CITY OF ZEPHYRHILLS
5335 - 8TH STREET
(813)780-0020
FIRE ALARM SYSTEM PERMIT
7404
Permit Number:
Permit Type:
Class of Work:
Proposed Use:
Square Feet:
Est. Value:
Improv. Cost:
Date Issued:
Total Fees:
Amount Paid:
Date Paid:
Work Desc:
7404
FIRE ALARM SYSTEM
FIRE-SUPPRESION SYS
LIGHT INDUSTRY
Address: 4330 20TH T
ZEPHYRHILLS, FL.
Township: Range: Book:
Lot(s): Block: Section:
Subdivision: CITY OF ZEPHYRHILLS
Parcel Number: 13-26-21-0070-08900-0020
12,450.00
Name: NESTLE WATERS NA, INC
Address: 4330 20TH ST
ZEPHYRHILLS, FL. 33542
130.00
130.00
3/04/2008 Phone:
INSTALL INERGEN FIRE SUPPRESSION SYSTEM ALARM
PflJ 08
if 0/ ~
I"a
FIRE ELEVATOR RECALL
Chapter 633, Florida Statutes, authorizes the City to charge and collect user fees to pay for the costs of fire
prevention and protection related activities such as inspections, plan review, administrative fees, and other
costs related to the aforementioned.
Complete Plans, Specifications and Fee Must Accompany Application. Commencement of work without written approval of
the Fire Department's Fire Marshal or required permits or opening up for commercial activity without an approved final
inspection shall be charged double permit fee per day of operation or a minimum of $100.00, whichever is greater. All
work shall be performed in accordance with City Codes and Ordinances,
"WARNING TO OWNER: YOUR FAILURE TO RECORD A NOTICE OF
COMMENCEMENT MAY RESULT IN YOUR PAYING TWICE FOR
IMPROVEMENTS TO YOUR PROPERTY. IF YOU INTEND TO OBTAIN
FINANCING, CO U T WITH YOUR LENDER OR AN ATTORNEY BEFORE
RECORDING Y UR OTICE OF COMMENCEMENT."
CONTRACTO SIGNATURE I
PE MIT EXPIRES IN 6 MONTHS WITHOUT APPROVED INSPECTlON
CALL FOR INSPECTlON - 8 HOURS NOTICE REQUIRED
ZEPHYRHILLS FIRE RESCUE DEPT - Fire Marshal Office - 813-780-0041
Fire Chief Keith Williams
ZEPHYRHILLS FIRE DEPARTMENT
6907 Dairy Road, Zephyrhills, FL 33542
Bus (813)780-0041 Fax (813)780-0044
FIRE SERVICE USER FEES
Occupancy No.:
Plan No.: /')sr ~ coY
Business Name: JUaJ;.t-k \/*J( (~w)
Business Address: Y. "3? () ;2.0~ s.. .
Business Phone No.:
Business Fax No.:
Contact:
PLAN REVIEW FEES
B Site Plan NlC
Multi-FamilylCommen:ia1 .06 sf
(Minimum Charge $25.00
o Plan Revisions DBl
INSPECTION FEES
NlC
NlC
$100
$250
$500
ARE ALARM SYSTEM
B System Acceptance $50
Recall Acceplance $50
OTHER
~ Fire Walll5molce Wall
LP Gas
Natural Gas
$15
$25
$25
per wall
per1ank
per system
$50 ~ Tent 10'x1a or gr..aer
Fire Pump
Fire Suppression
System AccepIance
B Exhaust HoodfOuct $30
Re-inspedion DBL
(other than annual)
$50 0 Inspection scheduled DBl
and cance/Ied less than
24 hours
B Construction Insp. NlC
.-h-,.,.. Emergency Vehicle Ao $50 __
PLANS TOTALLiQj INSPECTION TOTAL~
Comments:
$50
$50
$50
$50
GRAND TOTAL
$15
$45
$30
per tent
per system
per sysIem
PERMIT FEE
Sprinkler/S1f'41'~ ~
Standpipes $Sf
Fire Pump
Hoods
Fire Alarm
LP Gas
Natural Gas
FI;JE!l Tanks- pertank
Sparklers
fireWorks
Camp Fire
C0ntr0lIed Bum
HoodIDuct
Place of Assembly
Fire Protection
Flammable Application
Waste Tire Storage
Generator < KW
Generator >30 KW
BiD-Hazard waste
Fumigation Tenting
Torch Pot/Applied
Haz. Minerials
B
FALSE ALARM FEE
1st Alarm NlC
2nd Alarm N/C
3rd Alarm N/C
4th Alarm $100
5th Alarm $150
6th Alarm $200
$150
$50
$50
$50
$50
$50
$50
$100
$500
$25
$100
$50
$50 Annual
$25
$50 Annual
$50 Annual
$100
150
$100 Annual
$50
$50
$100 Annual
...-
PERMrrTOTAL~
FALSE AlARM
TOTALc=J
/30 -
Annual
1st Re-inspection
2nd Re-inspection
3rd Re-inspection
4th Re-Inspection
SPRINKLER SYSTEMS (Business closed until
B 0 - 25 Heads $50 violations corrected)
26 plus Heads $100 SPRINKLER SYSTEMS
STANDPIPE SYSTEM ~ Hydro Undergrounds $45
o Per Riser $50 Hydrostatic Test $65
FIRE PUMP . AccepIance Test $45
o Per Pump $100 Hydrant Flow $75
FIRE AlARM SYSTEM
B 0 - 25 Devices $50
26 plus Devices $100
SUPPRESSION SYSTEMS
B~~ ::
~Oth<< ~
KITCHEN EXHAUST
o HoodIDucts
OTHER
B LP InsIaIIaIion per tank
Fuel Tank Installation
(Per Tank)
o Natural Gas InslalIation
(Per System)
o spray Booth
Date:
1/17 ;&1
, ,
itrv 5r4 - r/ZL
(
Ins~ctor:
STATE OF FLORIDA
COUNTY OF PASCO
THIS IS TO CERTIFY THAT THE FOREGOING IS A
TRUE AND CORRECT COpy OF THE DOCUMENT ON ~ILE
OR OF PUBLIC RECORD IN THtSiJf-FFI , ITNESS MY
HAN NO OFFICI SEAL THIS DAY OF
2
JED A ,LER CIR COURT
BY EPUTY CLERK
11111111111111111111111111111111111111111I11111111111111111I
2008033418
Rcpt : 1165079 Rec: 10.00
DS: 0.00 IT: 0.00
03/04/08 Dpty Clerk
~~~0=~~IMAIN2" IP5ASCO COUNTY CLERK
. pm 1 of 1
OR BK 7776 PG 828
NOTICE OF COMMENCEMENT
Permit No.
Property Identification No.
THE UNDERSIGNED hereby give informs you that the improvement will be made to certain real property, and in accordance with
Section 713.13 of the Florida Statutes, the following information is provided m this NOTICE OF COMMENCEMENT.
( z-e~..,.,.tlls {!p~/JY eC/~I'~ Uh/J
l.Description of property (legal description:) 3~(" 2. 'CO?() {) 7t10() 0000 71i:ff~ Tr~.f; 8-7,~ 8'a-
a) Street Address: I't 33fS~
2.General description of improvements: r;"z~ ..s~r"'d ('/1>.# :::;jysr-J
3.0wnerInformation ~ /. L ~.-/ r- rJ /. ')/ .,c
a) Name and address: 7c.E /A...ltlfl6e.s pr~ ./f7>?.er/c.-? t;/'.3.:3b 20 JT Z"'+/J,,/,7J/Y(..5.3J'Vc)
, b) Name and address of fee simple titleholder (if other than owner) /l/h /
it ' c) Interest in property M
,Contractor Information ~ .
. a) Name and address: t/nrl'h:J ~/~ fk/,ce7?4?~ I M:!J./ /Ql:)O / dJ dfr~d ,.,,/ Sr:4./~i/'l' ~33;:Yb
b) Telephone No,: (177) ~7/ o~,t.() Fax No. (Opt.) (?v~~.?/ -QF6 /'
5.Surety Information
a) Name and address:
b) Amount of Bond:
c) Telephone No.:
6.Lender
a) Name and address:
~/4
A'A
Fax No. (Opt.)
Phone No.
7. Identity of person within the State of Florida designated y owner upon whom notices or other documents may be served:
a) Name and address:
b) Telephone No.: Fax No. (Opt.)
8.In addition to himself, owner designates the following person to receive a copy of the Lienor's Notice as provided in Section
713.13(1)(b), Florida Statutes:
a) Name and address: ./1/ M
b) Telephone No.: Fax No. (Opt.)
9.Expiration date of Notice of Commencement (the expiration date is one year from the date of recording unless a different date is
specified):
N'h
WARNING TO OWNER: ANY PAYMENTS MADE BY THE OWNER AFTER THE EXPIRATION OF THE NOTICE OF
COMMENCEMENT ARE CONSIDERED IMPROPER PAYMENTS UNDER CHAPTER 713, PART I, SECTION 713.13,
FLORIDA STATUTES, AND CAN RESULT IN YOUR PAYING TWICE FOR IMPROVEMENTS TO YOUR PROPERTY.
A NOTICE OF COMMENCEMENT MUST BE RECORDED AND POSTED ON THE JOB SITE BEFORE THE FIRST
INSPECTION. IF YOU INTEND TO OBTAIN FINANCING, CONSULT YOUR LENDER OR AN ATTORNEY BEFORE
COMMENCING WORK OR RECORDING YOUR NOTICE O(JF COMME CEMENT.
STATE OF FLORIDA - ~': DIANNKLIMPEL
COUNTY OF PASCO ~ MY COMMISSION iI 00573400
~.._~ EXPIRES: July 12, 2010 Signature 0 fymer or O~'s Autorized OfficerlDirectorlPartnerlManager
,1.J"Jl-l-NOrARY FI.NoIary~IAoooc.Co. 1trv ~
Print NalT\e
The foregoing instrument was acknowledged before me this -t- day of ~It , 20~by A ~ ~
~ ~ as ~r (type of authority, e.g. officer, trustee, attorney
in fact) for 1.ii tV'-'9"~ 46/".#14->>. (name of party on behalf of whom instrument was executed),
Pmonally Known 7'- OR Producad Identification ~ No"", Signature Ucv.Uv\... -, ~ ~'\'- r2
Typa ofldantification Prodncad Name (print) \:)' I 0. ,,\ " 0 ( >'1Il p.e J
Verification pw:s~nt to Section 92.525, Florida Statutes. Under penalties ofperjiny, I declare that I have read the foregoing and that
tha fan" ,tated m ,t ...a trua to tha b"t of my knowladga and batiar. fJJ1 'LA
Signature of Natural Person Signing Above
FORMSlNOC,rvsd2007
813-780-0020
City of Zephyrhills Permit Application
Building Department
Fax-813-780-0021
#- 1f!O~
Owner's Name
f. $1 LG'.
Owner's Address I 4330
Fee Simple Titleholder Namel
I ~ '6-0 B
'^-.b.... -t e.r ...5.
'20 (...... s-( -
Date Received
Fee Simple Titleholder Address I
I 43'"30
I
'Zo-t'h Sl-r'C"-ei-
I
B
2- H; Us.
LOT #
JOB ADDRESS
SUBDIVISION
PARCEL 10#1
(OBTAINED FROM PROPERTY TAX NOTICE)
SIGN 0 MOVE 0 DEMOLISH
PROPOSED USE
TYPE OF CONSTRUCTION
~
o
o
NEW CONSTR
INSTALL
SFR
BLOCK
OTHER
STEEL
I
o
OTHER I
WORK PROPOSED
DESCRIPTION OF WORK
//}57 -4 L. c....
I I TAGEI
"'...11..11...111..111......11...11....11....111........11..11...111.......'..111...11...11....111......111........,........11..."...,.............
D BUILDING 1$ VALUATION OF TOTAL CONSTRUCTION -111-<.. s'SO ap
D ELECTRICAL 1$
D PLUMBING 1$
D MECHANICAL 1$
D GAS c=J
FINISHED FLOOR ELEVATIONS I
BUILDING SIZE
AMP SERVICE
o
PROGRESS ENERGY
D
W.R.E.C.
I
/'
DYES
,
;JOeJ' ./
L:;~
VALUATION OF MECHANICAL INSTALLATION
ROOFING
c==J
I
SPECIALTY c=J
FLOOD ZONE AREA
OTHER
DNO
111"PI..",'I'I""""'II,,I'lll'I"I'IIIII'I'I"'"1'1""11111,"111"111,...,...,,,...,"'1"""11""""1"111'111"1111'111"11111""'"
COMPANY
REGISTERED
BUILDER
SIGNATURE
Y/N FEE CURRENT
License #
YI N FEE CURRENT
License #
Y/N FEE CURRENT
License #
YI N FEE CURRENT
Y/N
Address
ELECTRICIAN I
SIGNATURE .
Address I
PLUMBER I
SIGNATURE
Address I
MECHANICAL I
SIGNATURE .
COMPANY
REGISTERED
Y/N
COMPANY
REGISTERED
Y/N
COMPANY
REGISTERED
Y/N
, ~///
f,p C/o
Address
License #
~/e.E f?-c; "7c C' r;()'-
FEE CURRENT Y / N
License # I 900 & /j,f (JOG I~ ibu I
OTHER
SIGNATURE
Address
111111111III11I11111111111111I111111111111111111I11111I111111111111111111111I11111111111111111111111111111I111111111111111111111I11I1111I111111111
RESIDENTIAL Attach (2) Plot Plans; (2) sets of Building Plans; (1) set of Energy Forms; R-O-W Permit for new construction,
Minimum ten (10) working days after submittal date. Required onsite, Construction Plans, Stormwater Plans wi Silt Fence installed,
Sanitary Facilities & 1 dumpster; Site Work Permit for subdivisions/large projects
COMMERCIAL Attach (3) complete sets of Building Plans plus a Life Safety Page; (1) set of Energy Forms. R-O-W Permit for new construction.
Minimum ten (10) working days after submittal date. Required onsite, Construction Plans, Stormwater Plans w/ Silt Fence installed,
Sanitary Facilities & 1 dumpster. Site Work Permit for all new projects. All commercial requirements must meet compliance
SIGN PERMIT Attach (2) sets of Engineered Plans.
.".PROPERTY SURVEY required for all NEW construction,
11111111111111111 I 11111111111111111111111111111111111111111 I 111111111111111111 I 111111111111 I 1111111111111111111111111111 I 1111111111111111111111111
Directions:
Fill out application completely.
Owner & Contractor sign back of application, notarized
If over $2500, a Notice of Commencement is required. (A1C upgrades over $5000)
Agent (for the contractor) or Power of Attorney (for the owner) would be someone with notarized letter from owner authorizing same
OVER THE COUNTER PERMITTING (Front of Application Only)
Reroofs Sewers Service Upgrades NC Fences (Plot/Survey/Footage)
Driveways-Not over Counter if on public roadways..needs ROW
NOTICE OF DEED RESTRICTIONS: The undersigned understands that this permit may be subject to "deed" restrictions"
which may be more restrictive than County regulations. The undersigned assumes responsibility for compliance with any
applicable deed restrictions. '
UNLICENSED CONTRACTORS AND CONTRACTOR RESPONSIBILITIES: If the owner has hired a contractor or
contractors to undertake work, they may be required to be licensed in accordance with state and local regulations. If the
contractor is not licensed as required by law, both the owner and contractor may be cited for a misdemeanor violation
under state law. If the owner or intended contractor are uncertain as to what licensing requirements may apply for the
intended work, they are advised to contact the Pasco County Building Inspection Division-Licensing Section at 727-847-
8009. Furthermore, if the owner has hired a contractor or contractors, he is advised to have the contractor(s) sign
portions of the "contractor Block" of this application for which they will be responsible. If you, as the owner sign as the
contractor, that may be an indication that he is not properly licensed and is not entitled to permitting privileges in Pasco
County.
TRANSPORTATION IMPACT/UTILITIES IMPACT AND RESOURCE RECOVERY FEES: The undersigned understands
that Transportation Impact Fees and Recourse Recovery Fees may apply to the construction of new buildings, change of
use in existing buildings, or expansion of existing buildings, as specified in Pasco County Ordinance number 89-07 and
90-07, as amended. The undersigned also understands, that such fees, as may be due, will be identified at the time of
permitting. It is further understood that Transportation Impact Fees and Resource Recovery Fees must be paid prior to
receiving a "certificate of occupancy" or final power release. If the project does not involve a certificate of occupancy or
final power release, the fees must be paid prior to permit issuance. Furthermore, if Pasco County Water/Sewer Impact
fees are due, they must be paid prior to permit issuance in accordance with applicable Pasco County ordinances.
