HomeMy WebLinkAboutBIN B-4 PERMIT 4316 (2) TERMITE SPECIFICATIONS: · 1. A PERMANENT SIGN WHICH IDENTIFIES THE TERMITE TREATMENT PROVIDER AND NEED FOR RE-INSPECTION AND TREATMENT CONTRACT RENEWAL SHALL BE PROVIDED. THE SIGN SHALL BE POSTED NEAR THE WATER HEATER OR ELECTRIC PANEL.(FBC 104.2.6) 2. CONDENSATE AND ROOF DOWNSPOUTS SHALL DISCHARGE AT LEAST 1'-0" AWAY FROM BUILDING SIDE WALKS.(FBC 1503.4.4) 3. IRRIGATION/SPRINKLER SYSTEMS INCLUDING ALL RISERS AND SPRAY HEADS SHALL NOT BE INSTALLED WITHIN 1'-0" OF THE BUILDING SIDE WALLS.(FBC 1503.4.4) 4. TO PROVIDE FOR INSPECTION FOR TERMITE INFESTATION, BETWEEN WALL COVERING AND FINAL EARTH GRADE SHALL NOT BE LESS THAT 6 INCHES. EXCEPTION: PAINT OR DECORATIVE CEMENTATIOUS FINISH LESS THAN 5/8" THICK ADHERED DIRECTLY TO THE FOUNDATION WALL.(FBC 1403,1.6) 5. INITIAL TREATMENT SHALL BE DONE AFTER ALL EXCAVATION AND BACKFILL IS COMPLETE,(FBC 1816.1.1) 6. SOIL DISTURBED AFTER THE INITIAL TREATMENT SHALL BE RETREATED INCLUDING SPACES BOXED AND FORMED.(FBC 1816.1,2) 7. BOXED AREAS IN CONCRETE FLOORS FOR SUBSEQUENT INSTALLATION OF TRAPS, ETC., SHALL BE MADE WITH PERMANENT METAL OR PLASTIC FORMS. PERMANENT FORMS MUST BE OF A SIZE AND DEPTH THAT WILL ELIMINATE THE DISTURBANCE OF SOIL AFTER THE INITIAL TREATMENT.(FBC 1816.1.3) 8. MINIMUM 6 MIL VAPOR RETARDER MUST BE INSTALLED TO PROTECT AGAINST RAINFALL DILUTION. IF RAINFALL OCCURS BEFORE VAPOR RETARDER PLACEMENT, RETREATMENT IS REQUIRED.(FBC 1816.1.4) 9. CONCRETE OVERPOUR AND MORTAR ALONG THE FOUNDATION PERIMETER MUST BE REMOVED BEFORE EXTERIOR SOIL TREATMENT.(FBC 1816.1.5) 10. SOIL TREATMENT MUST BE APPLIED UNDER ALL EXTERIOR CONCRETE OR GRADE WITHIN 1'-0" OF THE STRUCTURE SIDEWALLS.(FBC 1816.1.6) 11. AN EXTERIOR VERTICAL CHEMICAL BARRIER MUST BE INSTALLED AFTER CONSTRUCTION IS COMPLETE INCLUDING LANDSCAPING AND IRRIGATION. ANY SOIL DISTURBED AFTER THE VERTICAL BARRIER IS APPLIED, SHALL BE RETREATED.(FBC 1816.1.6) 12. ALL BUILDINGS ARE REQUIRED TO HAVE PRE-CONSTRUCTION TREATMENT.(FBC 1816.1.7) 13. A CERTIFICATE OF COMPLIANCE MUST BE ISSUED TO THE BUILDING DEPARTMENT BY A LICENSED PEST CONTROL COMPANY BEFORE A CERTIFICATE OF OCCUPANCY WILL BE ISSUED. THE CERTIFICATE OF COMPLIANCE SHALL STATE: "THE BUILDING HAS RECEIVED A COMPLETE TREATMENT FOR THE PREVENTION OF SUBTERRANEAN TERMITES. THE TREATMENT IS IN ACCORDANCE WITH THE RULES AND LAWS OF THE FLORIDA DEPARTMENT OF AGRICULTURE AND CONSUMER SERVICES."