01lCEl ~)J
E3 NEWCONSTR fa. ADO/ALTO SIGN 0 MOVE 0 DEMOLISH r G
INSTALL c::::J REPAIR
PROPOSED USE 0 SFR ~ COMM 0 OTHER
TYPE OF CONSTRUCTION 0 BlOCK CJ FRAME 8 STEel 0 OTHER I
DESCRIPTIOHOFWORK LAoO ~ r,iU SOJeiJJk.Ui..'.-
I sa FOOTAGE / 6fXX) Fr~ HEIGHT I
OwnllI'aAclcha ~ w~ SW4w~ Ave.
Fee SImple TIlIehoIder ....1
Owner Phone Number
Owner "'- NUIIlber 1
Owner "'- NUIIlber I
Fee Simple T1UehoIder AckI_.
JOB ADDRESS
SUBDMSlON
/r
~
(00
Lff-frl5 ~
j}ct. t.j(
,..-
r~",.
I.)
Of -- >,
W.R,E,C, ~
~li~~~~~
S}5\1- Otu
WORK PROPOSED
BUILDING SIZE
D
D
D
I:B.
o
BUILDING
I VAlUATION OF TOTAL CONSTRUCTION
I AMP SERVICE
1$ I
rl ,,-~ 3. OD I VAlUATION OF MECHANICAL INSTAlLATION
o ROOFING ..8l SPECIAL TV 0 OTHER
FINISHED FLOOR ELEVATIONS I I FLOOD ZONE AREA DYES
ELECTRICAL
1$
1$
CJ
PROGRESS ENERGY
PLUMBING
MECHANICAL
GAS
ONO
:=RE I
Addreaa I
~I
Addru. I
PWIIBER I
SIGNATURE .
Addreaa I
=~I I:~
::;: 12 ~'fdJl~ ~
AddNaa _~Uk(;!'_~~. I
COMPANY
REGISTERED
I...!.L!U
FEE CURR&HT
L:!.!!L.I
License II
COMPANY
REGISTERED
I...!.L!U
FEEC~
L:!.!!L.I
License /I
COMPANY
REGISTERED
I...!.L!U
FEE CURRENT
L:!.!!L.I
License 1#
I...!.L!U
FEE CURRENT
L:!.!!L.I
RESIDENTIAL
COMMERCIAL
AIlach (2) Plot Plans; (2) sels of BuHding Plans; (1) set of Energy Fonns
MinimlA'n ten (10) working days 8II8r submittal dale, Required onsite, ConslruclIon Plans, ~ Facilities & 1 dumpster
AIlach (3) seIll of Bulking PI_; (1) set Of Energy Forms.
Minimum ten (10) working days 8II8r submittal dale, Required onsite, ConslrucIion Plans, ~ F8CiIilies & 1 cUnpster
AU commen:i81 requir8menls must ~ c:ompIi8nce,
Alt8ch (2) seIll of Engineered Plans,
'H'PROPERTV SURVEY required for all NEW construction,
SIGN PERMIT
D1rect1_:
Fill out .pplication completely,
Owner & Contractor SIgn back of appIicetion, nol8tized
If....... $2JOO,. ~ of C--1CtlIMnI1a ....uhd. lAIC ~....... $1000)
H Agent (for the c:ontnK:Ior) or Power Of AlIOmey (for the 0Ml8l') would be someone With nota1zed IlIlIer from _lIUlhorizing _
OVER THE COUNTER PERIIlT1ING (Front Of Applica1ion Only)
Reroofs Sewefs Service U~ A1C Fences (PIotISurveylFoolage)
Dltvewaya-Not over Counter if on public roadWays, ,needs ROW
NOTICE OF DEED RESTRICTIONS: The undersigned understands lhat this permit may be subject to "deed" restrictions"
which may be more reslrictive'than County regulations. The undersigned assumes responsibility for compliance with any
applicable deed resIEictions.
UNLICENSED CONTRACTORS AND CONTRACTOR RESPONSlBJUnES: If the owner has hired a contractor or
contractors to undertake work, they may be required to be licensed In accordance with state and local regulations. If the
contractor is not licensed as required by law, both the owner and contractor may be cited for a misdemeanor violation
under state law, If the owner or intended contractor are uncertain as to what licensing requirements may apply for the
intended work, they are advised to contact the Pasco County Building Inspection Divislon-licensing Section at 727-847-
8009. Furthermore, if the owner has hired a contractor or contractors. he is advised to have the contractor(s) sign
portions of the "contractor Block" of this application for which they will be responsible. If you, as the owner sign as the
contractor, that may be an indication that he Is not properly licensed and Is not entitled to penniUing privileges in Pasco
County.
TRANSPORTAnON IMPACT/UnunES IMPACT AND RESOURCE RECOVERY FEES: The undersigned understands
that Transportation Impact Fees and Recourse Recovery Fees may apply to the construction of new buildings, change of
use in existing buildings, or expansion of existing buUdings, as specified In Pasco County Ordinance number 89-07 and
90-07, as amended. The undersigned also understands, that such fees, as may be due, will be identified at the time of
permitting. It is further understood lhat Transportation Impact Fees and Resource Recovery Fees must be paid prior to
receiving a "certiIICate of occupancy" or final power release. If the project does not involve a certiIICate of occupency or
final power release, the fees must be paid prior to permit issuance. Furthermore, if Pasco County INaterISewer Impact
fees are due, they must be paid prior to permit issuance in accordance with applicable Pasco County ordinances.