CONSTRUCTION LIEN LAW (Chapter 713, Florida Statutes, as amended): If valuation of work is $2,500.00 or more, I
certify that I, the applicant, have been provided with a copy of the "Florida Construction Lien Law-Homeowner's
Protection Guide" prepared by the Florida Department of Agriculture and Consumer Affairs. If the applicant is someone
other than the "owner", I certify that I have obtained a copy of the above described document and promise in good faith to
deliver it to the "owner" prior to commencement.
CONTRACTOR'S/OWNER'S AFFIDAVIT: I certify that all the information in this application is accurate and that all work
will be done in compliance with all applicable laws regulating construction, zoning and land development. Application is
hereby made to obtain a permit to do work and installation as indicated. I certify that no work or installation has
commenced prior to issuance of a permit and that all work will be performed to meet standards of all laws regulating
construction, County and City codes, zoning regulations, and land development regulations in the jurisdiction. I also
certify that I understand that the regulations of other government agencies may apply to the intended work, and that it is
my responsibility to identify what actions I must take to be in compliance. Such agencies include but are not limited to:
Department of Environmental Protection-Cypress Bayheads, Wetland Areas and Environmentally Sensitive
Lands, Water/Wastewater Treatment.
Southwest Florida Water Management District-Wells, Cypress Bayheads, Wetland Areas, Altering
Watercourses.
Army Corps of Engineers-Seawalls, Docks, Navigable Waterways.
Department of Health & Rehabilitative Services/Environmental Health Unit-Wells, Wastewater Treatment,
Septic Tanks.
US Environmental Protection Agency-Asbestos abatement.
Federal Aviation Authority-Runways.
I understand that the following restrictions apply to the use of fill:
Use of fill is not allowed in Flood Zone "V" unless expressly permitted.
If the fill material is to be used in Flood Zone "A", it is understood that a drainage plan addressing a
"compensating volume" will be submitted at time of permitting which is prepared by a professional engineer
licensed by the State of Florida.
If the fill material is to be used in Flood Zone "A" in connection with a permitted building using stem wall
construction, I certify that fill will be used only to fill the area within the stem wall.
If fill material is to be used in any area, I certify that use of such fill will not adversely affect adjacent
properties. If use of fill is found to adversely affect adjacent properties, the owner may be cited for violating
the conditions of the building permit issued under the attached permit application, for lots less than one (1)
acre which are elevated by fill, an engineered drainage plan is required.
If I am the AGENT FOR THE OWNER, I promise in good faith to inform the owner of the permitting conditions set forth in
this affidavit prior to commencing construction. I understand ~hat a s.eparate perm~t. may ?e requir~d for elect~ica.l work,
plumbing, signs, wells, pools, air conditioning, gas, or other ~nstallatrons not speCifically 1n?luded. In the application. A
permit issued shall be construed to be a license to proce~d With the work a~d not as authorl~y ~o vlol~t~, cancel, alter, or
set aside any provisions of the technical codes, nor shall Issuance of a permit prevent the B~II.dlng OffiCial from the~eaft~r
requiring a correction of errors in plans, c~n~truction or violat~o~s o! any codes. Eve'!' ~ermlt Issued. shall become. invalid
unless the work authorized by such permit IS commenced Within SIX months of permit Issuance, or If work authOrized by
the permit is suspended or abandoned for a period of six (6) months after the time th~ work is commenced: An extension
may be requested, in writing, from the Building Officia~ for a period not t~ exceed nln~ty (,90) da~s and Will demonstrate
justifiable cause for the extension. If work ceases for ninety (90) consecutive days, the\Job IS conSidered abandoned.
WARNING TO OWNER: YOUR FAILURE TO RECORD A NOTICE OF COMMENCEMENT MAY RESULT IN YOUR
PAYING TWICE FOR IMPROVEMENTS TO YOUR PROPERTY. IF YOU INTEND TO OBTAIN FINANCING, CONSULT
WITH YOUR LENDER OR AN ATT NEY BEFORE RECORDING YOUR NOTICE OF COMMENCEMENT.
FLORIDA JURAT (F.S, 117.03)
OWNER OR AGENT eLl!. <!..JL L.-- ../
S bribed and sworn to (or affirmed) before me this
I () by r-lIl~ n L hb-r1 /t..J
o Is!. lJrE! personally known to me or has/have produced
i- ...~-!:::J. (P~ as identification.
CONTRACTOR
Subscribed and swom to (or affirmed) before me this
by
Who is/are personally known to me or has/have produced
as identification.
Notary Public
Notary Public
Commission No.
Name of Notary typed. printed or stamped
Zephyrhills Fire Rescue
6907 Dairy Road, Zephyrhills, FL 33542
Fire Marshal
Kerry Barnett
Bus (813) 780-0041
Fax (813) 780-0044
January 18,2008
I have reviewed and approved the plans for a fire suppression system located at 4330 20th
Street for Nestle Water. I have attached the comments for the plan approval. If there are
any questions please contact my office at 813-780-0041.
1. NFP A 72, 2007 edition shall be used with this project.
2. Ensure proper seal is used on firewall penetrations.
Inspections Required
1. Copy of pressure test on piping shall be given to Fire Marshal at time of
acceptance test.
2. Acceptance test
1A:J,f11l~:p~ 1]:) S]J1Ffjjid :J-J'iJ2:iiril
iF].p@:pPy:S'fj!iUJJ~J)
FIRE SUPPRESSION SYSTEM
FOR:
Building shall comply with
, Ie c of
NF'~):,\ ,e ~ ';.::'1
. '"~ .I.... _. C',- ....~ i, \0..
'jtn:, Handbook
. i_ L:;phyrhills
APPROVED
by Fire Mar~ha! of Zephyrhills
wi~rOVided with plan(s}
L/ ~ ///1 {iJ~
NESTLE WATERS
4330. 20th Street ~1+t<f01
ZephyrhiIIs, ~L 33540
.--
)(~
/~'7,t? ;>
Headquarters ~
12001 31st Court N.- St. Petersburg, FL 33716 - (727) 471-0860 - Fax (727) 471-0861
www.united-fire.com
..:s,..: -.-
The AUTOPULSE'! 542R is a six zone FACP lor single and dual hazard
agent releasing applications. The AUTOPULSE 542R provides reliable
lire detection, signaling and protection lor commercial, industrial and
institutional buildings requiring agent-based releasing. The AUTOPULSE
542R is compatible with System Sensor's i3 detectors which are
conventional smoke detectors that can transmit a maintenance trouble
signal to the FACP indicating the need for cleaning and a superviSOry
'freeze' signal when the ambient temperature falls below the detector
rating of approximately 45 of (7.22 OC), In addition, the control panel is
compatible with conventional input devices such as two-wire smoke
detectors, four-wire smoke detectors, pull stations, waterflow devices,
tamper switches and other normally-open contact devices. Refer to
Device Compatibility Document for a complete listing of compatible
devicQs."
Four outputs are programmable as NACs (Notification Appliance
Circuits) or releasing circuits. Three programmable Form-C relays
(factory programmed for Alarm, Trouble and SuperviSOry) and 24 VDC
special application resettable and non-resettable power outputs are also
included on the main circuit board. The AUTOPULSE 542R supervises
all wiring, AC voltage, battery charger and battery level.
Activation of a compatible smoke detector or any normally open fire
alarm initiating device will activate audible and visual signaling devices,
illuminate an indicator, display alarm information on the panel's LCD,
sound the piezo sounder at the FACP, activate the FACP alarm relay
and operate an optional module used to notify a remote station or initiate
an auxiliary controllunction. .
The AUTOPULSE 542R(E) releasing panel offers the same features as
the AUTOPULSE 542R but allows connection to 220/240 VAC, Unless
otherwise specified, the information in this data sheet applies to both the
110/120 VAC and 220/240 VAC versions of the panels,
",
. Designed for agent releasing standards NFPA 12, 12A, 12B and 2001
. Disable/Enable control per input zone and output zone
. Extensive transient protection
. Dual hazard operation
. Adjustable pre-discharge, discharge and waterflow delay timers
. Cross-zone (double-intertock) capability
. Six programmable Style B (Class B) iDCs (Initiating Device Circuit)
. System Sensor 13 series detector compatible
. Four programmable Style Y (Class B) output circuits - (special appli-
cation power)
. Strobe synchronization
- System Sensor
- Wheelock
- Gentex
- Faraday
- Amseco
. Three programmable Form-C relays
. 7,0 amps total 24 VDC output current
. Resettable and non-resettable output power
. Built-in Programmer
. Short circuit RAC supervision
00,.,.11
. ANN-BUS for connection to optional (up to eighttOlal of any of the
following):
- N-ANN-80 Remote LCD Annunciator
- N-ANN-I/O LED Driver
- N-ANN-S/PG Printer Module
- N-ANN-RL Y Relay Module
_ N-ANN-LED Annunciator Module
. 80-character LCD display (backlit)
. Real-time clock/calendar with daylight savings time control
. History log with 256 event storage
. Piezo sounder for alarm, trouble and supervisory
. 24 volt operation
. Low AC voltage sense
. Outputs programmable for:
- Releasing Circuits
. NACs programmable for:
- Silence Inhibit
- Auto-Silence
- Strobe Synchronization
_ Selective Silence (horn-strobe mute)
- Temporal or Steady Signal
- SilenceabJe or Non-silenceable
- Release Stage Sounder
. Automatic battery charger with charger supervision
. Optional Dress Panel DP-510SO (red)
. Optional Trim Ring TR-CE (red) lor semi-flush mounting the cabinet
. Optional CAC-5X Class A Converter Module for Outputs and IDCs
. Optional 4XTM Municipal Box Transmitter Module
. Optional Digital Alarm Communicators (411, 411UD, 411UDAC)
- :>.;
PROGRAMMING AND SOFTWARE:
. Custom English labels (per point) may be manually entered or
selected from an intemallibrary file
. Programmable Abort operation
. Three programmable Form-C relay outputs
. Pre-programmed and custom application templates
.. Continuous fire protection during online programming at the front
panel
. Program Check automatically catches common errors not linked to
any zone or input point
USER INTERFACE:
. Integral 80-character LCD display with backlighting.
. Real-time clock/calendar with automatic daylight savings adjustments.
. ANN-Bus for connection to remote annunciators.
. Audible or silent walk test capabilities.
. Piezo sounder for alann, trouble, and supervisory.
CON11lOL5 AND INDICATORS
LED INDICATORS
. FIRE ALARM (red)
. SUPERVISORY (yellow)
. TROUBLE (yellow)
. AC POWER (green)
. ALARM SILENCED (yellow)
. DISCHARGED (red)
. PRE-DISCHARGE (red indicator)
. ABORT{yellow indicator)
CONTROL BUTTONS
. ACKNOWLEDGE
. ALARM SILENCE
. SYSTEM RESET (tamp test)
. DRILL
AC Power-TB1
. AUTOPULSE 542R: 120 VAC. 50/60 Hz, 2.3 amps
. AUTOPULSE S42R{E): 240 VAC, 50 Hz, 1.15 amps
. Wire size: minimum #14 AWG (2,O mm2) with 600V insulation
. Supervised, nonpower-Iimited
Battery (sealed lead acid only) - J12:
. Maximum Charging Circuit - Normal Flat Charge: 27.6 VDC @
1.4 amp Supervised. nonpower-limited
. Maximum Charger Capacity: 26 Amp Hour battery (two 18 Amp
Hour batteries can be housed in the FACP cabinet. Larger batteries
require separate battery box such as the BB-26 or BB-55).
. Minimum Battery Size: 7 Amp Hour
Initiating Device Circuits - 104 ana I 00
. Alann Zones 1 - 5 on TB4
. Alarm Zone 6 on TB6
. Supervised and power-limited circuitry
. Style B (Class B) or Style Z (Class A) with optional converter module
. Normal Operating Voltage: Nominal 20 VDC
. Alarm Current: 15 mA minimum
. Short Circuit Current: 40 mA maximum
. Maximum Loop Resistance: 100 Ohms
. End-of-Llne Resistor: 4.7K Ohms. 1/2 watt (Part No. 71252)
. Standby Current: 4 mA
Notification Applance and Releasing Clrcult(s) - TBS and TB7
. Four output circuits
. Style Y (Class B) or Style Z (Class A) with optional converter module
. Special application power
. Supervised and power-limited circuitry
. Normal Operating Voltage: Nominal 24 VDC
. Maximum Signaling Current: 7.0 amps (3.0 amps maximum per
NAC)
. End-of-L1ne Resistor: 4.7K Ohms. 1/2 watt (Part No. 71252)
. Maximum Wiring Voltage Drop: 2 VDC
Refer to the Device Compatibility Document for compatible listed
devices.
Form-C Relays - Programmable - TB8
. Relay 1 (factory default programmed as Alarm Relay)
. Relay 2 (factory default programmed as fail-safe Trouble Relay)
. Relay 3 (factory default programmed as Supervisory Relay)
. Relay Contact Ratings:
- 2 amps @ 30 VDC (resistive)
- 2 amps @ 30 VAC (resistive)
Auxiliary Trouble Input - J6
The Auxiliary Trouble Input is an open collector circuit which can be
used to monitor external devices for trouble conditions. It can be
connected to the trouble bus of a peripheral, such as a power supply,
which is compatible with open collector circuits,
Special Application Resettable Power - TB9
. Operating Voltage: Nominal 24 VDC
. Maximum Available Current: 500 mA - appropriate for powering
4-wire smoke detectors (see Note 1)
. Power-limited circuitry
Note 1: Total current for resettable power, nonresettable power and
output circuits must not exceed 7.0 amps.
Special Application Resettable or Nonresettable Power - TB9
. Operating Voltage: Nominal 24 VDC
. Maximum Available Current: 500 mA (see Note 1)
. Power-limited circuitry
. Jumper selectable by JP31 for resettable or nonresettable power
PRODUCT UNE INFORMATION
AUTOPULSE 542R: Six zone, 24 volt Agent Release Control Panel
(includes backbox, power supply, technical manual, and a frame & post
operating instruction sheet) for single and dual hazard deluge and
pre action applications,
AUTOPULSE 542R(E): Same as above but allows connection to
220/240 VAC.
CAC-5X: Class A Converter Module can be used to convert the Style B
(Class B) Initiating Device Circuits to Style 0 (Class A) and Style Y
(Class B) Output Circuits to Style Z (Class A).
Note: Two Class A Converter modules are required to convert all four
Output Circuits and six Initiating Device Circuits,
4XTM: Transmitter Module provides a supervised output for local energy
munidpal box transmitter and alann and trouble reverse polarity. It
includes a disable switch and disable trouble LED.
N-ANN-80: LCD Annunciator is a remote LCD annunciator that mimics
the information displayed on the FACP LCD display. Recommended wire
type is un-shielded.
N-ANN-LED: Annunciator Module mounts in the DP-51050LED Dress
Panel and provides three LEOs for each zone: Alarm, Trouble and
Supervisory.
N-Ablt+-RLY: Relay Module, which can be mounted inside the cabinet,
provides 10 programmable Form-C relays.
N-ANN-SIPG: SeriallParallel Printer Gateway module provides a
connection for a serial or parallel printer.
N-ANN-VO: LED Driver Module provides connections to a user-supplied
graphic annunciator.
DP-S10S0: Dress panel (red) is available as an option. The dress panel
restricts access to the system wiring while allowing access to the
membrane switch panel.
DP-S10S0LED: Dress panel is available as an option. The dress panel
restricts access to the system wiring while allowing access to the
membrane switch panel. It also allows the installation of an optional
ANN-LED annunciator module,
TR-CE: Trim-ring (red) Is available as an option, The trim-ring allows
semi-flushing mounting of the cabinet.
8B-26: Battery box, holds up to two 26 Amp Hour batteries and
CHCH5.
BB-S5: Battery box, houses two 55 Amp Hour batteries,
BAT Series Batteries
:::::I . ..:- .
SYSTEM CAPACITY
. Annunciators: 8
ELECTRICAL SPECIFICATIONS
. AUTOPULSE 542R (FLPS-7 power Supply): 120 VAC, 50/60 Hz,
2,3 amps
. AUTOPULSE 542R(E) (FLPS-7 Power Supply): 240 VAC, 50 HZ,
1.15 amps
. Wire size: minimum 14 AWG (2.0 mm2) with 600 V insulation, super-
vised, non power-limited .
CABINET SPECIFICATIONS
Door: 19.26 in. (48.92 cm) high x 16,82 in, (42.73 cm) wide x 0,72 in.