(FBC 1816.1.7) 14. AFTER ALL WORK IS COMPLETED, LOOSE WOOD AND FILL MUST BE REMOVED FROM BELOW AND WITHIN 1'-0" OF THE BUILDING. THIS INCLUDES ALL GRADE STAKES, TUB TRAY BOXES, FORMS, SHORING OR OTHER CELLULOSE CONTAINING MATERIAL. (FBC 2303.1.3) 15. NO WOOD, VEGETATION, STUMPS, CARDBOARD, TRASH, ETC., SHALL BE BURIED WITHIN 15'-0": OF ANY BUILDING OR PROPOSED BUILDING.(FBC 2303.1.4) A,B. Abv. A/C Adj. A.F.F. A.H.U. ALT. B.C. B.F. Bk Sh . Bm. BOT. B.P. , Brg. Cir. Clg. Co!. Compo C.T. D Dec. Ded. Dbl. Dia, Disp. Dist. D.S. D.V. D.w. Ea. E.w. Elec. Elev. Ext. Exp. .~ -t ~ ABBREVIATIONS Anchor Bolt Above Air-Conditioner Adjustable Above Finished Floor Air Handler Unit Alternate Base Cabinet Blfold Door Book Shelf Beam Bottom Bypass door Bearing Circle Ceiling Column A/C Compressor Ceramic Tile Dryer Decorative Dedicated Outlet Double Diameter Disposal Distance Drawer Stack Dryer Vent Dishwasher Each Each Way Electrical Elevation Exterior Expansion F.B.C. Fin. Fir. F.G. Fir. Fdn. Fir. Sys. F.PI. Ft. Ftg. FX Galv. G.C. G.F.1. G.T. Hdr. Hgt. HB Int. K/Wall K.S. Laun. Lav. L,F. L.T. Mas. Max M.C. Mfgr. Micro. Min M.L. Mir. Mono N.T.S. Florida Bldg. Code Finished Floor Fixed Glass Floor Foundation Floor System Fireplace Foot / Feet Footing Fixed Galvanized General Contractor Ground Fault Interrupter Girder Truss Header Height Hose Bibb Interior Kneewall Knee Space Laundry Lavatory Linear Ft. Laundry Tub Masonry Maximum Medicine Cabinet Manufacturer Microwave Minimum Microlam Mirror Monolithic Not to Scale Opn'g. Opt. Pc. Ped. P,L. PLF PIt. Ht. Pit Sh. PSF P.T. Pwd. Rad. Ref. Req'd. Rm. Rnd. R/SH SD. S.F. Sh. SHT S.L. S.P.F. Sq. S.Y.P. Temp. Thik'n. T.O.B. T.O.M. T.O.P. Trans. Typ. UCL U.N.O. VB Vert. V.L. VTR W WI W/C W.A. Wd WP MASTER REVISIONS DATE DESCRIPTION Opening Optional Piece Pedestal Parallam Pounds per linear foot Plate Height Plant Shelf Pounds per square foot Pressure Treated Powder Room Radius Refrigerator ReqUired Room Round Rod and Shelf Smoke Detector Square Ft. Shelves Sheet Side Lights Spruce Pine Fir Square Southern Yellow Pine Tempered Thicken Top of Block Top of Masonry Top of Plate Transom Window Typical Under Cabinet Lighting Unless Noted Othervvise Vanity Base