CONSTRUCnoN UEN LAW (Chapter 713, Florida Statutes. a. amended): If valuation of work is $2,500.00 or more, I
certify that I, the applicant, have been provided with a copy of the "Florida Construction Lien Law-Homeowner's
Protection Guide" prepared by the Florida Department of Agriculture and Consumer Affairs. If the applicant is someone
other than the "owner", I certify that I have obtained a copy of the above described document and promise in good faith to
deliver it to the "owner" prior to commencement.
CONTRACTOR'SIOWNER'S AFFIDAVIT: I certify that al the infonnalion in this application is accurate and that aU work
wi. be done In compliance with al applicable laws regulating construction. zoning and land development. AppIlcation is
hereby made to obtain a permit to do work and installation as indicated. I certify that no work or Installatlon has
commenced prior to issuance of a permit and that all work wiD be performed to meet standards of all laws regulating
construction, County and City codes, zoning regulations, and land development regulations in the jurisdiction. I also
certify that I understand lhat the regulations of other government agencies may apply to the intended work, and that it is
my responsibility to identify what actions I must take to be in compliance. Such agencies include but are not 8m/ted to:
Department of Environmental Prolectlon-Cypress Bayheads, Wetland Areas and Environmentally Sensitive
lands, Water1Wastewate Treatment.
Southwest Florida Water Management DistrIct-WeHs, Cypress Bayheads, weiland Areas, Altering
Watercourses.
Army Corps of Engineers-Seawalls, Docks, Navigable Waterways.
Department of Health & Rehabilitative ServiceslEnvlronmental Health Unit-Wells, Wastewater Treatment,
Septic Tanks,
US Environmental Protection Agency-Asbestos abatement.
Federal Aviation Authority-Runways.
I understand that the following resIJiclions apply to the use of fill:
Use of fill is not allowed in F/ood Zone V unless expressly permitted.
If the fill material is to be used in Flood Zone "A", It is understood that a drainage plan addressing a
"compensating volume' will be submitted at time of permitting which is prepared by a professional engineer
licensed by the State of Florida.
If the fill material is to be used In Flood Zone UN in connection with a permitted buildIng using stem wall
construction, I certify that fill will be used only to fiU the area within the stem wall.
If fill material is to be used in any area, I certify that use of sud1 fill wiD not adVersely affect adjacent
properties. If use of fill is found to adversely afrect adjacent properties, the owner may be cited for violating
the conditions of the building permit issued under the atIached permit application, for lots less than one (1)
acre which are elevated by fill, an engineered drainage plan Is required.
If I am the AGENT FOR THE OWNER, I promise in good faith to inform the owner of the permitting conditions set forth in
this affidavit prior to commencing construction, I understand that a separate permit may be required for electrical work,
plumbing, signs, wells, pools, air conditioning, gas, or other installations not specifically included in the application. A
permit issued shall be construed to be a license to proceed with the work and not as authority to violate, cancel. alter, or
set aside any provisions of the technical codes, nor shall issuance of a permit prevent the BuIlding 0fIIcia1 from thereafter
requiring a correction of errors in plans, construction Of' violations of any codes. Every permit issued shall become invalid
unless the work authorized by sud1 permit is commenced within six months of permit issuance, Of' if wort authorized by
the permit is suspended or abandoned for a period of six (6) months after the time the work is commenced. An exIiension
may be requested, in writing, from the Building Official for a period not to exceed ninety (90) days and wRI demonstrate
justifiable cause for the extension, If work ceases for ninety (90) consecutive days, the job is considered abandoned.
WARNING TO OWNER: YOUR FAILURE TO RECORD A NOnCE OF COMMENCEMENT MAY RESULT IN YOUR
PAYING TWICE FOR IMPROVEMENTS TO YOUR PROPERTY. IF YOU INTEND TO OBTAIN FINANCING, CONSULT
F
CommissiOn No,
CONTRACTOR~ ~. A... -
~' d and to (or 8IlInned) ~~elhis
o by~S' ~
~[j;:~~
Commission No,
Notary Public
Public
Name of Notary typed, printed or stamped
Name of Notary typed. pMled or stamped
BELEN ROMAN ,
Notary Public, State 01 FlorIda
My comm. expo Sept. 23, 2008
ComlT\. No. DO 355500
BELEN ROMAN
Notary Public, State 01 Florida
My comm. expo Sept. 23, 2008
Comrn. No. DO 355500
Zephyrhills Fire Rescue
6907 Dairy Road, Zephyrhills, FL 33542
F ire Marshal
Kerry Barnett
Bus (813) 780-0041
Fax (813) 780-0044
October 15, 2007
I have reviewed and approved the plans for a sprinkler system modification located at
5048 Airport Rd. I have attached the comments for the plan approval. If there are any
questions please contact my office at 813-780-0041.
1. Letter from contractor required that system is up to current code for the space
it occupies. (NFP A 13, 2007 Edition)
Inspections Required
1. System to be isolated and pressure tested since all heads are being replaced in
occupancy (200 psi for 2 hours).
2. Acceptance Test.
APPROVED
by Fire Marshal of ZephyrhiUs
with comments provided with plan(s)
(tllSl;?