(1.82 cm) deep
Backbox: 19.00 in, (48,26 cm) high x 16.65 in. (42.29 cm) wide x
5.25 in. (13.34 cm) deep
Trim Ring (TR- CE):22.00 in. (55,88 cm) high x 19,65 in. (49.91 cm)
wide
SHIPPING DIMENSIONS
_ Height: 20.00 in. (SO.80 em)
_ Width: 22,50 in. (57.15 cm)
_ Depth: 8.50 in, (21,59 cm)
TEMPERATURE AND HUMIDITY RANGES
This system meets NFPA requirements for operation at 32-120 OF
(049 OC) and at a relative humidity 93%:1: 2%.RH (non-condensing) at
90 of:!: 3 "F (32 "C :I: 2 oc). However, the useful life of the system's
standby batteries and the electronic components may be adversely
a fEcted by extreme temperature ranges and humidity. Therefore, it is
recommended that this system and its peripherals be installed in an
environment with a normal room temperature of 60-80 OF (15-27 OC).
NFPA STANDARDS
_ NFPA 12 CO2 Extinguishing Systems (High Pressure Only)
_ NFPA 12A Halon 1301 Extinguising Systems
_ NFPA 72 National Fire Alann Code for Local Fire A1ann Systems and
Remote Station Fire A1ann Systems (requires an optional Remote
Station Output Module)
_ NFPA 2001 Clean Agent Fire Extinguishing Systems
LISTINGS AND APPROVALS
The listings and approvals below apply to the basic AUTOPULSE 542R
and AUTOPULSE 542R(E) control panels. In some oases, certain
modules may not be listed by certain approval agencies, or listing may
be in process, Consult factory for latest listing status.
. UL: 54935
ORDERING INFORMAnON
Part No,
433605
433606
Description
AUTOPULSE 542R FACP, 120 VAC
AUTOPULSE 542RE FACP, 220/240 VAC
..
..
ANSUL and AU TCPJLSE are lrademarks of AnN Incorporated or its affiliates.
November 29, 2004
DN.6933 . E.205
@)NOTIFIER@
BAT Series Batteries
Sealed Lead-Acid or Gell Cell
Section: Power Supplies
GENERAL
BAT Series Batteries feature a new part-numberingllist-
ing system - providing an improved method of delivery
for NOTIFIER-approved sealed lead-acid batteries for all
your fire alarm system needs. Multiple brands of batteries
are now offered under generic part numbers, reducing
backorder situations and permitting us to deliver these prod-
ucts in a more timely fashion. NOTIFIER has approved the
multiple brands listed below as possible product shipped
for a given part number. Please note that any incoming
orders for .PS Series. batteries will be converted to the
equivalent BAT Series part numbers.
'i\I
M H 19884 (8 & B Battery)
MH20727 (Jolt)
MH20845 (Power-Sonic)
. Provide secondary power for control panels.
Sealed and maintenance-free.
. Overcharge protected.
. Easy handling with leakproof construction,
. Ruggedly constructed, high-impact case (ABS, polysty-
rene, or polypropylene, depending on models).
. long service life.
. Compact design.
&933ke Ubi 8933c:oy,jpg
PREVIOUS CURRENT BATTERY ALTERNATES APPROVED:
manufacturers and PINs
Part Number Part Number DESCRIPTION shipped under BAT PINs
PS-1250 BAT-1250 12 V, 5 AH, sealed. BP5-12 (B&B Battery), PS-1250
(Power-Sonic), SA 1250 (Jolt).
PS-1270 BAT-1270 12 V, 7 AH, sealed. BP7-12 (B&B Battery), PS-1270
(Power-Sonic), SA 1272 (Jolt).
PS-12120 BAT-12120 12 V, 12 AH, sealed. BP12-12 (B&B Battery), PS-12120
(Power-Sonic), SA12120 (Jolt),
PS.12170 BAT-12180 12 V, 18 AH, sealed. PS-12180 (Power-Sonic),
SA12180 (Jolt),
PS-12180 BAT-12180 12 V, 18 AH, sealed. PS-12180 (Power-Sonic),
SA12180 (Jolt).
PS-12250 BAT-12260 12 V, 26 AH, sealed. BP26-12 (B&B Batte~). PS-12260
(Power-Sonic), SA 12 60 (Jolt),
PS-1242 BAT-1250 12 V, 5 AH, sealed. BP5-12 (B&B Batte~), PS-1250
(Power-Sonic), SA 1 50 (Jolt).
PS-12550 BAT-12550 12 V, 55 AH, sealed. PS-12550 (Power-Sonic),
XSA 12550 (Jolt).
PS-12600 BAT-12550 12 V, 55 AH, sealed. PS.12550 (Power-Sonic),
XSA 12550 (Jolt).
PS-612 Discontinued N1A N/A
PS-12750 Discontinued N1A N1A
PS-695 PS-695 6 V, 9.5 AH, gell cell. N1A (Power-Sonic only).
PS-121000 BAT-121000 12 V, 100 AH, gell cen, PS-121000 (Power-Sonic),
XSA121000A (Jolt).
.. fEATURES
NOTlFIERiID is a Honeywell company.
This document is not Intended to be used for Installation purposes. We try to keep our
product Information up-to-date and accurate. We cannot cover all specific applications or
anticipate all requirements. All specifications are subject to change without notice.
For more information, contact NOTIFIER. Phone: (203) 484-7161 FAX: (203) 484.7118
@) NOTI FI E R~ 12 Cllntonvllle Road, Northford, Connecticut 06472
ISO 9001
1I:~=I:II..::II.DI..1
ENCINlEIIN; . MAHUFAC111I1NG
QUALITY SYSTEMS
DN.6933 . 11/29/04 - Page 1 of 8
POWER.SONIC
"Oll1tbl
Nominal Discharge DIMENSIONS
Capacity Current Height over
Nominal @ @ Width Depth Height terminal Weight
Voltage 20 hr. rate 20 hr. rate
MODEL V A.H. mA In. mm. In. mm. In. mm. In. mm. Ibs. kg.
PS.695 6 9.5 475 4.26 108 2.75 70 5.54 141 5.54 141 4.9 2.2
PS.1250 12 5.0 250 3,54 90 2,76 70 4,02 102 4.21 107 4.1 1,9
PS.1270 12 7.0 325 5.94 151 2.56 65 3.70 94 3.86 98 5,7 2.6
PS-12120 12 12 600 5.94 151 3.86 98 3.70 94 3.86 98 8.8 4.0
PS.12180 12 18 875 7.13 181 2.99 76 6,57 167 6.57 167 12.8 5.8
PS.12250 12 25 1300 6.89 175 6,54 166 4.92 125 4.92 125 18.7 8.5
PS.12550 12 55 3000 10.25 260 6.60 168 8.20 208 9.45 240 39.7 18.0
PS.121000 12 100 5000 12.00 305 6.60 168 8.20 208 9.45 240 65.7 29.8
.. 6.5 13
~ 6.0 12
.,
01
~ 5.5 11
~
2:- 5.0 10
.,
r:
'"
a3 4.5 9
4.0 8
0
r I I I 1 I
- r-..
r--;;: -
r-- t- r- " -.... '\ \ r\ \ \
- '"
\ 1\ L.. _ 1.Q.C
, O.175C O.5C
\ " O.2~C
'nRr
f
I
: 3C 2C - lC
..
;;:
~
120%
Effect of Temperature on Capacity
..... .0.5 C
.... .0.1 C
Characteristic Discharge Curves
100%
,Q 80%
iii
~ "
"
?;o 60%
'0
III
0..
~ 40% ",
",
E
.
f
20% .'
2 3 5 10 2030 60 2 3 5 10 20 30
minutes I hours ---1
Discharge Tome @ 20'C (68'F)
"
"
0%
-20' -10'
O' 10' 20' 30' 40' 50' 60'
Temperature (Degrees C.)
90%
Charging Is NOT
necessary un/e..
100~. 01 capacity
is required,
100%
.Q
iii 80%
~
c
.2 70%
C'
CI)
4i
~ 60%
?;o
'0
11 50%
III
u
40%
0%
0 2 4
Charging before
US" is necessary
to help roccver
full capacily.
...lIIIIIl PS-121000
~ Shelf-Life
and Storage
Chars" may
fail to reslore
~~ ~g~city, E
.
let balleries ~
reach IIlis slate f
6 8 10 12 14 16 18 20
Standing Perlod (Months)
14.0V
13.0V
CI) 12.0V
01
2l
;g 11.0V
iii
c
E 10.0V
~
g.ov
8,OV
1.2 2.4
Ambient Temperature 20'C (6S'F)
E
.
~
~
...lIIIIIl PS-121000
~ Discharge
Characteristics
~ IIAloIO ..CMAIItG...."'.
...'fUI.
POll/ERe Sl1NIt'
.....1 r'....
. .,.It . S "'"
....'.I...I!. Ca,..'.'i.'"
6 12 24 3618 1 2 4 6 8 10 20 40
MINUTES )( HOURS
Discharge Time
PS-695
Page 2 of 8 - ON-6933' 11/29/04
B & B BAnERY
'933bbb 1 lbl
Nominal Capacity (AH) Weight Terminal Dimensions
Model V Standard Optional L W H TH
20 hr 10 hr 5 hr 1 hr kg Ibs Type Pos. Type Pos. mm In mm In mm In mm In
6P5-12 12 5.00 4.75 4.25 3,00 1.86 4,10 T1 3 12 90 3.54 70 2.76 102 4.02 106 4.17
6P7-12 12 7.00 6.65 5.95 420 2.00 5.73 I 12 5 Tl 151 5.94 65 2.56 93 3.66 98 3.86
6P12.12 12 12,00 11.40 10,20 7.20 4,03 8.89 I 61 5 T1 151 5.94 98 3.86 94 3.70 98 3.86
6P26-12 12 26.00 24.70 22.10 15,60 9,40 20,13 61 7 12.11 9 175 6,89 166 6.54 125 4,92 125 4.92
Temperature Maximum Charging time 0,1 CA,
Charging compensation charging 20.C (h)
Application Charging method voltage at coefficient of current Temp (.C)
20.C (V/cell) charging voltage (eA) 100% 50%
(mVrC/cell) discharge discharge
For standby Constant voltage and 2.25 - 2,30 -3 0.3 24 20
power source constant current o - 40.C
For cycle charging (with current 2.40 - 2.50 -4 0.3 16 10 (32- 104 'F)
service restriction)
Temperature compensation of charging voltage is not needed Men using the batteries 'Aithin S'C to 3S'C range.
Charging Procedure
Discharge Time
Final 5 min 10 min 15 min 30 min 1 hr 3 hr 5 hr 10 hr 20 hr
Voltage Battery Output Power (W)
10.80 V 180.8 133,1 106,6 63,5 36.39 14.57 10.05 5.62 2.94
10.50 V 209.2 144,2 111.5 65.9 37.48 14,87 10,20 5.70 3,00
10.20 V 222.3 149.4 115.0 67,4 38.16 15,00 10.26 5,73 3.01
9.90 V 232.3 152,9 117,6 68.3 38,61 15.10 10.29 5.75 3.02
9.60 V 240.0 156.0 120,0 69.0 39,00 15.20 10.32 5.75 3.02
1933bb05.lllI
Discharge Time
Final 5min 10 min 15 min 30 min 1 hr 3 hr 5 hr 10 hr 20 hr
Voltage Battery Output Power (W)
10.80 V 253,1 186.3 149.3 88.8 50.95 20.40 14.07 7.86 4.11
10.50 V 292.9 201.8 156,2 92.2 52.47 20,81 14.28 7.98 4.20
10.20 V 311.2 209.1 161,0 94,3 53.42 21.00 14,36 8.02 4.22
9.90 V 325.2 214.1 164.7 95.6 54.06 21.15 14.41 8,04 4.23
9.60 V 336.0 218.4 168,0 96.6 54.60 21.27 14.45 8.04 4.23
1933l1b01.lllI
Discharge Time
Final 5min 10 min 15 min 30 min 1 hr 3 hr 5 hr 10 hr 20 hr
Voltage Battery Output Power (W)
10,80 V 433,9 319.4 256.0 152.3 87,34 34.98 24,12 13.48 7.05
10,50 V 502,2 346.0 267.7 158.1 89.96 35.68 24.48 13.68 7.20
10.20 V 533.6 358,5 276.0 161,7 91.57 36,00 24.61 13,75 7.23
9.90 V 557.5 367.1 282.4 164.0 92.67 36.25 24.70 13.79 7.25
9,60 V 576,0 374.4 288.0 165.6 93,60 36.47 24.71 13,79 7.25
1933bb'2.lbl
Discharge Time
Final 5min 10 min 15 min 30 min 1hr 3 hr 5 hr 10 hr 20 hr
Voltage Battery Output Power (W)
10,80 V 940,0 692.0 554,6 330.0 189.23 75.79 52.25 29,20 15,26
10.50 V 1088.0 749.7 580,0 342.5 194,91 71.30 53.04 29.64 15,60
10.20 V 1156.0 716.7 598.0 350.3 198.41 78.00 53.33 29,79 15.67
9.90 V 1208.0 795.3 611.8 355.2 200.79 78.54 53.,52 29,88 15.71
9,60 V 1248.0 811.2 624,0 358.8 202,80 79.01 53.68 29,88 15.71
1933bb21lbl
1933bbc:I\ Ibl
at left:
Constant Power Discharge
Characteristics a-t 25ocn70F
for BP5-12
at left:
Constant Power Discharge
Characteristics at 25ocn70F
for BP7-12
a t left:
Constant Power Discharge
Characteristics at 25ocn70F
for BP12-12
a t left:
Constant Power Discharge
Characteristics at 25ocn70F
for BP26-12
DN-6933 . 11/29/04 - Page 3 of 8
B & B BAnERY
BPS.12 battery discharge characteristics (2S0Cn70F)
13.3 I
I
................~
'\ \ '\ \
---.....
120 r---..... --......... .....,0'" """
"-
\1 \
~
w
~ 110
~
~ .00
-'
<<:
z
:E 90
CI:
W
1-
__ oiis;;'-0"is..-02s.>
1.25>'
3A
I
I
I
80
,5->-'oA - SA
I
2 3 5 '0 20 30
hours I
10
2 3 5 '0 20 30 80
minutes I
8PQSdil.Ii'
DISCHARGE TIME
., "
BP12.12 battery discharge characteristics (2soC/710F)
13.0
I
- ....... r::: :--... r.....
-
- ~ "'"'" ~ '\ \ \ "\ '\
I-- ............
'\ A , 04iiiTliA--O.6A
J;~: ,
I
I
I
I
12.;;' -- '21\
12.0
~
w
o 11.0
~
~ 100
-'
<<:
z
:E 9.0
a:
w
1-
80
1.0
,
l
\0 20 30
J
2 3
5 '0 20 X 60 2 3 5
minutes I hours
DISCHARGE TIME
BP12dil.tif
8P5-12
BP7.12 battery discharge characteristics (2soCI710F)
13.3
I I
- ........ r--..... 1---... -.......
- -
I-- ...... " """ "- \ '\ '\
- -..... :'"
\ \ '\gJ. -o.~;;. -0 3S-'
--
1.1SA
, ,
,
4.2A
I
I
I
- 1A -
2t \....
\2.0
~
w
~ 11.0
~
~ 100
-'
<<:
z
:E 90
a:
w
1-
80
1.0
2 3 5 '0 20 30
hours I
2 3 5 10 20 30 60
minutes I
8P07dil.lif
DISCHARGE TIME
BP26.12 battery discharge characteristics (2S0Cn70F)
13.0
I I I I I
- r--.. ........... --..... ........
i-- ............
I-- - r---.. ~ '" """ "- \ "\ \
\ \ \ ," 4..i2A - 2.47A -'.3A
.SA
, ,
1~.8A
, I
I
1f 52A - 261.
12.0
~
w
o 11.0
~
g 10.0
:i!
z
~ 9.0
a:
UJ
....
80
1.0
\
I
2 3
5 \02030 60 235
minutes I hours
DISCHARGE TIME
'0 20 30
I
8P2ldis.lif
BP26-12
Page 4 of 8 - DN-5933" 11129104
JOLT BAnERY
SA1250
SA12S0 discharge current vs time
T~
!h
... ;,.,1-1) 1~
L:
I I ,
I I I I
I I,,"
O"C{32'F) ~ \. ~C('04"F)
-
'-"
.,
,-
, "-
o &:10 I 2 3
~-(",^I · r
5 10 21 30 &:I 100 200
1'1
,I
C....renl
... ...
u
~ 12
& 11
.
~
1 ~
;! 9
I 2 3 5 10 21 JJ II] 2 3 6 to :n JO
..I~ 'I-~. .,
SA1250 SPECIFICATIONS
. Nominal voltage: 12 V.
. Nominal capacity (20 hr): 5,0 AH.
. Dimensions: total height 107 mm (4.21 in); container
height 101 mm (3.98 in); length 90 mm (3.54 in); width
70 mm (2,76 in).
. Weight: approximately 1.83 kg (4.03 Ibs).
. Container material: UL94HS ASS, UL94V-0 ASS.