Vertical Versalam Vent through Roof Washer With Water Closet Wedge Anchor Wood Water Proof STRUCTURAL NOTES: STRUCTURAL DESIGN CRITERIA FOUNDATIONS 3. ANY WOOD FRAME INTERIOR BEARING WALL STUDS THAT HAVE HOLES IN THE CENTER OF THE STUD UP TO 1" DIA. SHALL HAVE STUD PROTECTION SHIELDS FOR ALL HOLES OVER 1" IN DIA. FOR PLUMBING LINES, ETC. SHALL BE REPAIRED WITH SIMPSON HSS2 STUD SHOES,TYP., U.N.O. CODES: FLORIDA BUILDING CODE, 2001 EDITION WITH 2003 REVISIONS BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE (ACI 318-02) SPECIFICATIONS FOR STRUCTURAL CONCRETE BUILDINGS (ACI 301-02) BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES (ACI 530-02) NATIONAL DESIGN SPECIFICATION FOR WOOD CONSTRUCTION, 2001 EDITION APA PLYWOOD DESIGN SPECIFICATION SOIL TO BE COMPACTED TO AT LEAST 95% OF MAX. DRY DENSITY AS DETERMINED BY ASTM - 1557 ( MODIFIED PROCTOR) FOUNDATION INSPECTIONS A FOUNDATION SURVEY SHALL BE PERFORMED AND A COPY OF THE SURVEY SHALL BE ON SITE FOR THE BUILDING INSPECTORS USE, OR ALL PROPERTY MARKERS SHALL BE EXPOSED AND A STRING STRETCHED FROM MARKER TO MARKER TO VERIFY REQUIRED SETBACKS. CAST IN PLACE CONCRETE 1. ALL CONCRETE SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH AT 28 DAYS OF 3000 PSI, A SLUMP OF 6" PLUS OR MINUS 1", AND HAVE 2 TO 5% AIR ENTRAINMENT, AND A MAXIMUM WATER/CEMENT RATIO OF 0.63 2. ALL REINFORCING STEEL SHALL BE NEW DOMESTIC DEFORMED BILLET STEEL CONFORMING TO ASTM A-615 GRADE 40. 3. WELDED WIRE FABRIC SHALL CONFORM TO ASTM A-185. WWF SHALL BE LAPPED AT LEAST 6" AND CONTAIN AT LEAST ONE CROSS WIRE WITHIN THE 6". 4. HOOKS SHALL BE PROVIDED AT DISCONTINUOUS ENDS OF ALL TOP BARS OF BEAMS. 5. HORIZONTAL FOOTING BARS SHALL BE BENT 1'-0" AROUND CORNERS OR CORNER BARS WITH A 2'-0" LAP PROVIDED 6. MINIMUM LAP SPLICES ON ALL REINFORCING BAR SPLICES SHALL BE 40 BAR DIAMETERS TYP. 7. CONCRETE COVER MIN. 3" WHEN EXPOSED TO EARTH OR 11/2" TO FORM WOOD FRAMING INSPECTION LIVE LOADS: ROOF RESIDENTIAL FLOOR, UNLESS OTHERWISE INDICATED BALCONIES ST AI RS LIGHT PARTITIONS (DEAD LOAD), U.N.O. WIND LOADS BASED ON FBC, SECTION 1606.2. WIND VELOCITY: 123 M.P.H., USE FACTOR: 1.0 20 PSF (REDUCIBLE) 40 PSF 40 PSF 40 PSF 20 PSF 10 PSF ATTIC L.L. ALL PLUMBING, ELECTRICAL, AND MECHANICAL ROUGH-INS MUST BE COMPLETE, INSPECTED AND APPROVED BEFORE REQUESTING FRAMING INSPECTION. PREFABRICATED WOOD TRUSSES 1. ALL PREFABRICATED WOOD TRUSSES SHALL BE SECURELY FASTENED TO THEIR SUPPORTING WALLS OR BEAMS WITH HURRICANE CLIPS OR ANCHORS. 