. Internal resistance (250C, 770F): - 32 m.
. Discharge capacity under different temperatures:
40oC: - 102%
250C: - 100%
ooC: - 85%
. Capacity 250CI770F:
20 hr @ 0.25 A: 5.0 AH.
5 hr @ 0.8 A: 4.0 AH.
1 hr @ 3.0 A: 3.0 AH.
1 C@5.0A:2.5AH.
. Charging voltage (250C, 770F):
Standby use: 13.65 V :t 0.15 V.
Cycle use: 14.7 V :t 0.3 V.
. Maximum discharge current: 60 A (5 see).
. Maximum charging current: 1.5 A.
. Self-discharge residual capacity (250C, 770F):
After 3 months: - 90%.
After 6 months: - 82%.
After 12 months: - 70%.
SA 1272
SA1272 d
T~
(h) 2
.l,
J 1:
~ !mit) 10
t
ischarQe current vs time
1 I I I 1 I
I '"~ I I IT
I l\: I I I I
O'C~"h '-""- .cO"C(I04"F)
"
"
"
o 51(l I 22
I---lmAl 'It
5 10 :11:11 51 100 200
(AI -I
C....rent
SA 1272 discharge characteristics (2soCI770F)
II
~12
.
i' 11
~
"Il 1O
J 9
2 J 5 10 21:11 II] 2 1 5 to 2130
mil' I-h
DischlIrge rme
SA1272 SPECIFICATIONS
. Nominal voltage: 12 V.
. Nominal capacity (20 hr): 7.2 AH.
. Dimensions: total height 100 mm (3.94 in); container
height 94 mm (3.70 in); length 151 mm (5.95 in); width
65 mm (2.56 in).
. Weight: approximately 2.66 kg (5.85 Ibs).
. Container material: UL94HS ASS, UL94V-0 ASS.
. Internal resistance (250C. 770F): - 22 m.
. Discharge capacity under different temperatures:
40oC: - 102%
250C: - 100%
ooC: - 85%
. Capacity 250CI770F:
20 hr @ 0.36 A: 7.2 AH.
5 hr @ 1.15 A: 5.76 AH.
1 hr @ 4.32 A: 4.32 AH.
1 C @ 7.2 A: 3.6 AH.
. Charging voltage (250C, 770F):
Standby use: 13.65 V:t 0.15 V,
Cycle use: 14.7 V :t 0.3 V.
. Maximum discharge current: 90 A (5 see).
. Maximum charging current: 2.16 A.
. Self-discharge residual capacity (250C. 770F):
After 3 months: - 90%.
After 6 months: - 82%.
After 12 months: - 70%.
ON-6933 . 11/29/04 - Page 5 at 8
JOLT BAnERY
SA12120
SA12120 discharge current vs time
I:
('II 2
~ ,
T~
~ 20
1= (..I~, 10
L:
I I I -T I I
I I I I I I
1""'- T II
0"C{32'F)"\ .o'C1104"1')
'"
'..,
~
o 5oD' 2 3 5 10 20 Xl 50 '00 3)0
~(",^l '1' IAI .1
Cut. nl
SA 12120 discharge characteristics (2soC/71"F)
"
l]
~12
.,
~ "
~
'! \0
i
o
2 3 5 10 3)3> eo 2 3 5 10 203:1
"'~ I-ft
Oischarll' lime
SA12120 SPECIFICATIONS
o Nominal voltage: 12 V.
o Nominal capacity (20 hr): 12.0 AH.
o Dimensions: total height 100 mm (3.94 in); container
height 94 mm (3.70 in); length 151 mm (5.95 in); width
98 mm (3,86 in).
o Weight: approximately 4.10 kg (9.04 Ibs).
o Container material: UL94HS ASS, UL94V-0 ASS.
o Internal resistance (250C. 770F): - 14 m.
o Discharge capacity under different temperatures:
40oC: - 102%
2SoC: - 100%
ooC: - 85%
o Capacity 250CrT70F:
20 hr @ 0.6 A: 12.0 AH,
5 hr @ 1.92 A: 9.6 AH.
1 hr @ 7.2 A: 7.2 AH.
1 C @ 12.0 A: 6.0 AH.
o Charging voltage (2SoC. 770F):
Standby use: 13.65 V :I: 0.15 V.
Cycle use: 14,7 V :I: 0.3 V.
o Maximum discharge current: 120 A (5 see).
o Maximum charging current: 3.6 A.
o Self-discharge residual capacity (250C, 770F):
After 3 months: - 90%.
After 6 months: - 82%.
After 12 months: - 70%.
Page 6 of 8 - DN.6933' 11/29/04
SA12180
SA12180 discharge current vs time
f~
1"1 2
..l,
1 ~
.1
"r
I I I I
II ~I I I I
I ~ I I I
O'C(32'1=) ~ oIO"CI1004"1')
~
~
~
'\.'
I'
--..: :;;:;::, t-,.--
- r....... '\ r\'-. , \
-
\ \ \ _ i.- uiiA O.io\
L -5(~ ~u. ~ 10~; I Z. dA
-
I
o 530' 23
~_(nw\1 'I'
5 10 20 Xl !il lOG 200
cr.1
CUT en!
SA12180 discharge characteristics (2S0CmOF)
lJ
_ '2
C:.
& 11
.I!
j
-I '0
{J .,
o
123510 3)l) dO 23510 3)3Q
mln
D_ga Tine
~
SA12180 SPECIFICATIONS
o Nominal voltage: 12 V.
o Nominal capacity (20 hr): 18.0 AH.
o Dimensions: total height 167 mm (6.S8 in); container
height 167 mm (6.58 in); length 181 mm (7.13 in); width
76 mm (2.29 in).
o Weight: approximately 6.06 kg (13.36 Ibs).
o Container material: UL94HS ASS. UL94V-0 ABS,
o Internal resistance (250C. 770F): - 13 m.
o Discharge capacity under different temperatures:
40oC: - 102%
250C: - 100%
ooC: - 85%
o Capacity 2soCrT70F:
20 hr @ 0.9 A: 18.0 AH.
5 hr @ 2.88 A: 14.4 AH.
1 hr @ 10.8 A: 10.8 AH.
1 C @ 18.0 A: 9.0 AH.
o Charging voltage (250C. 770F):
Standby use: 13.65 V :I: 0.15 V.
Cycle use: 14.7 V :I: 0.3 V.
o Maximum discharge current: 300 A (S see).
o Maximum charging current: 5.4 A.
o Self-discharge residual capacity (250C, 770F):
After 3 months: - 90%.
After 6 months: - 82%.
After 12 months: - 70%.
JOLT BAnERY
SA12260
SA12260
T~
t" ~
.~
.... ~rnlr} 11)
t
discharge current vs time
I I TI
T I'" I I I I
IT" TTI ..!
O'C(32'Fj \." 40'1:(' 04"F)
,\.
\.
\\
o 5),) I %3 5
~-"'Al '1_
10 21)0 50 100 21,)
IAI
.1
CutBnl
SA 12260 discharge characteristics (2soC/77"F)
....
l)
~12
II
Ii' 11
~
"! 10
.~
...
o
I %3 5 m 21~ ~ %3 5 m 21m
Mill .J..---\
o..oMrlllt T....
SA12260 SPECIFICATIONS
. Nominal voltage: 12 V.
. Nominal capacity (20 hr): 26.0 AH.
. Dimensions: total height 125 mm (4.92 in); container
height 125 mm (4.92 in); length 166 mm (6.54 in); width
175 mm (6.89 in).
. Weight: approximately 8.80 kg (19.40 Ibs).
. Container material: UL94HS ASS, UL94V-0 ASS.
. Internal resistance (25'C, 770F): - 10 m.
. Discharge capacity under different temperatures:
40oC: - 102%
2SoC: - 100%
OOC: - 8S%
. Capacity 250Cf77"F:
20 hr @ 1.3 A: 26.0 AH.
5 hr @ 4.16 A: 20.8 AH,
1 hr @ 15,6 A: 15.6 AH,
1 C @ 26.0 A: 13.0 AH,
. Charging voltage (2S0C, 770F):
Standby use: 13.65 V :t 0,15 V.
Cycle use: 14.7 V:t 0.3 V.
. Maximum discharge current: 300 A (S see).
. Maximum charging current: 7.8 A.
. Self-discharge residual capacity (2SoC. 770F):
After 3 months: - 90%.
After 6 months: - 82%.
After 12 months:o- 70%.
XSA12550
XSA12SS0 discharge current vs time
T~
III) 2
1-,
~ 1:
F 1"'1'1110
t
I T I I I
I I I I I
T T,' I I I
O'l:(32'F) 40'C( 104'F)
\.
.\.
\.
\.'\
"
o SJ<l I %)
1+-""'1 lor
5 10 21)O!ol toO 21Q
(AI .1
Curnnl
XSA12SS0 discharge characteristics (2soCI770F)
IJ
~ I~
II
I"
:>
I to
~ .
o
I 2) 5 10 21 3J 61 2 3 5 10 21 m
n+ I-~ ~
Diodla~ T....
XSA 12550 SPECIFICATIONS
. Nominal voltage: 12 V.
. Nominal capacity (20 hr): 55,0 AH.
. Dimensions: total height 234.5 mm (9.23 in); container
height 216.5 mm (8.52 in); length 229 mm (9.02 in); width
138 mm (5.43 in).
o Weight: approximately 19.0 kg (41.8 Ibs).
o Container material: UL94HB ABS, UL94V-0 ASS.
o Internal resistance (250C, 770F): - 8 m.
. Discharge capacity under different temperatures:
40oC: - 102%
2SoC: - 100%
ooC: - 85%
. Capacity 2soCf770F:
20 hr @ 2.75 A: 55.0 AH.
5 hr @ 8.8 A: 44.0 AH.
1 hr @ 33.0 A: 33.0 AH.
1 C @ 55.0 A: 27,5 AH.
. Charging voltage (2S0C, 770F):
Standby use: 13.65 V :t 0.15 V.
Cycle use: 14.7 V:t 0.3 V.
. Maximum discharge current: 600 A (5 see).
. Maximum charging current: 16.5 A.
. Self-discharge residual capacity (2S0C, nOF):
After 3 months: - 90%.
After 6 months: - 82%.
After 12 months: - 70%.
ON.6933 . 11/29/04 - Page 7 of 8
JOLT BAnERY
XSA121000A discharge current vs time
1:
!h
... :rthl1-)
L:
I I
I I
I I
~ ~'l:(104"F)
O'C(32'F) ~
~
~
~
'I.'
o !lJG 1 2 3
~,m^l 'I_
IG :)J 30 50 1O0 200 300
(^I ,I
Cu"""l
XSA 1 21000A discharge characteristics (2soC/770F)
13
--
- -, -
~....: r-......
\\ 1\ " '\ '\
I 1,..--: ...1.\
L -
~^t ti j^
...~ u
f 11
;>
'lIl 1O
'1
.. i
o
2 3 5 10 :lJ:lJ III 2 3 5 10 2!l 3J
rrlt I-b
OisGha'9" Time
Charging Procedure. Jolt Battery
XSA121000A SPECIFICATIONS
. Nominal voltage: 12 V.
. Nominal capacity (20 hr): 100.0 AH.
. Dimensions: total height 221 mm (8.70 in); container
height 214 mm (8.43 in); length 329 mm (12.9S in); width
172 mm (6.77 in).
. Weight: approximately 34.00 kg (74.8 Ibs).
. Container material: UL94HS ASS, UL94V-0 ABS.
. Internal resistance (2S0C, 770F): - 6.5 m.
. Discharge capacity under different temperatures:
40oC: - 102%
2SoC: - 100%
ooC: - 85%
. Capacity 250CI77"F:
20 hr @ 5.0 A: 100.0 AH.
5 hr @ 16.0 A: 80,0 AH.
1 hr @ 60.0 A: 60.0 AH,
1 C @ 100.0 A: 50.0 AH.
. Charging voltage (250C. 770F):
Standby use: 13.65 V :I: 0.15 V,
Cycle use: 14.7 V :I: 0.3 V.
. Maximum discharge current: 600 A (S see).
. Maximum charging current: 30 A.
. Self-discharge residual capacity (2S0C, 77"F):
After 3 months: - 90%.
After 6 months: - 82%.
After 12 months: - 70%.
1933iacl\. tbI
Temperature Maximum ChargIng time 0.1 CA,
Charging compensation charging 2SoC (h)
Application Charging method voltage at coefficient of current Temp ('C)
2S'C (V/ceU) charging voltage (CA) 100"10 SO"lo
(mVrC/cell) discharge discharge
For standby Constant voltage and 2.25 - 2.30 -3.3 0,3 T C: 24 T c: 20
power source constant current (-1.8 mVrF/cell) o - 400C
For cycle charging (with current 2.40 - 2,50 -S 0,3 16<T<24 10 < T < 24 (32 -104"F)
seNlce restriction) (-2.8 mVrF/cell)
Temperature compensation of charging voltage is not needed l'Ilen using the batteries 'lithin S"C to 3S'C range.
Summary discharge current vs. time curve (2S0Cn70F)
I I I
I
!
I
I
sr-
i
I
-- -l --
: 10
-s
.~ 5
Xl 501OO2CXI ~ t 215
"'^ I
DISCHARGE CURRENT
JOLTllme.wm'
Page 8 of 8 - DN-6933. 11/29104
Summary discharge characteristics
Lu I.lO!='..
U I
S luru
~,uru
<Ill( IIlI,_to
;;:; I
:! II I- t,
~ u t" -
. .
I
I
JOlTdil.w",r
-t- ----J---+
1 ) Ii It l':
hours -.---..-..-.-..
1 J' ,~ 2'J)oJ 10
minutes
XSA12550
eg33)OSS."
I
I Electrical Specifications
I
DTK-120 HW
I
Class: AC Hard-Wired Transient Voltage Surge Suppressor
Installation Point: Single Circuit
Agency Approvals: UL, cUL 1449 ,IEEE C62.41B
Connection Method: Hardwire parallel connection
Continuous Current: Unlimited (Parallel Installation)
Response Time: <5 nSec Installed, <1 nSec Component Level
MCOV: 130 VRMS/185VPK
.. Operating Frequency: 50/60 Hz
AC Protection Modes: L - N, L - G, N - G
Service Voltage: 110/125 VAC
Diagnostics: Indicator Light
EMIIRFI Noise Filtering: Yes
Surge Current: 22,500 Amps (max)
Suppressed Voltage Rating: 600V
Max. Energy: 190 Joules
Operating Temp Range: -40oC to +850C
Operating Enviroment: Outdoor Use; Out of direct weather (5% to 100% non-condensinQ)
MTBF: 6,000,000 Hours; MIL - 217H / Bellcore method
Physical Specifications
Housing:
Housing Color:
Housing Size:
Weight:
High Impact Plastic
Black
3" X 1.5" X 1.5"
0.181bs
Warranty
Lifetime Product Replacement Warranty
Revised 10/12/05
DITEK warrants this product to be free from defects in workmanship and material and to operate under
normal use and conditions. If defective, DITEK will repair or replace this unit without charge.
ONE DITEK CENTER
1720 Starkey Road,
Largo, FL 33771
1-800-753-2345
www.ditekcorp.com
i1Jl'
~NOTIFIER@
September 17. 2001
DN-6840' F-710
NBG-12LR and NBG-12LRA
Dual-Action Agent Release Stations
Section: Releasing Panels
GENERAL
The NBG-12LR and NBG-12LRA are Agent Release Sta-
tions designed for use with NOTIFIER Fire Alarm Control
Panels with releasing capabilities and RP Series Releas-
ing Systems,
"
FEATURES
. Non-coded, dual action operation.
. Made with durable polycarbonate,
. Optional surface backbox,
. NBG-12LRA Includes:
V' Abort switch,
V' Power-on indication.
V' Released indication.
V' Manual release (dual-action).
. NBG-12LR Includes:
V' Dual-action release only.
APPLICATIONS
The NBG-12LRA and NBG-12LR are ideal for areas such
as clean rooms and computer rooms where a chemical
agent is used to extinguish a fire.
PRODUCT LINE INFORMATION
NBG-12LRA
NBG-12LR
SBA-10
SB.10
Agent release station with abort switch,
Release LED, Normal LED.
Dual-action agent release station.
Surface backbox for NBG-12LRA.
Surface backbox for NBG-12LR.
@ I California
.' Slale Fire
C L1~T~D US <8> ~ ~~:~~~28199
S692
Approved
SYSTEM
NORMAL
SYSTEM
ACTIVATED
o
r::':\
-...::J
o
~
o
TO ABORT - HOLD IN
l
~
i
Dual-Action NBG-12LRA
(shown activated)
This document Is not intended to be used for installation purposes. We try to keep our
product information up-to-date and accurate. We cannot cover all specific applications or
anticipate all requirements, An specifications are subject to change without notice.
For more information, contact NOTIFIER. Phone: (203) 484-7161 FAX: (203) 484-7118
~ NOT. F. E R' 12 Clintonville Road, Northford, Connecticut 06472
ISO 9001
K..-t =I: tI 11.::1. =I .]i
fNClNfEBINC . MANUfACl1l1NC
DN-6840 . 09/17/01 - Page 1 of 2
System
Normal "l"
LED \\'\\
(Green)
System
Operated , ,\\'.l!
LED (Red)
10K
1/4W
10K
1/4W
N.O. Abort Switch
--=-
10K,1/4W U
Resistors
~p
*~
10K,1/4W
Resistors
*NOTE: Mount End-of-Line Resistor on the last unit.
"Mount 4,7K ELR on the last unit when abort switch and manual release switch are
connected to control panel circuits. Mount 47K resistor on last unit when abort switch and
manual release switch are connected to monitor module or control module. Refer to
control panel manual for the listed ELR. Refer to the following documents when connect-
ing to the control panel: S-500rrC-2 (PIN 15019/15023); S-5000rrCM-2 (PIN 155831
15805); RP-1002 (PIN 15151); AFP-200 (PIN 15511), AFP-400 (PIN 50253).
B
1
Dual-Action NBG-12LR
DIMENSIONS, BACKBOXES
E f-ol 4-1/2" {11.43 cm) ~
T
0 0 0 0
0
bot h
8-3/16" 5BA-10 ar e
(20,8) 1-31 8"
(3,4 9)
dee p
0 000 0
.!.
1&40sllb.wmI
@
~f~. 2:::3'..c::~
;!~-, :~-: I. '~'l
!Jll!!fiL1lJl
jOn ;:i
. It II . ~'\'I
'1~~':C-'~ ~
~ ' "
~..,,~J.
@
1
1
!
NBG-12LRA (rear view)
Agent Release Pull Station
Page 2 of 2 - DN-6840' 09/17/01
~ 4-1/S" (1Q,4Scm) ~
I
o
--O---c7--0
5B-10
(
5-1/2"
(13.97)
I
I
.I.
o
o
ANSUL~
Detection and Control Components
( ffi\M~@~ijl~eJ
Abort Switch
Features
Stackable, screw-terminal, contact blocks
. Compatible with AUTOPULSE~ control units
. Surface-mount assemblies listed by Underwriters
Laboratories, Inc,
. Components mounted on stainless steel switch plate
Applications
The Abort. Switch is used to momentarily interrupt the release
circtJn signal when the control unit is in the alarm condition,
As long as the abort pushbutton is held in, the fire suppres-
sion system will not release, (Note: When the control unit is
programmed for IRI compliance, the abort will not be effec-
tive after pre-discharge,) When the pushbutton is released,
the release circuit is activated (unless the control unit has
been reset to the non-alarm condition).
Description
The Abort Switch assembly consists of a momentary-
contact pushbutton switch, normally-open contact block,
normally-closed contact block, and stainless steel switch
plate with silk-screened label. Surface-mount assemblies
include a single-gang weather-proof box with three 1/2 in.
I.P.S, threaded conduit outlets and gasket.
The stackable, screw-terminal contact blocks are rated for 28
VDC @ 1,1 amp makelbreak or 6 amp continuous carry,
Listings and Approvals
The switch is UL listed (S3623) when installed in the surface-
mount box (with gasket) that is provided with the surface-
mount assembly.
MOUNTING DIMENSIONS
\_2 718 IN. -1
(73mm) I
SURFACE.MOUNT
,_2518IN._
(67mm)
o
ANSUL
FIRE SUPPRESSION
SYSTEM ABORT
-
o
PUSH AND HOLD
4 5/8 IN.
(117 mm)
J
-
o
TYPICAL WIRING DIAGRAMS
ABORT SWITCH (SERIES)
EOL RESISTOR
4(
r - -- - -
I
I
I ::~:
I CONTROL UNIT
ABORT CIRCUIT
LT~~~A~'_
,--.,
'T'
I I
L___J
NC ABORT
SWITCH
ABORT SWITCH (PARALLEL)
r
I
i ::::
I CONTROL UNIT
NO ABORT ABORT CIRCUIT
SWITCH 12E~t~ _
. SEE CONTROL UNIT MANUAL FOR SPECIFIC WIRING REQUIREMENTS.
EOL RESISTOR
/
~
!~r-l
L___....J
Ordering Information
Part No,
76494
76495
76485
76486
Description
Abort Switch, Surface-Mount
Abort Switch, Flush-Mount
Extra Contact Block, N.C.
Extra Contact Block, N.O,
Shipping
Weight
lb. (kg)
1.0 (0.45)
1.0 (0.45)
0,25 (0.11)
0.25 (0.11)
ANSUL and AUTOPULSE aro regislorod tradoma",s.
FLUSH.MOUNT
2 3/8 IN.
(60mm)
ANSUL INOJRPORATEO, ONE STANTON STREET, MARINETTE, WI 54143-2542 715-735-7411
3-34
Fonn No. F.9S111 0111995 Ansullncorpo<alod Lilho In U.S.A.
@)NOTIFIER@
May 6, 2002
DN-6910' J-200
SSM Series
Alarm Bells
Section: AudioNisual Appliances
GENERAL
System Sensor's SSM Series alarm bells are low-current. high-
decibel notification appliances for use in fire and burglary sys-
tems or other signaling applications, They come pre-wired to
reduce installation time, and also incorporate a polarized elec-
trical design for use with supervision circuitry.
Reliable performance. SSM Series alarm bells pro-
vide loud, resonant tones. They operate on 24 VDC and are
motor-driven.
Simplified installation. For indoor use, SSM Series
alarm bells mount to a standard 4" (10.16 cm) square electri-
cal box. For outdoor applications, a WBB weatherproof
backbox is used,
"FEATURES
. Approved for indoor or outdoor (with WBB backbox) use,
. Low current draw.
. High dB output.
. Three sizes available: 6" (15.24 cm), 8" (20.32 cm), and
10" (25.40 cm) diameter,
. 24 VDC models; polarized for use with supervision circuitry,
. Bells mount directly to standard 4" (10.16 cm) square elec-
trical box.
SPECIFICATIONS
Nominal voltage: 24 VDC.
Operating voltage range: 19.2 to 26.4 VDC,
Average current draw: 0.03 A.
Sound output: 85 dB.
Operating temperature range: -310F (-350C) to +1400F
(+600C).
Termination: provided with two sets of leads for in/out wiring,
Service use: Fire Alarm, General Signaling, Burglar Alarm.
ENGINEERING AND
ARCHITECTURAL SPECIFICATIONS
Model shall be a SSM Series alarm bell. Bells shall have
underdome strikers and operating mechanisms. Gongs on
said bell shall be no smaller than nominal 6" (15.24 cm), 8"
(20.32 cm), or 10. (25.40 cm) (specify size) with an operating
voltage of 24 VDC. Bells shall be suitable for surface or semi-
flush mounting. Outdoor surface-mounted installations shall
be weatherproof (using optional WBB weatherproof backbox);
otherwise, bells shall mount to a standard 4" (10.16 cm) square
electrical box having a minimum projection of 2.5" (6.35 cm).
Bells shall be located as shown on the installation drawings or
as determined by the Authority Having Jurisdiction, Bells shall
be Listed for indoor/outdoor use by Underwriters laborato-
ries, ULC (Canada), and the California State Fire Marshal, and
approved by Factory Mutual and MEA.
@
LISTED
S4011
@
~ California
~...i.!'<' State Fire
~ Marshal
'. -
.., 7135-1209:164
CS548, Vol. 7
(SSM24-6A,
SSM24-8A.
SSM24-10A)
<8>
Approved
MEA
331-01-E
ORDERING INFORMATION
SSM24-6 6" (15.24 cm) bell, 24 VDC, polarized, 85 dBA.
SSM24-6A Canadian model of 6" bell above,
SSM24-8 8" (20.32 cm) bell, 24 VDC. polarized, 85 dBA.
SSM24-8A Canadian model of 8" bell above,
SSM24.10 10. (25.40 cm) bell. 24 VDC. polarized. 85 dBA.
SSM24-10A Canadian model of 10" above.
WBB Weatherproof backbox.
NOTIFIER~ is an operation of Honeywell,
This document Is not intended to be used for installation purposes. We try to keep our
product Information up-to-date and accurate, We cannot cover all specific applications or
anticipate all requirements. All specifications are subject to change without notice.
For more Information, conlact NOTIFIER. Phone: (203) 484-7161 FAX: (203) 484-7118
@) NOTI FI E!: R" 12 Cllntonvllle Road, N~rthford, Connecticut 06472
ISO 9001
..-.11 =I :11-111 =-. =1-.)
BUlftEEIINC I MANlIfUl1IBINS
DN-6910' 05/06/02 - Page 1 of 1
SpectrAlert@ Advance
Selectable Output
Notification Appliances
DN-7087:A' J-70
@l) NOTI FI ER<!l
by Honeywell
AudioNisual Devices
General
System Senso~ SpectrAle~ Advance selectable-output
horns, strobes and horn/strobes are rich with features guaran-
teed to cut installation times and maximize profits. The SpectrA-
lert Advance series of notification appliances is designed to
simplify your installations, with features such as: plug-in
designs, instant feedback messages to ensure correct installa-
tion of individual devices, and eleven field-selectable candela
settings for wall and ceiling strobes and horn/strobes.
More specifically, when installing Advance products, first attach
a universal mounting plate to a four-inch square, four-inch octa-
gon, or double-gang junction box. The two-wire mounting plate
attaches to a single-gang junction box.
Then, connect the notification appliance circuit wiring to the
~EMS terminals on the mounting plate,
,.. Finally, attach the horn, strobe, or horn/strobe to the mounting
plate by inserting the product's tabs in the mounting plate's
grooves. The device will rotate into position, locking the prod-
uct's pins into the mounting plate's tenninals. The device will
temporarily hold in place with a catch until it is secured with a
captured mounting screw.
SpectrAlert Advance products allow you to choose:
. 12 or 24 volts.
, At 24 volts, 15, 15/75,30,75,95,110,115, 135,150,177, or
185 candela by way of a rear-mounted slide switch and front
viewing window.
. Horn tones and volume by way of a rotary switch.
, The SpectrAlert Advance series includes outdoor notification
appliances. Outdoor strobes and horn/strobes (two-wire and
four-wire) are available for wall or ceiling, Outdoor horns are
available for wall only. All System Sensor outdoor products
are rated between -40'F and 151'F (--40'C and 66'C) in wet
or dry applications.
Models available:
, Indoor wall-mount: horn, strobe, 2-wire horn/strobe, 4-wire
horn/strobe,
, Indoor ceiling-mount: strobe, 2-wire horn/strobe, 4-wire horn/
strobe.
. Outdoor wall-mount: horn, strobe, 2-wire horn/strobe, 4-wire
horn/strobe,
, Outdoor ceiling-mount: strobe, 2-wire horn/strobe, 4-wire
horn/strobe.
Features
, Plug-in design.
, Same mounting plate for wall- and ceiling-mount units,
, Shorting spring on mounting plate for continuity check before
installation.
. Captive mounting screw.
, Tamper-resistance capability,
, Field-selectable candela settings on wall and ceiling units:
15,15/75,30,75.95,110,115,135,150,177,185.
, Automatic selection of 12 or 24 volt operation at15 and 15/75
candela.
, Outdoor wall and ceiling products.
. Outdoor products rated from -40'F and 151'F (-40'C and
66'C).
7017...' pa
7CS7phaJ ;PO
70a7p"oS.PQ
~l.;..... "... ...
" .
'!=' .
( .., ~~;,' .
~-
Indoor Wall Horn
70a7""04 ;pa
Indoor Ceiling Strobe
, Minimal intrusion into thebackbox.
, Horn rated at 88+ dbA at16 volts.
, Rotary switch for tone selection.
, Three horn volume settings.
, Electrically compatible with existing SpectrAlert products.
Engineering Specifications
SpectrAlert Advance horns, strobes, and horn/strobes shall
mount to a standard 4.0. x 4.0" x 1,5" (10.16 x 10,16 x 3.81 em)
backbox, 4.0" (10.16 cm) octagonal backbox, or a double-gang
backbox. Two-wire products shall also mount to a single-gang
2.0" x 4.0" x 1,875" (5,08 x 10.16 x 4.763 cm) backbox. A uni-
versal mounting plate shall be used for mounting ceiling and
wall products. The notification appliance circuit wiring shallter-
minate at the universal mounting plate. Also, SpectrAJert
Advance products, when used with the Sync'CircuitN Module
accessory, shall be powered from a non-coded notification appli-
ance circuit output and shall operate on a nominal 12 or 24
volts When used with the Sync'Circuit Module, 12-volt rated
notification appliance circuit outputs shall operate between 9
and 17.5 volts; 24-volt rated notification appliance circuit outputs
shall operate between 17 and 33 volts. Indoor SpectrAlert
Advance products shall operate between 32'F and 120'F (O'C
and 49'C) from a regulated DC, or full-wave-rectified, unfiltered
power supply. Strobes and horn/strobes shall have field-select-
able candela settings including 15, 15/75,30,75,95, 110, 115,
135,150,177,185.
ON-7087:A' 10/18/06 - Page 1 or 4
STROBE
The strobe shall be a System Sensor SpectrAlert Advance
Model listed to UL 1971 and shall be approved for fire
protective service. The strobe shall be wired as a primary-sig-
naling notification appliance and comply with the Americans with
Disabilities Act requirements for visible signaling appliances,
flashing at 1 Hz over the strobe's entire operating voltage range,
The strobe light shall consist of a xenon flash tube and associ-
ated lens/reflector system.
HORN/STROBE COMBINA T/ON
The horn/strobe shall be a System Sensor SpectrAlert Advance
Model listed to UL 1971 and UL 464 and shall be
approved for fire protective service. The horn/strobe shall be
wired as a primary-signaling notification appliance and comply
with the Americans with Disabilities Act requirements for visible
signaling appliances, flashing at 1 Hz over the strobe's entire
operating voltage range. The strobe light shall consist of a
xenon flash tube and associated lens/reflector system. The hom
shall have three audibility options and an option to switch
between a Temporal 3 pattern and a Non-Temporal (continuous)
pattern. These options are set by a multiple position switch. On
four-wire products, the strobe shall be powered independently of
the sounder. The horn on horn/strobe models shall operate on a
" eoded or non-coded power supply.
OUTDOOR PRODUCTS
SpectrAlert Advance outdoor horns, strobes and horn/strobes
shall be listed for outdoor use by UL and shall operate between
-40"F and 151"F (-40"C and 56"C). The products shall be listed
for use with a System Sensor outdoorlweatherproof backbox
with half-inch and three-fourths-inch conduit entries.
SYNCHRONIZA T/ON MODULE
The module shall be a System Sensor Sync"Circuit
listed to UL 464 and shall be approved for fire protective service.
The module shall synchronize SpectrAJert strobes at 1 Hz and
horns at Temporal 3. Also, while operating the strobes, the mod-
ule shall silence the horns on horn/strobe models over a single
pair of wires. The module shall mount toa 4.588" x 4.688" x
2.125" (11.906 x 11.906 x 5,398 cm) backbox. The module shall
also control two Style Y (class B) circuits or one Style Z (Class
A) circuit. The module shall synchronize multiple zones. Daisy-
chaining two or more synchronization modules together will syn-
chronize all the zones they control. The module shall not oper-
ate on a coded power supply,
Strobe Current Draw,
UL Maximum (mA RMS)
8-17.5V 16 - 33 V
Candela DC FWR DC FWR
15 123 128 66 71
15175 142 148 77 81
Standard 30 NA N/A 94 96
Candela 75 NA NA 158 153
Range 95 NA NA 181 176
110 NA NA 202 195
115 NA NA 210 205
135 NA NA 228 207
High 150 NA NA 246 220
Candela
Range 177 NA NA 281 251
185 NA NA 286 258
Operating Specifications
" Standard operating temperature: 32"F to 120"F (O"C to 4S"C).
" K Series operating temperature: -40"F to 151"F (-40"C to
56"C).
" Humidity range: 10% to 93% non-condensing (indoor products),
" Strobe flash rate: 1 flash per second,
" Nominal voltage: regulated 12 VDC/FWR or regulated 24
VDCIFWR. NOTE: Full Wave Rectified (FWR) voltage is a
non-regulated, time-varying power source that is used on
some power supply and panel outputs.
" Operating voltage range: 8 V to 17.5 V (12 V nominal); or
16 V to 33 V (24 V nominal). NOTE: p. S, PC, and SC prod-
ucts will operate at 12 V nominal only for 15 cd and 15/75 cd.