2. PREFABRICATE WOOD TRUSSES SHALL BE DESIGNED IN ACCORDANCE WITH THE LATEST EDITION OF THE "NATIONAL DESIGN SPECIFICATION FOR STRESS-GRADE LUMBER AND ITS FASTENERS" AS RECOMMENDED BY THE NATIONAL FOREST PRODUCTS ASSOCIATION. 3. TRUSS MEMBERS AND CONNECTIONS SHALL BE PROPOR- TIONED ( WITH A MAXIMUM ALLOWABLE STRESS INCREASE FOR LOAD DURATION OF 25%) TO WITHSTAND THE LIVE LOADS GIVEN IN THE NOTES AND TOTAL DEAD LOAD. 4. BRIDGING FOR PRE-ENGINEERED TRUSSES SHALL BE AS REQUIRED BY THE TRUSS MANUFACTURER U~LESS NOTED ON THE PLANS. 5. TRUSS ELEVATIONS AND SECTIONS ARE FOR GENERAL CONFIGURATION OF TRUSSES ONLY. WEB MEMBERS ARE NOT SHOWN, BUT SHALL BE DESIGNED BY THE TRUSS MANUFACTURER IN ACCORDANCE WITH THE FOLLOWING DESIGN LOADS: 6. DESIGN SPECIFICATIONS FOR LIGHT WEIGHT METAL PLATE CONNECTED WOOD TRUSSES PER THE TRUSS PLATE INSTITUTE TPI LATEST EDITION. 7. PRE-ENGINEERED WOOD TRUSSES SHALL BE DESIGNED BY THE MANUFACTURER IN ACCORDAI\CE WITH SPECIFIED LOADS AND GOVERNING CODES. SUBMITTALS SHALL INCLUDE TRUSS FRAMING PLANS A~D DETAILS SHOWING MEMBER SIZES, BRACING, ANCHORAGE, CONNECTIONS, TRUSS LOCATIO~S, AND AND PERMANENT BRACING AND/OR BRIDGING AS REQUIRED FOR ERECTION AND FOR THE PERMA~ENT STRUCTURE. EACH SUBMITTAL SHALL BE SIGNED AND SEALED BY A FLORIDA REGISTERED STRUCTURAL ENGINEER. SUBMIT 3 COPIES FOR REVIEW AND APPROVAL PRIOR TO FABRICATION. 8. THE TRUSS MANUFACTURER SHALL DETERMINE ALL SPANS WORKING POINTS, BEARING POINTS, AND SIMILAR CONDITIONS. TRUSS SHOP DRAWINGS SHALL SHOW ALL TRUSSES, ALL BRACING MEMBERS, AND ALL TRUSS TO TRUSS HANGERS. WIND LOADS: (F.B.C.) CONCRETE STRENGTH @ 28 DAYS ALL CONCRETE UNLESS OTHERWISE INDICATED PEA GRAVEL CONCRETE FOR MASONRY CELLS ONLY (DO I'\OT USE FOR CONCRETE COLUMNS OR TIE BEAMS) 3000 PSI 3000 PSI REINFORCING: WELDED WIRE FABRIC SHALL CONFORM TO ALL REINFORCING BARS ALL STIRRUPS AND TIES ASTM A185 ASTM A615-40 40,000 PSI ASTM A615-40 40,000 PSI CONCRETE MASONRY UNITS: ASTM C90-99b, STANDARD WEIGHT UNITS, fm=1500 PSI MORTAR TYPE "S" 1800 PSI CONCRETE GROUT 3000 PSI CONTINUOUS MASONRY INSPECTION IS REQUIRED DURING CONSTRUCTION ALL STRUCTURAL AND MISCELLAI\EOUS STEEL A36 36,000 PSI, U.N.O SHOP AND FIELD WELDS: E70XX ELECTRODES ALL BOLTS CAST IN CONCRETE: ASTM A36 OR ASTM A-307 BEAMS, RAFTERS, JOIST, PLATES, ETC. U.N.O. 1'\0. 2 SOUTHERN YELLOW PINE (19% M.C.) ROOF DECK: PLYWOOD C-C/C-D, EXTERIOR, or OSB FLOOR SHEATHING: T&G A-C GROUP 1 APA RATED (48/24) WALL SHEATHING: PLYWOOD C-C/C-D, EXTERIOR OR OSB VERSA LAM BEAM Fb = 2900 PSI (2,OE) WOOD COLS. PARALLAM 2.0E U.N.O. DESIGN LOADS: TOP CHORD LIVE LOAD: 20 PSF TOP CHORD DEAD LOAD: 10 PSF STRUCTURAL STEEL: REINFORCING STEEL WOOD FRAMING: ALL REINFORCING STEEL SHALL BE NEW DEFORMED BARS FREE FROM RUST, SCALE & OIL & SHALL MEET ASTM A615 REI~FORCING FOR FOOTING SHALL BE SUPPORTED ON PRE- CAST CONCRETE PADS, TOP REINFORCING SHALL BE POSITIVELY SUPPORTED BY TEMPORARY STRINGERS. DOWELS FOR COLUM~S & FILLED CELLS SHALL BE SECURED IN PLACE BY USING ADDITIONAL CROSS- REINFORCING TIED TO FOOTING REINFORCING. SPLICES IN REI~FORCING WHERE PERMITTED SHALL BE THE FOLLOWING MINIMUM, UNLESS OTHERWISE INDICATED ON THE DRAWINGS: FTGS, WALLS, COLUMNS, BEAMS, SLABS: 36 DIA. OR 2'-0" MIN., WHICHEVER IS MORE. FILLED CELL REINFORCING: 40 DIA. OR 2'-0" MIN., WHICHEVER IS MORE. TEMPERATURE REINFORCING: 20 DIA. OR 1'-0" MIN., WHICHEVER IS MORE. WELDED WIRE MESH: 8" LAP WOOD ROOF TRUSSES: BOTTOM CHORD DEAD LOAD: 10 PSF 40 PSF 10 PSF BOTTOM CHORD ATTIC LIVE LOAD: SEE DRAWINGS FOR SPECIAL CONCENTRATED LOADS. DESIGN FOR NEW WIND UPLIFT AS PER SPECIFIED CODES, DEDUCTING A MAXIMUM OF 5 P.S.F. DEAD LOAD, BUT NOT EXCEEDING ACTUAL DEAD LOAD. DESIGN LOADS: DEAD LOAD: LIVE LOAD: TOTAL: MASONRY WALL CONST. 1. HOLLOW LOAD BEARI:'\G UNITS SHALL BE NORMAL WEIGHT, GRADE N, TYPE 2, CONFORMING TO ASTM C90, WITH A MINIMUM NET COMPRESSIVE STRENGTH OF 1900 PSI ( f'm = 1500 PSI) 2. MORTAR SHALL BE TYPE "S", CONFORMII\G TO ASTM C270. 3. COARSE GROUT SHALL CONFORM TO ASTM C476 WITH A MAXIMUM AGGREGATE SIZE OF 3/8" AND A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI SLUMP 8" TO 11". 4. VERTICAL REINFORCEMENT SHALL BE AS NOTED ON THE DRAWI~GS WITH THE CELLS FILLED WITH COARSE GROUT. 5. VERTICAL REINFORCEMENT SHALL BE HELD IN POSITION AT THE TOP AND BOTTOM AND AT A MAXIMUM SPACING OF 192 BAR DIAMETERS. REINFORCEMENT SHALL BE PLACED IN THE CENTER OF THE MASONRY CELL TYPICAL UNLESS OTHERWISE NOTED. 