" Input terminal wire gauge: 12 to 16 AWG (3.31 to 0.821 mm').
" Ceiling-mount dimensions (including lens): 6.6" diameter
x 2.5" deep (17.3 em diameter x 6A cm deep).
" Wall-mount dimensions (including lens): 5.6" H x 4,7" W x
2.5" 0 (14.2 cm H x 11,9 cm W x 6.4 cm D).
" Horn dimensions: 5.6" H x 4.7" W x 1.3" 0 (14.2 cm H x
11.9 cm Wx 3.3 em D),
Agency Listings and Approvals
The listings and approvals below apply to SpectrAlert Advance
Selectable Output Notification Devices. In some cases, certain
modules may not be listed by certain approval agencies, or list-
ing may be in process. Consult factory for latest listing status.
" UL Listed: file S4011 (HR_, HW_, P2_, P4_, PC2_,
PC4_ models); file S5512 (models SCR, SCRH, scw,
SCWH, SR, SRH, SW, SWH); file S3593 (SCRHK, SCRK,
SRHK, SRK).
" ULC Listed: file CS1099 (HRA, HRKA); file CS1089 (typi-
cally "A" models, with exception of outdoor strobes), See
Canadian data sheet for listings and specifications.
" FM approved.
" MEA approved: file 452-05-E.
" CSFM approved: file 7125-1653:186 (SCR, SCRH, SCW,
SCWH, SR, SRH, SW, SWH); file 7125-1653:188 P2_,
P4_. PC2_, PC4_models); file 7135-1653:189 (HR, HRK,
HVV); file 7300-1653:187 (SCRHK, SCRK, SRHK, SRI<).
Horn Current Draw,
UL Maximum (mA RMS)
8 - 17.5 V 16 - 33 V
Sound
Pattern dB DC FWR DC FWR
Temporal High 57 55 69 75
Temporal Medium 44 49 58 69
Temporal Low 38 44 44 48
Non-temporal High 57 56 69 75
Non-temporal Medium 42 50 60 69
Non-temporal Low 41 44 50 50
Coded High 57 55 69 75
Coded Medium 44 51 56 69
Coded Low 40 46 52 50
Page 2 of. - ON-7087:A " 10118108
Horn and Horn/Strobe
Rotary Switch Setting
Settlng Repetition Rate dB Level
1 Temporal horn High
2 Temporal horn Medium
3 Temporal horn Low
4 Normal horn High
5 Normal horn Medium
6 Normal horn Low
7" Extemally coded High
8" Externally coded Medium
9" Externally coded Low
"NOTE: Settings 7, 8, and 9 are not available
on 2-wire hom/strobe.
Horn and Horn/Strobe Output (dBA)
8 -17.5 V 16 - 33 V
Switch Sound
Position Pattern dB DC FWR DC FWR
1 Temporal High 78 78 84 84
2 Temporal Medium 74 74 80 80
3 Temporal Low 71 73 76 76
4 Non-temporal High 82 82 88 88
5 Non-temporal Medium 78 78 85 85
6 Non-temporal Low 75 75 81 81
7" Coded High 82 82 88 88
8" Coded Medium 78 78 85 85
9" Coded Low 75 75 81 81
"NOTE: Settings 7, 8. and 9 are not available on 2-wire hom/strobe.
Two-Wire Horn/Strobe, STANDARD Candela Range (15 - 115 cd),
UL Maximum Current Draw (mA RMS)
8 - 17.5 V 16 - 33 V
Input, Sound Pattern, dB Level 15 15/75 15 15/75 30 75 95 110 115
DC Input. Temporal. High 137 147 79 90 107 176 194 212 218
DC Input, Temporal, Medium 132 144 69 80 97 157 182 201 210
DC Input. Temporal, Low 132 143 66 77 93 154 179 198 207
DC Input, Non-temporal, High 141 152 91 100 116 176 201 221 229
DC Input, Non-temporal, Medium 133 145 75 85 102 163 187 207 216
DC Input, Non-temporal, Low 131 144 68 79 96 156 182 201 210
FWR Input, Temporal. High 136 155 88 97 112 168 190 210 218
FWR Input, Temporal, Medium 129 152 78 88 103 160 184 202 206
FWR Input, Temporal, Low 129 151 76 86 101 160 184 194 201
FWR Input, Non-temporal, High 142 161 103 112 126 181 203 221 229
FWR Input. Non-temporal, Medium 134 155 85 95 110 166 189 208 216
FWR Input, Non-temporal, Low 132 154 80 90 105 161 184 202 211
..
..
Two-Wire Horn/Strobe, HIGHCandela Range (135 -185 cd),
UL Maximum Current Draw (mA RMS)
16 - 33 V 16 - 33 V
DC Input 135 150 177 185 FWR Input 135 150 177 185
DC, Temporal, High 245 259 290 297 FWR, Temporal, High 215 231 258 265
DC. Temporal, Medium 235 253 288 297 FWR, Temporal, Medium 209 224 250 258
DC, Temporal, Low 232 251 282 292 FWR, Temporal, Low 207 221 248 256
DC, Non-temporal, High 255 270 303 309 FWR, Non-temporal, High 233 248 275 281
DC. Non-temporal, Medium 242 259 293 299 FWR, Non-temporal, Medium 219 232 262 267
DC. Non-temporal, Low 238 254 291 295 FWR, Non-temporal, Low . 214 229 256 262
7047d1ml..'
r\
2.5- '- '--
1
\ I
'-. ./
;
-' ./
ON-7087:A. 10/18106 - Page 3 of 4
Ordering Information
Model Description. Model Description
WALL HORN/STROBES CEiLING HORN/STROBES
P2R 2-wire horn/strobe, standard cd, red, PC2R 2-wire horn/strobe, standard cd, red.
P2RH 2-wire horn/strobe. high cd, red. PC2RH 2-wire horn/strobe. high cd, red.
P2RK 2-wire horn/strobe, standard cd, red. outdoor." PC2RK 2-wire horn/strobe. standard cd, red, outdoor.
P2RHK 2-wire horn/strobe. high cd, red, outdoor. PC2RHK 2-wire horn/strobe. high cd, red, outdoor.
P2W 2-wire horn/strobe. standard cd. white. PC2W 2-wire horn/strobe. standard cd, white.
P2WH 2-wire horn/strobe, high cd, white. PC2WH 2-wire horn/strobe, high cd, white.
P4R 4-wire horn/strobe, standard cd. red. PC4R 4-wire horn/strobe. standard cd, red.
P4RH 4-wire horn/strobe, high cd, red. PC4RH 4-wire horn/strobe. high cd, red.
P4RK 4-wire horn/strobe. standard cd, red. outdoor. PC4RK 4-wire horn/strobe, standard cd, red. outdoor.
P4RHK 4-wire horn/strobe, high cd. red, outdoor. PC4RHK 4-wire horn/strobe, high cd. red, outdoor.
P4W 4-wire horn/strobe, standard cd, white. PC4W 4-wire horn/strobe, standard cd. white.
P4WH 4-wire horn/strobe. high cd, white. PC4WH 4-wire horn/strobe, high cd, white.
WALL STROBES CEILING STROBES
SR Strobe. standard cd. red. SCR Strobe, standard cd, red.
'SRH Strobe, high cd. red, SCRH Strobe, high cd. red.
SRK Strobe. standard cd. red, outdoor. SCRK Strobe, standard cd, red, outdoor.
SRHK Strobe, high cd, red, outdoor. SCRHK Strobe, high cd, red, outdoor.
SW Strobe, standard cd, white. SCW Strobe. standard cd, white,
SWH Strobe, high cd, white. SCWH Strobe, high cd, white,
ACCESSORIES HORNS
BBS-2 Backbox skirt. wall, red. HR Horn, red.
BBSW-2 Backbox skirt, wall. white. HRK Hom. red. outdoor.
BBSC-2 Backbox skirt, ceiling, red, HW Hom, white.
BBSCW-2 Backbox skirt. ceiling, white. ACCESSORIES, continued
SA-WBB Weatherproof backbox, wall. MP-2W-20BP 2-wire Indoor mounting plates, pkg of 20,
SA-WBBC Weatherproof backbox, ceiling. cont'd at right MPK.2W.20BP 2-wire outdoor mounting plates, pkg of 20.
NOTE: ..High cd" refers to strobes that include 135, 150, 1n, and 185 candela settings. .Standard cd" refers to strobes that
include 15, 15/75,30, 75, 95, 110, and 115 candela settings. "All outdoor models ("K" suffix) include weatherproof backboJ(,
SyncoClrcult '" is a trademarlt. and NOT1FIER~, SpectrAlerf3l, and System
Sen.o~ are registered trademarlts 0' Honeywelllntemationallnc.
C2006 by Honeywell International Inc All rights reselVed. Unauthorized use
0' this document is stricUy prohibited.
ISO 9001
...._1~...=-.=-.J
IMIIIIIINI 'MNIIHmIIlI
lUUITY USTEIIS
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
For more information, c:ootact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
www.notifier.com
Page 4 of 4 - ON-7087:A' 10/18/06
Description
The cylinder is factory filled with INERGEN~ agent. A single
cylinder may be used or multiple cylinders can be manifold-
ed together to obtain the required quantity of agent for total
flooding. The cylinder valve can be actuated electrically,
pneumatically, and/or manually with approved valve actua-
tion components. All valves are equipped with an anti-recoil
feature.
The cylinders are shipped with a maintenance record card
and protective shipping cap attached to the threaded neck
of eact). cylinder. This cap entirely encloses and protects the
valve"while in shipment.
System Components
ULEX-4510 6-1-02 Page 1-1.1
REV. 3
CV-98 Valve I Cylinder Shipping Assembly.
The equivalent length of the valve is equal to 20 ft. (6.1 m)
of 1/2 in. Sch. 40 pipe.
Component Material Approvals
Cylinder Steel Meets DOT 3M2300
Valve Brass
Safety Relief Valve Brass
Valve/Cylinder FMRC Approved
Assembly UL Listed (EX-451 0)
Shipping Cap Steel
Shipping Nominal Cylinder AetuallNERGEN Approximate Dimension Dimension
Assembly Size Agent Quantity Weight A B
Part No. ft.3 (m3) ft.3 m3 lb. (kg) In. (cm) In. (em)
Shipping Assemblies - Red Standard Paint
426147 200 (5.7) 205 (5.8) 128 (58) 52,7 (129) 8.5 (21.6)
426148 250 (7.1 ) 266 (7.5) 169 (77) 57.7 (147) 9.3 (23.5)
426149 350 (9.9) 355 (10.1 ) 217 (98) 59.7 (152) 10.7 (27.3 )
426620 LC-350 (9.9) 355 (10.1 ) 217 (98) 60.2 (152.9) 10.5 (26.7)
426594 LC-425 (12.0) 429 (12.1 ) 246 (111.6) 70.5 (179.1 ) 10.5 (26.7)
426150 435" (12.3) 439 (12.4) 260 (117.9) 66.9 (170.0) 11.0 (27.9)
Shipping Assemblies - Red Corrosion Resistant Paint
426256 200 (5.7) 205 (5.8) 128 (58) 52.7 (129) 8.5 (21.6)
426257 250 (7.1 ) 266 (7.5) 169 (77) 57.7 (147) 9.3 (23.5)
426258 350 (9.9) 355 (10.1 ) 217 (98) 59.7 (152) 10.7 (27.3)
426621 LC-350 (9.9) 355 (10.1) 217 (98) 60.2 (152.9) 10.5 (26.7)
426595 LC-425 (12.0) 429 (12.1 ) 246 (111.6) 70.5 (179.1 ) 10.5 (26.7)
426259 435 (12.3) 439 (12.4) 260 (117.9) 66.9 (170.0) 11.0 (27.9)
~
~ . NOTE: For Shanghai version, order Part No. 430935.
Canadian TC Approved
Shipping Nominal Cylinder AetuallNERGEN Approximate Dimension Dimension
Assembly Size Agent Quantity Weight A B
Part No. ft.3 (m3) ft.3 m3 lb. (kg) In. (em) In. (em)
Shipping Assemblies - Red Enamel Paint
426712 200 (5.7) 205 (5.8) 128 (58) 52.7 (129) 8.5 (21.6)
426713 250 (7.1 ) 266 (7.5) 169 (77) 57.7 (147) 9.3 (23.5)
426714 350 (9.9) 355 (10.1 ) 217 (98) 59.7 (152) 10.7 (27.3)
427551 LC-425 (12.0) 429 (12.1 ) 246 (111.6) 70.5 (179.1 ) 10.5 (26.7)
426715 435 . (12.3) 439 (12.4 ) 260 (117 .9) 66.9 (170.0) 11.0 (27.9)
.
Shipping Assemblies - Red Epoxy CR Paint .
426716 200 (5.7) 205 (5.8) 128 . (58) 52.7 (129) 8.5 (21.6)
426717 250 (7.1 ) 266 (7.5) 169 (77) 57.7 (147) 9.3 (23.5)
426718 350 (9.9) 355 (10.1 ) 217 (98) 59.7 (152) 10.7 (27.3 )
427552 LC-425 (12.0) 429 (12.1 ) 246 (111.6) 70.5 (179.1 ) 10.5 (26.7)
426719 435 (12.3) 439 (12.4 ) 260 (117.9) 66.9 (170.0) 11.0 (27.9)
CYl.INDER
,,/ SHIPPING CAP
rc;I .
PRESSURE It;}./ VALVE SHIPPING CAP
GAUGE ~ ~
RECORD
TAG
HEIGHT TO OllTlET
CENTER A
'>-
~B
002.251
CV-98 INERGEN Valve
The CV-98 valve has a ten (10) year warranty. The valve
requires no Internal maintenance. The valve Is sealed
closed and must not be disassembled. If there is ever a
malfunction of the CV-98 valve, the complete valve must be
sent back to Ansul for warranty replacement. If the exter-
nal seal Is broken, the warranty Is voided.
NOTE: Use Flexible Discharge Bend, Part No. 427082, when
attaching valve to supply pipe or manifold.
ANSUL and IN ERG EN are trademar1<s ~t Ansullncorporated or its affiliates.
ANSUL INCX:fV'OAATEO, 0fI.E STANTON STREET, MARINETTE, WI 54143-2542
715-735-7411
t
3 112 IN.
(89mm)
REFERENCE
~II"
f-- --.,
..l-- -- --l.
..f ---- -=-.:- .:-.:.:- ~
/ "
/ '\.
/ \
I \
PRESSURE
GAUGE
SAFElY
RELIEF
VALVE
Fotm No. F.9877-3 C2002 Ansullncorporaled
OC2~'2
UtIlo in U.S.A.
ANSUL~
.
System Components
UL EX-451 0 11-1-00 Page 1-3.6
Booster Actuator
Description
The Booster Actuator, Part No. 428949, is used when elec-
tric actuation is required on the 1 in. selector valve, 2 in.
selector valve, or the CV-98 cylinder valve. The actuator
mounts directly to the component and then a HF electric
actuator mounts to the top of the booster actuator.
~.,~(""'''
3.025
n
1 1/8 -18 UNEF
ANSUL end INERGEN are trademarl<s 01 Ansullncorporoted Ot its amUotes,
The Booster Actuator requires resetting after actuation. A
Reset Tool, Part No. 429847, is available for this use.
1IOeo:l7
ANSUL INCORPORATED. ONE STANTON smeET, MAAlNETTE, WI 54143-2542 715-735-7411
FOtm No. F.2001068 C2001 An.ullncotpol1lled Litho In U.S.A.
ANSUL~
In~~
eM." A-'::c\!f!J) ~~.ue
Systef!l Components
UL EX-451 0 11-1-00 Page 1-2.1
REV. 2
CV-98 Electric Actuator
Description
Electrical actuation of a CV-98 INERGEN valve is accom-
plished by a CV-98 electric actuator interfaced through an
AUTOPULSE Control System. This actuator can be used in
hazardous environments where the ambient temperature
range is between 32 of to 130 of (0 oC to 54 OC). The elec-
tric actuator meets the requirements of N.E.C. Class I, Div.
1, Groups B, C, D and Class II, Div. 1, Groups E, F, G. A
maximum of two CV-98 electric actuators can be used on a
single AUTO PULSE release circuit. When using either one
~ or two CV-98 electric actuators, a current limiter module,
Part-No. 427354, must always be used.
The Actuator Shipping Assembly contains a current Iim-
~ iter module along with an installation instruction sheet.
The actuator specifications are:
Nominal Voltage
~ 24 VDC @ .75 amps
In auxiliary or override applications, a manual cable pull
actuator can be installed on top of the CV-98 electric
actuator by removing the safety cap.
~ A manual lever actuator, Part No. 423309, is available for
~ use with the CV-98 electric actuator.
The actuator contains a standard 1/2 in. threaded female
straight connector for electrical conduit hookup.