6. REINfORCING STEEL SHALL BE LAPPED A MI~IMUM OF 40 BAR DIAMETERS, UNLESS OTHERWISE NOTED ON THE DRAWINGS 7. GROUT STOPS SHALL BE PROVIDED BELOW BOND BEAM. PLASTIC SCREEN, METAL LATH STRIP OR CAVITY CAPS MAY BE USED TO PREVENT THE FLOW GROUT INTO CELLS BELOW. THE USE OF FELT PAPER AS A STOP IS PROHIBITED. UPLIFT CONNECTORS 1. UPLIFT CONNECTORS SUCH AS HURRICANE CLIPS, TRUSS ANCHORS AND ANCHOR BOLTS ARE ONLY REQUIRED ON MEMBERS IN WALLS THAT ARE EXPOSED TO UPLIFT FORCES. INTERIOR LOAD BEARING WALLS ARE NOT ALWAYS EXPOSED TO UPLIFT FORCES. THE MEMBERS OF THESE WALLS WOULD NOT NEED TO HAVE CONNECTORS APPLIED. PLEASE CONSULT THE TRUSS ENGINEERING FOR THE LOCATION OF THESE WALLS. WOOD FLOOR TRUSSES: 15 PSF 50 PSF 65 PSF ,.. ASSUMED ALLOWABLE SOIL BEARING PRESSURE AFTER COMPACTION: 2000 PSF SEE SOILS REPORT AND SPECIFICATIONS FOR COMPACTION REQUIREMENTS IF SOIL CONDITIONS IN THE PROJECT DO NOT MEET OR EXCEED THE CAPACITY THE GENERAL CONTRACTOR SHALL CONTACT THE E~GINEER PRIOR TO FOU~DATION POUR FOR VERIFICATION OF FOUNDATION DESIGN. SOIL BEARING VALUE: BUILDING DATA CONSTRUCTION TYPE - TYPE VI UNPROTECTED (SECTION 608 - FBC 2001) MEAN ROOF 15 FT. HIGH TYPICAL FOR SINGLE HOMES WIND SPEED 123 MPH (3 SEC. GUST) WIND IMPORTANCE FACTOR - (Iw) = 1.0 WIND EXPOSURE - "B" (FBC 1606.1.8) INTERNAL PRESSURE COEFFICIENT = +/- 0.55 (PARTIALLY ENCLOSED BLDG) WOOD CONSTRUCTION 1. WOOD CONSTRUCTION SHALL CONFORM TO THE NFPA "NATIONAL DESIGN SPECIFICATION FOR WOOD CONSTRUCTION", LATEST EDITION. 2. ALL EXTERIOR WOOD STUD WALLS, BEARING WALLS, SHEAR WALLS AND MISC. STRUCTURAL WOOD FRAMING MEMBERS, ( I.E. BLOCKING OR GABLE END BRACING) SHALL BE EITHER SOUTHERN PINE, OR S.P.F. NUMBER 2 GRADE SHALL BE USED REGARDLESS OF SPECIES. DESIGN WIND PRESSURE: (COMPOI\ENT AND CLADDING) WORST CASE (10 SF - END ZONE) WINDOWS AND DOORS 123 MPH + 38 PSF / - 40 PSF GARAGE DOORS (V = 123 MPH) SINGLE 9x7 +37.0 PSF / -40.0 PSF DOUBLE 16x7 +37.0 PSF 1-41.0 PSF SEE FLOOR PLAN FOR ACTUAL PRESSURES ALL WORK SHALL COMPLY WITH ALL PREVAILING CODES, FLORlDABUlLDn-:G CODE, NATIONAL ELECTRIC CODE AND CITY OF ZEPHYRHILLS ORDINANCES ENGINEERED PLANS ON FILE REVIEWED HAY 1 0 2005 ~~ COLONIAL GRANDE 2003 GENERAL NOTES: THE FOLLOWING TECHINCAL CODES SHALL APPLY: 2001 FLORIDA BUILDING CODE, WITH 2003 REVISIONS PLUMBING, MECHANICAL, FUEL GAS, ENERGY EFFICIENCY, ACCESSIBILITY, AND NFPA 70-02 NATIONAL ELECTRICAL