The CV-98 electric actuator uses a replaceable
METRON~ PROTRACTOR which is a device designed to
produce a high forc.e mechanical output. The actuator is
electrically actuated and will operate within milliseconds.
CAUTION
LABEL
001395
112 IN.
CONDUIT
THREADS
~
17/8 IN. HEX ~
(4.8 em) "...............
The METRON PROTRACTOR must be replaced after
discharge of the INERGEN system.
Shipping Assembly
Part No. Description
423684 CV-98 Electric Actuator
42~958 Replaceable METRON
PROTRACTOR
427354 Current Limiter Module
~
Component Material Thread Sizerrype Approvals
CV-98 Electric Actuator Body: 1/2 in. Straight Female UL (E62842)
Brass on Conduit Connection FM Approved
METRONPROTRACTOR
Plunger:
Stainless Steel
~
ANSUL INCO'V'ORATED. ONE STANTON ~ MAAINETTE. WI 54143-2542
715-735-7411
Form No. F.9878.2 C2000 Ansull~rporal.d Litho In U.S.A.
ANSUL~
\ l~{gen.1
System Components
UL EX-4510 11.1.00 Page 1-15
REV. 6
Pressure Reducer/Union
Description
The pressure reducer/union is required to restrict the flow
of INERGEN!l agent thus reducing the agent pressure
down stream of the union, The 3000 psi (206.9 bar)
NSCWP union contains a stainless steel orifice plate which
is drilled to the specific size hole required based on the flow
calculation.* The orifice plate provides readily visible orifice
identification. The orifice union is available in six sizes:
1/2 in" 3/4 in., 1 in., 1 1/4 in., 1 1/2 in, ,and 2 in. NPT.
All pressure reducer/unions must be installed in the piping
with .the orifice identification tab on the pressure inlet side
of1he system. The 1 1/4 in., 1 1/2 in. and 2 in. orifice
unions must be installed per the direction of the flow arrow
stamped on the body.
A
..
VISIBLE ORIFICE
IDENTIFICATION
002197
Shipping Assembly
Part No. Description A B C
416677 1/2 in. NPT pressure reducer/union 2,06 in. (5,2 cm) 1.18 in. (2.9 em) 1.95 in. (4.9 cm)
416678 3/4 in. NPT pressure reducer/union 2.38 in. (6.1 cm) 1.50 in. (3.8 em) 2.38 in, (6,1 em)
416679 1 in. NPT pressure reducer/union 2.63 in. (6.7 em) 1.78 in. (4.5 em) 2.77 in. (7.0 em)
416680 1 1/4 in, NPT pressure reducer/union 2.94 in. (7.5 cm) 2.04 in. (5.2 em) 3.31 in. (8.4 em)
416681 1 1/2 in. NPT pressure reducer/union 3.31 in. (8.4 em) 2.31 in. (5.9 em) 3.70 in. (9.4 em)
416682 2 in. NPT pressure reducer/union 3.56 in. (9.0 cm) 2.85 in. [1.2 em) 4.39 in. (11.2 cm)
Component Material Thread Size Approvals
Pressure Reducer/ Body: Forged 1/2,3/4,1, FMRC Approved
Union Steel 1 1/4, 1 1/2, UL Listed (EX-4510)
2 in. NPT
Orifice Plate:
Stainless
Steel
.. NOTE: Refer to "Nozzle/Pressure Reducer Range Chart" in
.. Design Section for detailed orifice range information.
. Orifice diameter must be specified 't'll'hen placing order.
ANSUL and INERGEN are r.9i,torod tradema"',.
ANSUL INCORPORATED, ONE STANTON STREET. MARINETTE. WI 54143-2542
715.735.7411
Form No. F.9311.8 C2001 ""sullncorporaled Lllho in U.S.A.
ANSUL~
Il~19~n.1
System Components
UL EX-4510 5-1-00 Page 1-12
REV. 4
Flexible Discharge Bend
Description
.. The valve Flexible Discharge Bend (Part No. 427082) is a
5/8 in. (1,59 cm) 1.0. extra-heavy flexible hose which con-
nects the valve discharge outlet to the fixed piping or head-
er manifold. The discharge bend has a special female
thread for connecting to the valve outlet and a male 1/2 in.
NPT thread for connecting to the fixed piping or manifold,
.. The discharge bend will withstand a pressure of 9000 psi
.. (621 bar). Its flexible connection allows for easy alignment
of multiple cylinder banks to fixed piping. Each bend has a
built-in check valve that prevents loss of agent should the
sY5tem discharge while any cylinder is removed.
The equivalent length of this hose is equal to 18 ft. (5.5 m)
of 1/2 in. Sch. 40 pipe.
Shipping Assembly
Part No. Description
427082 Flexible discharge bend
842430 Washer
..
Thread SizelType
Component Material Valve End Manifold End Approvals
5/8 in, Flexible SAE 100 R2 Special to 1/2 in, NPT Male FMRC Approved
Discharge Bend Type AT mate with UL Listed (EX-4510)
CV~O and
CV-98 Valve
..
..
~
FEMALE ADAPTOR
(BRASS)
WASHER
CHECK
VAlVE END
ANSU~ and INERGEN lIIe registered Itadema"'s.
ANSu~ INCORPORATI:O. ONE STANTON smEET, MARINETTE, WI 54 143-2542
187/8 IN,
(47.9 em)
1/2 IN, NPT
MA~E COUP~ING
MANIFO~DIEND
oooosa
715-735-7411
Form No. F-9306-8 Q2000 Ansullncorpo<ated Litho in U.S.A.
ANSUL~
L~{gen'l
System Components
UL EX-4510 11-1-00 Page 1-16
REV. 6
3600 Discharge Nozzle
Description
Discharge nozzles are designed to direct the discharge of
INERGEN(!) agent using the stored pressure from the cylin-
ders. Ten sizes of nozzles are available. The system design
specifies the orifice size to be used for proper flow rate and
distribution pattern". The nozzle selection depends on the
hazard and location to be protected. Standard nozzles are
constructed of brass.
NOTE: 2,21/2, and 3 in. nozzles are not recommended in
areas that are subject to damage by high velocity dis-
charg,es, such as suspended ceiling tiles.
Shipping Assembly
Part No. Description
417908 1/4 in. NPT nozzle".
417723 3/S in. NPT nozzle"
417362 1/2 in. NPT nozzle
417363 3/4 in. NPT nozzle
417364 1 in. NPT nozzle
417365 1 1/4 in. NPT nozzle
417366 1 1/2 in. NPT nozzle
426155 2 in. NPT nozzle
426156 21/2 in. NPT nozzle
426137 3 in. NPT nozzle
Component Material Thread Size Approvals
Nozzle Body-Brass 1/4.", 3/S", 1/2,3/4,1,11/4, FMRC Approved
1 1/2, 2, 2 1/2, 3 NPT UL Listed (EX-4510)
B~
C ----
..--
0021"
ANSUl and INERGEN are registered Itademarks.
. Orifice diameter must be specified when ordering noule.
Refer to Orifice Size Chart in Manual AppendiA Section.
"ULNlC ~sted only.
ANSUlINCORPOAATED. ONE STANTON STREET. MARINETTE. WI 54143-2542
..
Size A-In. B-In. C-ln. Hex
1/4 in. 5/S 1 9/16 21/32 5/8
3/S in. 3/4 15/S 23/32 3/4
1/2 in. 15/16 1 31/32 27/32 15/16
3/4 in. 1 1/8 2 5/32 7/8 1 1/8
1 in. 1 13/32 2 9f16 1 1 7/16
1 1/4 in. 1 3/4 23/4 1 1/16 1 3/4
1 1/2 in. 2 2 31/32 1 1/16 2
2 in. 2 3/8 3 1 2 3/8
2 1/2 in. 3 31/2 1 3
3 in. 31/2 41/8 1 1/4 31/2
.. NOTE: Refer to "Nozzle/Pressure Reducer Range Chart' in
.. Design Section for detailed orifice range information.
715-735-7411
Form No. F.9328.9 C2001 Ansullncorporated litho In U.S.A.
ANSUL~
L~{gen.
..
System Components
UL EX-451 0 3-1-99 Page 1-16.2
Nozzle Deflector Shield
Description
The INERGEN~ system nozzle deflector shield is used to
control the pattern of the discharge of the INERGEN agent.
The deflector shield helps keep the agent discharge away
from false ceiling tiles and fragile light fixtures, avoiding
damage to them.
The deflector shields are constructed of steel and painted
with a cameo cream colored paint. They are available in
five sizes.
Component Material Approvals
Nozzle Steel FMRC Approved
Deflector UL Listed (EX-4510)
Shield
.. B C
Shtpping A D E
Assembly Inlet Length of Overall Deflector Coupling
Part No. NPT Coupling Length O.D. 0.0.
417708 1/2 in. 1 7/8 in. 3 in. 3 3/8 in. 1 1/8 in.
(4.8 cm) (7.6 cm) (8.6 cm) (2.9 cm)
417711 3/4 in. 2 in. 3 1/4 in. 3 3/8 in. 1 3/8 in.
(5.1 cm) (8.3 cm) (8.6 cm) (3.5 cm)
417714 1 in. 2 3/8 in. 313/16 in. 4 7/8 in. 1 3/4 in.
(6.0 cm) (9.7 cm) (12.4cm) (4.4 cm)
417717 1 1/4 in. 2 5/8 in. 43/16in. 47/8 in. 2 1/4 ili.
(6.7 cm) (10.6 cm) (12.4 cm) (5.7 cm)
417720 1 1/2 in. 31/8 in. 429/32 in. 521/32 in. 2 1/2 in.
(7.9 cm) (12.5 cm) (14.4 cm) (6.4 cm)
.. NOTE: There are no deneClor shields available for the 2. 2 112. or 3 in. models.
A
l 1
B
!
c
I
~o
OOlGS I
.
ANSUl and INERGEN are regislared "ademarks.
ANSUlINCORPOAATEO. ONE STANTON STREEt MARINETTE. WI 54143-2542
715.735.7411
Form No. F.V4152-1 C1V99Ansultncorporaled lItho in U.S.A.
ANSUL~
L~{gen.
System Components
UL EX-4510 3-1-99 Page 1-17
REV. 7
Cylinder Bracketing
Description
The cylinder bracketing is designed to rigidly support the
installed INERGEN~ agent cylinders. The bracketing com-
ponents are constructed of heavy structural steel. Bracket
assemblies are available in modules for two to six cylinders
and can also be connected together for any combination
over six. Bracketing can be assembled to support single
row, double row or back-to-back rows of cylinders.
Bracketing components are painted with a red enamel coat-
ing. Uprights and back frame assemblies can be bolted or
welded together, which ever makes the installation more
convenient.
Component Material Approvals
Bracketing Steel FMRC Approved
UL Listed
(EX-4510)
Shipping Assembly
Part No.
845120
845244
845121
845261
.. 845122
.. 845245
879638
879639
879640
879641
879642
.. 873257
.. 426592
I
..
873553
873554
873555
873556
418508
879413
873250
873251
873252
.
418502
873253
873254
873255
..
418503
873091
873092
871683
871682
871684
423027
Description
200 ft.3 (5.7 m3) cylinder strap (single cylinder)
200 ft.3 (5.7 m3) cylinder channel with nuts and bolts (single cylinder)
250 ft.3 (7.1 m3) cylinder strap (single cylinder)
250 ft.3 (7.1 m3) cylinder channel with nuts and bolts (single cylinder)
350 ft.3 (9.9 m3), 425 ft.3 (12.0 m3), 435 ft.3 (12.3 m3) cylinder strap (single cylinder)
350 ft.3 (9.9 m3), 425 ft.3 (12.0 m3), 435 ft.3 (12.3 m3) cylinder channel
with nuts and bolts (single cylinder)
Back frame assembly (2 cylinder)
Back frame assembly (3 cylinder)
Back frame assembly (4 cylinder)
Back frame assembly (5 cylinder)
Back frame assembly (6 cylinder)
Upright, for 200,250,350, and 435 ft.3 (12.3 m3) cylinders (used either for right side,left side
or center (center upright required when connecting seven or more cylinders in a row))
Upright, for 425 ft.3 (12.0 m3) cylinder (used either for right side, left side, or center
(center upright required when connecting seven or more cylinders in a row))
Single row or back-to-back row bracket foot (left side)
Single row or back-to-back row bracket foot (right side)
Double row bracket foot (left side)
Double row bracket foot (right side)
Center upright foot
Connector (required to hook together back frames for seven or more cylinders)
10.5 in. (26.7 cm) carriage bolt with nut (for single row 200 ft.3 (5.7 m3) cylinders)
11 in (27.9 cm) carriage bolt with nut (for single row 250 ft.3 (7.1 m3) cylinders)
12.5 in. (31.8 cm) carriage bolt with nut (for single row 350 ft.3 (9.9 m3) and
425 ft.3 (12.0 m3) cylinders)
13 in. (33.0 cm) carriage bolt with nut (for single row 435 ft.3 (12.3 m3) cylinders)
21 in. (53.3 cm) carriage bolt with nut (for double row 200 ft.3 (5.7 m3) cylinders)
22 in. (55.9 cm) carriage bolt with nut (for double row 250 ft.2 (7.1 m3) cylinders)
26 in. (66 cm) carriage bolt with nut (for double row 350 ft.3 (9.9 m3) and
425 ft.3 (12.0 m3) cylinders)
.27 in. (68.6 cm) carriage bolt with nut (for double row 435 ft.3 (12.3 m3) cylinders)
Cylinder clamp (2 cylinders)
Cylinder clamp (3 cylinders)
Weigh rail support - single row
Weigh rail support - double row
Weigh rail support - back-to-back rows
Weigh rail support back-to-back double row
..
Multi-Cylinder
..
&
~. I ",
~ ,e=9" t \
I I \ I I
J=1 ,-t:= " I II I
.Y /-- ,I II I
-3, f II II
I \! II II
f II II
I ,: II
I 1\
I II
I I
I
CYLINDER CLAMF'
I
I
I I
I I
I I
I ,
I I
I I
I : I
I ...
I I( 1---
I I, )
I ---
I ./
.......--..-
II I
1....---'
I
____I
II
II
II
II
II
II
LEFT
BRACKET FOOT
..
ANSUl and INERGEN are registered lradem3rks.
ANSUllNa:lRPORATED. ONE STANTON STREET. MAAINETlE. WI 54 1 43-2542
715-735-74\ 1
Form No. F.9309.7 Cl1999 Ansullncorporaled
Lill>o in U.S.A.
Single Cylinder
ClAMF'
CHANNEL
00::200
ANSUL!>
APPLICATION
INERGENll extinguishing agent used in
Ansul engineered systems is particularly
useful for hazards where an electrical. 0.00.-
conductive medium is essential or desirable;
where clean-up of other agents presents a
problem; where hazard obstructions require
the use of a gaseous agent; or where the
hazard is normally occupied and requires a
non-toxic agent.
The follOwing are typical hazards protected
by INgRGEN systems:
o Computer rooms
o Subfloors
o Tape storage
o Telecommunications/Switchgear
o Vaults
o Process equipment
o All normally occupied or unoccupied areas
where electronic equipment is either very
sensitive or irreplaceable
ENVIRONMENTAL IMPACT
INERGEN agent Is a mixture of three natu-
rally occurring gases: nitrogen, argon and
carbon dioxide. As INERGEN agent is
derived from gases present in the earth.s
atmosphere. it exhibits no ozone depleting
potential, does not contribute to global warm-
ing, nor does it contribute unique chemical
species with extended atmospheric lifetimes.
Because INERGEN agent is composed of
atmospheric gases. it does not pose the
problems of toxicity associated with the
chemically derived Halon altemative agents.
DESCRIPTION
INERGEN agent is a plentiful. non.corrosive
gas that does not support combustion nor
react with most substances. INERGEN agent
contains only naturally-occurring gases which
have no impact on the ozone or the environ-
ment in general. INERGEN agent is a mix-
ture of three inerting (oxygen diluting) gases:
52% nitrogen, 40% argon. and 8% carbon
dioxide. INERGEN agent extinguishes fire by
lowering the oxygen content below the level
that supports combustion. When INERGEN
agent is discharged into a room, it introduces
the proper mixture of gases that still allow a
ANSUL INCORPORATED
MAAINETTE. WI 54143-2542
715-735-7411
INERGEN@ FIRE
SUPPRESSION
SYSTEMS
DATA SHEET
person to breathe in a reduced oxygen
atmosphere. It actually enhances the body's
ability to assimilate oxygen. The normal
atmosphere in a room contains approximate-
ly 21% oxygen and less than 1% carbon
dioxide. If the oxygen content is reduced
below 15%, most ordinary combustibles will
not bum. INERGEN agent will reduce the
oxygen content to approximately 12.5% while
increasing the carbon dioxide content to
about 3%. The increase in the carbon dioxide 4
content increases a person's respiration rate
and the body's ability to absorb oxygen.