CODES 1. TANK TYPE WATER CLOSET VOLUME 1.6 GALLONS 2. WALL MOUNT WATER CLOSET VOLUME 3.5 GALLONS 3. WATER - FLOW RATE. PUBLIC FACILITIES 0.5 G.P.M. PRIVATE FACILITIES 2.2 G.P.M. SHOWER HEADS 2.5 G.P.M. 4. ALL WATER LINE PLUMBING TO BE PVPC VTR LOCATIONS ARE APPROXIMATE AND MAY CHANGE DUE TO JOBSITE CONDITIONS THE FOLLOWING SHALL COMPLY WITH THE 2001 FBC. o PORCHES AND BALCONIES SECTION 1014 D HANDRAILS - SECTION +007.5 D GUARDRAILS - SECTION 1015, 1019.9 D STAIRS - SECTION 1007 D CHIMNEY & FIREPLACE SECTION 2804-2806 (MFGR) SECTION 2113-2114 (MAS) D EGRESS WINDOWS SECTION 1005.4 5. ALL OPENINGS SHALL COMPLY WITH 2001 FBC WIND LOADS AS STATED BELOW. ATTACHMENTS OF WiNDOWS, DOORS, SLIDING GLASS DOOR? AND O.H. GARAGE DOOR~ ARE TO DELEGATED THE MANUFACTURER OF THESE ITEMS. THE MANUFACTURER OF THESE ITEMS SHALL SUBMIT ATTACHMENTS FOR SITE INSTALLATION. SEE ATTACHED SPECIFICATION $HEETS FOR MANUFACTURERS DESIGN CRITERIA AND INSTALLATION METHODS FOR WINDOWS, DOORS, SLIDING GLASS DOORS, OVERHEAD GARAGE DOORS, A~D ROOFING. , I 6. ALL DOORS INTERIOR & EXTERIOR ARE 6'-8" UNLESS OTHERWISE NOTED ALL SHOWER ENCLOSURES TO BE TEMPERED GLASS 7. ALL WINDOWS WITHIN 24" OF DOORS (INTERIOR & EXTERIOR) AND WITHIN 18" OF FLR TO BE TEMPERED GLASS. (SECTION 2405,2) SHT NO 1 2 3 4 5 6 S-1 S-2 S-3 S-4 8-5 S-6 S-7 S-8 S-9 S-10 S-10A S-11 S-12 S-13 S-14 S-15 S-16 S-17 S-18 INDEX OF DRAWINGS TITLE COVER SHEET FLOOR PLAN FOUNDATION PLAN ELECTRICAL PLAN ELEVATIONS TRUSS LAYOUT MASONRY DETAILS LINTEL PLAN AND DETAILS DETAILS DETAILS DETAILS DETAILS STRUC. NOTES & HANGER INFORMATION DETAILS DOOR DETAILS ROOFING DETAILS ROOFING DETAILS GARAGE DETAILS DETAILS PRODUCT APPROVAL WINDOW DETAILS SGD DETAILS DETAILS DETAILS DETAILS NOTICE TO BUILDER IT IS THE INTENT OF THIS DESIGNER THAT THESE PLANS ARE ACCURATE AND ARE CLEAR ENOUGH FOR THE LICENSED PROFESS- ONAL TO CONSTRUCT THIS PROJECT. IN THE EVENT THAT SOMETHING IS UNCLEAR OR NEEDS CLARIFICATION..STOP..AND CALL THE DESIGNER LISTED IN THIS TITLE PAGE. IT IS THE RESPONSIBILITY OF THE LICENSED PROFESSIONAL THAT IS CONSTRUCTING THIS PROJECT TO FULLY REVIEW THESE DOCUMENTS BEFORE CONSTRUCTION BEGINS AND ANY AND ALL CORRECTIONS, IF NEEDED, TO BE MADE BEFORE ANY WORK IS DONE. W LL.~O::: '00:::0 W LL.LL. I-w I- <to~z ~-O:,) W x~o:::o () o:::)LL.u L- O:::OZU r- Cl.."""w<t O Cl..""'~1- <to<to Z wO:::l-z O:::LL.w W <tzo:::o fr'l ow<to '-J W~(/)o <:( I-~ZZ L- 0 o<t r- :,)w-w o o~~~ o ~(/)w<tz LL (.?z~EEo <toooi= w 5U;0:::1-C) 0:: o~Q~::J <:( LL."""o:::UCl.. w:::;wOCl.. ::) O:::Ol-ffi<t a <t -" ~ -" :,) -" . 0::: -" (j) o(/) <t (/) 0 <t~ 0:::-"" -"W-"O -">~zo:: <to:><tO en Q,)Q,)-" (/)10;2 ~.u ~ ~ ~ ~ I en 0 (/)calS: Q,)c8 - 'OJ) i:i: (0-- - ...enb:: OQ,)w e'au -" <( 0::: I- ~ o (/) (/) W o U -"('I')i:i:x OJ 0 LL. <t w I'- 0 LL. (.? C\I ('I') ~ z('l') ('1')0 <t-"('I')('I') 0::: LL. C\I C\I o . 00 .;2 0000 (/) Cl.. a;:> a;:> Ii) 0 I'- I'- ~o... 00 O'l<t~~ ~il' ~ c:::::J 0 ~<(rn (/) w o (.? z: o -" :,) OJ W (.? 0 I z: 00 1-. (/) :s: N Z (.?zw <tu)~ ~ (/)~Qo O:::NU) (I) . of-O o.-i=l:t: Z ffiz<tu w~lRri 0 w<t~(.? II=l:t:, ~ ~ti;!:!::z I-I-..JUl :l (.? 0::: U 0 0::: LL. U. Q. ..J zw~-" OOwz 0 wO(/)S(/)LL.ZQ.Ul (I) WZ(/)OJZOO ~C Z I:,)ZwOWi=ZO:: l-o<!:IU5<i.O:::~:J CJ LL.z....Jf->wOoa:l (i) O<tCl..IW(/)Cl..o::..; LIJ I-W-"I-O:::o-"a:I..J C ~(.?~:s:('I')Z~ 'Ul J OJO:,) 0<t:,)<C<C ..... WI->-O I-..JJ: C W:;;U-"C\lOuo::(,) ;:;:: I:>:::)Cl.. W:,)<C- ... f-00:::~~60:::(,)::!E 0 8 ~ t;; 8 :s: U5 t;;DD ii O'l o ('I') C\I o 00 ~ a;:> <t I- b(/) E ~o::: ~ ~~ 0('1') - aso~<-'<t ~~~~~ C('I'),_Jw"- co -" ~ <t I- co OLL.c;j~<t..-i ~ "I-U"" . co I'- -"-' (/)~ou!:!::..-i Q.~:::)I-O'l W ..-i 0 0::: 0::: . I- li)Q.II-WO<t O'l<tCl..(/)UZ 0 0 0 1.0 w ~ - 0 :J U1 q- r--. r- . r--. z 0 r- I l\1 0 > ID - ..J 0 III U1 r1l I 1.0 ID - > W ['l'] 1.0 - r! ['l'] r--. Q 0 I ~ I ..J ['l'] U1 l.L. r- II ~ 00 I ~ U1 I ~ W II r- ~ ~ I ~ . ~ Z 0 0 1.0 0 z W " Z v;~S:2 0 WI--V)W:J ozv)::::!< O-I> ~2!:::~v) <NWo::~ ",.-j~Oo ~o::ooO ~OWWU <lJ..I-'1-- O::Oi-l5z: O::Jo::V)~ ~;;:~OO:: ~~<~B z 0 (/) > Ii) C\J (j)wo 0:::" 1.O ZUO'l Of-" C\J <t('l') (j) Ii) Cl.. ...-i _O'lO >('1')" 0) w..-iO '~ C/) o::~~ (Y) ~ -I w -I 0 0 - ~ I z w 0 I 0::: N <( () >-LL.z Zl-O <tz- 0:: (V) zw~ L!) S r- -(/)> 0 OZo 00 t30<t I Z :,)Uo F'- lLJ -10 oz- oWO::: <(N r- o:::t:g ~ - Cl..-LL. > I wo:::-" - O:::~<t ~ Z (D wwO::: J- OJII- wO I-I-~ L!) Ol-U C/) 0:: z:::) . ~-I >-0Cl.. ~ <!:O >- <tIO::: lLJ ~!:::O ~() 0... z:S=u ::so:::w 0:: 0 w~ >- <!: Cl..zO -I () (/)ZI U 0... -<t(/) 0:: ~~:,) SHEET NO. Cl.. 0 0::: 0) 1 0 U J- w (Y) ~ 0 Z OF I ~ 25 (/) :::) lLJ ('I') 0 J- 0 > LAST PLOT DATE C\I @ 0 March 10, 2005 Z COVER SHEET -I -