Simply stated, the human body is stimulated
by the carbon dioxide to breathe more deeply
and rapidly to compensate for the lower oxy-
gen content of the atmosphere.
PERFORMANCE
INERGEN is an effective fire extinguishing
agent that can be used on many types of
fires. INERGEN extinguishing system units
are designed for total flooding protection
against Class A surface burning, Class B
flammable liquid, and Class C fires occurring
within an enclosure by lowering the oxygen
content below the level that supports com-
bustion.
INERGEN agent has been tested by FMRC
for Inerting capabilities. Those tests have
shown that INERGEN agent, at design con-
centrations between 40% and 50%, has suc.
cessfully inerted mixtures of propane/air, and
methane/air.
PHYSICAL PROPERTIES OF INERGEN
Specific gravity
O.085Ibs./cu. ft. (1.36 kg/m3)
Vapor pressure
1925 psi @ 32 OF (132.7 bar@ 0 'C)
2175 psi @ 70 OF (149.9 bar@ 21 'G)
2575 psi @ 130 'F (177.5 bar @ 54 .c)
Vapor density
1.1 (Air = 1)
Approximate molecular weight
34
Form No. F.9313.8
EXTINGUISHING
AGENT
ORDERING INFORMATION
INERGEN filled cylinders for use in
engineered systems may be ordered in
sizes of 200. 250. 350, 425. and 435 cu. ft.
(5.7. 7.1, 9.9. 12.0, and 12.3 cu, m.).
APPROVAL
INERGEN agent complies with the NFPA
Standard 2001, Standard for Clean Agent
Fire Extinguishing Systems and EPA
Program SNAP, Significant New Alternate
Policy.
Agent is listed and approved by Underwriters
Laboratories, Inc. (UL) and FactorY Mutual
Research Corp~ration (FMRC).
Containers meet the applicable Department
of Transportation (DOT) specifications.
ANSUl and INERGEN are Irademarks of Msul
Incorporated or its affiliates.
Cl2000 Ansullncorporaled
LilhO In U.SA
ANSUL~
ANSUL 1Na:l~OAATEO
MARINETTE. WI 54143-2542
INERGEN MATERIAL SAFETY DATA SHEET
CONFORMS TO DIRECTIVE 2001158/EC
1. IDENTIFICATION OF THE SUBSTANCElPREPARATION AND OF THE COMPANYIUNOERTAKING
1.1. Identification of the preparation
Product Name: "INERGEN"
Chemical Name: NIA - This is a mixture/preparation.
CAS No.: N/A - This is a mixture/preparation.
Chemical Formula: N/A - This is a mixture/preparation.
EINECS Number: N/A - This is a mixture/preparation.
1.2. Use of the preparation
The intended or recommended use of this preparation is to discharge a FIRE EXTINGUISHING AGENT.
1.3. Company identification
Manufacturer/Supplier: ANsUL INCORPORATED
Address: One Stanton Street, Marinette, WI 54143-2542
Prepared by: Safety and Health Department
Phone: 715-735-7411
fnterneUHome Page: http://www.ansul.com
" "Date of Issue: September, 2004
1.4. Emergency telephone
CHEMTREC 800-424-9300 or 703-527-3887
2. COMPOSITIONIINFORMATION ON INGREDIENTS
2.1. Ingredient Name:
Chemical Formula:
CAS No.:
EINECs Number:
Concentration, Wt %:
Hazard Identification:
Ingredient Name:
Chemical Formula:
CAS No.: .
EINECS Number;
Concentration, Wt %:
Hazard Identification:
Ingredient Name:
Chemical Formula:
CAS No.:
EINECS Number:
Concentration, Wt %:
Hazard Identification:
Nitrogen.
N2.
7727-37-9.
231-783-9.
42.5%
See Heading 3.
Argon.
Ar.
7440.37-1.
231-147-0.
47%.
See Heading 3.
Carbon Dioxide.
CO2,
124-38-9.
204-696-9.
10.5 %.
See Heading 3.
3. HAZARDS IDENTIFICATION
FOR HUMANS:
Product:
EU Classification:
R Phrases:
S Phrases 9
Limit Values for Exposure:
Nitrogen:
Argon:
Carbon Dioxide:
Nonflammable Gas.
None.
Keep container in a well ventilated place.
None established.
None established.
OSHA PEL: 5,000 ppm.
ACGIH TLV-TWA: 5,000 ppm.
ACGIH TLV-sTEL: 30,000 ppm.
IDLH (Immediately Dangerous for Life and Health): 50,000 ppm.
Neither this preparation nor the substances contained in it have been listed as carcinogenic by National Toxicology
INERGEN (Continued)
Page 2
Program, IARC, or OSHA.
SIGNS AND SYMPTOMS:
Acute Exposure:
Eye Contact:
Skin Contact:
Inhalation:
Non-irritating gas.
Non-irritating gas.
Vapor is heavier than air and can cause suffocation by reducing oxygen available for breathing.
Breathing very high concentrations of vapor can cause Iightheadedness, giddiness, shortness of
breath, muscular tremors, and weakness, acrocyanosis. Also unconsciousness or even death.
Ingestion: Non-irritating gas. Not a likely route of entry.
Chronic Overexposure: No data available.
MEDICAL CONDITIONS GENERALLY AGGRAVATED BY EXPOSURE: None known.
FOR ENVIRONMENT:
Carbon dioxide is a global warming gas.
4. FIRST AID MEASURES
Eye Contact:
Immediately flush eyes with water for a minimum of 15 minutes. If redness, itching or a burning sensa-
tion develops, get medical attention. Treat for frostbite if necessary.
If redness, itching or a burning sensation develops, get medical attention. Treat for frostbite if neces-
sary.
Remove victim to fresh air. If cough or other respiratory symptoms occur, consult medical personnel. If
not breathing, give artificial respiration, preferably mouth-to-mouth. If breathing is difficult, give oxygen.
Consult medical personnel.
None needed.
Skin Contact:
"
"Inhalation:
.Ingestion:
5. FIRE-FIGHTING MEASURES
Non-flammable gas. Use agent appropriate to surrounding material.
Though gas cylinders are equipped with pressure and temperature relief devices, they should be removed from high
temperature areas or fires, if safe to do so, to avoid risk of rupture.
There are NO extinguishing media which must not be used for safety reasons.
NO special protective equipment is needed for fire-fighters. Wear protective equipment appropriate for the fire conditions.
6. ACCIDENTAL RELEASE MEASURES
For personal protection: Prevent direct skin and eye contact, see Heading 8.
Clean up: This substance will vaporize into the atmosphere, see Heading 13.
Carbon dioxide is a global warming gas.
7. HANDLING AND STORAGE
7.1. Handling
Care should be taken in handling all chemical substances and preparations.
Secure to prevent falling. Do not move without safety cap in place to prevent damage to valve.
See incompatibility information in Heading 10.
7.2. Storage
Store cylinders with restraints to prevent possibility of rupture. Store as a compressed gas in DOT-approved vessels. Keep
safety cap in place while in storage.
See incompatibility information in Heading 10.
Store in original container. Keep tightly closed until used.
Carbon Dioxide is a global warming gas.
7.3. Specific use
The intended or recommended use of this preparation is to discharge a FIRE EXTINGUISHING AGENT.
INERGEN (Continued)
Page 3
8. EXPOSURE CONTROLSIPERSONAL PROTECTION
8.1. Exposure limit values
Limit Values for Exposure:
Nitrogen: None established.
Argon: None established.
Carbon dioxide: OSHA PEL: 5,000 ppm, (9,000 mg/m3).
ACGIH TLV.lWA: 5,000 ppm, (9,000 mg/m3).
ACGIH TLV-sTEL: 30,000 ppm, (54,000 mg/m3).
IDLH (Immediately Dangerous for Life and Health): 50,000 ppm.
8.2. Exposure controls
8.2.1. Occupational exposure controls
8.2.1.1. Respiratory protection
Exposure to high concentrations requires the use of self.cantained breathing apparatus. Other respirators
will not protect in an oxygen deficient atmosphere.
8.2.1.2. Hand protection .
Use leather gloves when handling cylinders.
8.2.1.3. Eye protection
Use safety glasses with side shields or safety goggles.
8.2.1.4. Skin protection
No special equipment is needed.
8.2.2. Environmental exposure controls
None needed. The components of this product are normal atmospheric gases.
9. PHYSICAL AND CHEMICAL PROPERTIES
9.1. Generallnformation
Appearance:
Odor:
Colorless gas.
None.
9.2. Important health, safety, and environmental information
pH: 7 (at 25 OC).
Boiling poinllboiling range: -320oC.
Flash point: None to boiling.
Flammability (solid/gas): Not flammable.
Explosive properties: Not explosive.
Oxidizing properties: Not an oxidizer.
Vapor Pressure: 2205 psi @ 70 of. (21.1 oc)
Relative Density (Water = 1): 0.084Ibs/fl3.
Solubility:
- Water solubility: Carbon dioxide: 88 ml per 100 ml @ 20 oc.
Nitrogen: Insoluble.
Argon: Insoluble.
- Fat solubility: Not soluble.
Partition coefficient, n.octanollwater: Not determined.
Viscosity: Not determined.
Vapor density (Air = 1): 1.0.
Evaporation rate (Butyl acetate = 1): < 1, water only evaporates.
9.3. Other Information
Auto-ignition temperature:
Does not ignite.
INERGEN (Continued)
Page 4
10. STABILITY AND REACTIVITY
10.1. Conditions to avoid
Extremely high temperatures, as in a fire may cause a cylinder to fail.
There are NO known conditions such as temperature, pressure, light, shock, etc., which may cause a dangerous reaction.
10.2. Materials to avoid
Because of Carbon Dioxide: (AI + Na202), (Mg + Na20), Cs20, Li, K, Mg(C2HS)2' KC2H, Na, NaK, and Ti.
10.3. Hazardous decomposition products
Normally stable.
Hazardous polymerization will NOT occur.
There are no hazardous combustion or decomposition products.
11. TOXICOLOGICAL INFORMATION
Carbon dioxide:
Inhalation LCLO (human) = 100,000 ppm/min.
Can cause suffocation by reducing oxygen available for breathing. Breathing very high concentrations of vapor can cause
dizziness, shortness of breath, unconsciousness, or even death.
"
..
12. ECOLOGICAL INFORMATION
12.1. Ecotoxicity
This preparation consists of normal atmospheric gases.
'12.2. Mobility
This preparation consists of normal atmospheric gases.
12.3. Persistence and degradability
This preparation consists of normal atmospheric gases.
12.4. Bioaccumulative potential
This preparation consists of normal atmospheric gases.
12.5. Other adverse effects
Ozone depletion potential:
Photochemical ozone creation potential:
Global warming potential:
None.
None.
Carbon dioxide is a global warming gas.
13. DISPOSAL CONSIDERATIONS
Carbon dioxide is a global warming gas.
This preparation consists of normal atmospheric gases.
14. TRANSPORT INFORMATION
Hazard Class or Division: Compressed Gas N.O.s. (Mixture of compressed nitrogen, argon, and carbon dioxide),
Class 2.2, UN1956.
Label: Nonflammable gas.
Emergency response guide page number: 126; EMS (Inti): 2-04.
For additional transport information, contact Ansullncarporated.
Carbon dioxide is a global warming gas.
tNERGEN (Continued)
Page 5
15. REGULATORY INFORMATION
EU Classification:
R Phrases:
5 Phrases: 9
Exposure Limit Values:
Nitrogen:
Argon:
Carbon dioxide:
Nonflammable gas.
None.
Keep container in a well ventilated place.
None established.
None established.
OSHA PEL: 5,000 ppm, (9,000 mg/m3).
ACGIH TLV-lWA: 5,000 ppm, (9,000 mg/m3).
ACGIH TLV.STEL: 30,000 ppm, (54,000 mg/m3).
IDLH (Immediately Dangerous for Life and Health): 50,000 ppm.
EINECS Status: All components are included in EINECS inventories or are exempt from listing.
EPA TSCA Status All components afe included in TSCA inventories Of are exempt from listing.
Canadian DSL (Domestic Substances List): All components are included in the DSL or are exempt from listing.
Environmental restrictions: None are known.
Restrictions on Marketing and Use: None are known.
Refer to any other national measures that may be relevant.
16. OTHER INFORMATION
- (HMIS) HAZARDOUS MATERIAL IDENTIFICATION SYSTEM RATINGS:
HEALTH:
FLAMMABILITY:
REACTIVITY:
-L
i
i
4. Severe Hazard
3. Serious Hazard
2. Moderate Hazard
1. Slight Hazard
O. Minimal Hazard
(WHMIS) CANADIAN WORKPLACE HAZARDOUS MATERIAL
IDENTIFICATION SYSTEM RATINGS:
This product is rated: A Compressed Gas.
Format is from directive 2001/58/EC.
EINECS data is from hltp:/Iecb.jrc.iUexisting-chemicalsl
Data used to compile the data sheet is from Ansul Material Safely Data Sheet, February, 2002.
Toxicological information added from the EINECS ESIS (Existing Substances Information System).
A rating under WHMIS has been added, following the Canadian guidelines.
17. DISCLAIMER
THE ABOVE INFORMATION IS BELIEVED TO BE CORRECT, BUT DOES NOT PURPORT TO BE ALL INCLUSIVE AND
SHALL BE USED ONLY AS A GUIDE. ANSUL SHALL NOT BE HELD LIABLE FOR ANY DAMAGE RESULTING FROM
HANDLING OR FROM CONTACT WITH THE ABOVE PRODUCT.
MSDS available at http://www.ansul.com
ANSUl and INEAOEN aro trademarks 01 Ansullncorporatod or ill affilial...
ANSUlINCOAPORATEO. ONE STANTON S-mEET. MARlN€TTE. WI 54143.2542 715-735-7411
Form No. F.9759.4
C2004 Ansullncorporaled LJlho '" USA
ANSUL
INERGEN DESIGNER
Version 5. 1. 3
File: Data file: Z:\Jobs\Nestle Waters\Nestle Waters Data Room.inr
Job: 07 -896TP
Customer: Nestle Waters
Address: 4330 20th Street
Zephyrhills FL 33540
Country: Pasco
Hazard Area Information
Area: DATA
Design concentration 34.2% at 700 Fahrenheit
Estimated maximum concentration 42.4% at maximum hazard temperature 800 Fahrenheit
Net volume of enclosure 1056.0 cubic feet
Minimum INERGEN required 442.5 cubic feet
Appr,pximate INERGEN supplied 572. cubic feet
Flooding factor .419 cubic feet of INERGEN per cubic feet of enclosure volume
Maximum allowable wall strength 5.0 Ibs.lsq.ft.
Area consists of one volume
Volume 1: Length 11 ft Width 12 ft Height 8 ft
2 nozzles. Nozzle identifiers: 301, 302
Aaent Storaae Conditions
Number of cylinders: 1 each containing 572 cubic feet of INERGEN.
Total agent 572 cubic feet
Engineering units (ft, cu ft, psia) are specified
Calculation based on 70 degree Fahrenheit pre-discharge Pipeline Temperature
Pipe Data Input
Sec See Nominal Length Elev 90's Side Thru Unionl Qty Eql
Start End Pipe Size (ft) (ft) Tee Tee Cplg cu ft (ft)
1 2 1/2 - 40 T 0.01 0.00 0 0 0 0 38.00
2 3 o - DFL T 1.00 1.00 0 0 0 0 0.00
3 4 o - DFL T 0.00 0.00 0 0 0 0 Orifice
4 5 o - DFL T 3.00 3.00 0 0 0 0 0.00
5 6 o - DFL T 7.00 0.00 0 0 0 0 0.00
6 7 o - DFL T 4.50 0.00 0 0 0 0 0.00
7 301 1/2-DFLT 2.00 -1.00 1 0 1 0 286.00 0.00
7 302 1/2-DFLT 2.00 -1.00 1 1 0 0 286.00 0.00
1 (End of Data Input File Printout)
ANSUL
INERGEN DESIGNER
UL listed EX4510. FM ADDroved tP.I.13022155. ULC listed CEx1151
Version 5. 1. 3
~ile: Data file: Z:\Jobs\Nestle Waters\Nestle Waters Data Room.inr
Job Number 07 -896TP for Nestle Waters
Address: 4330 20th Street
Zephyrhills FL 33540
Country: Pasco
Aaent Storaae Conditions
Storage pressure is 2900 psia at 70 degrees Fahrenheit.
572 cubic feet of INERGEN stored in each of 1 cylinders.
Total agent in storage is 572 cubic feet.
Time to discharge 515 cubic feet (90% of INERGEN) is 83.1 seconds
Maximum pressure downstream of manifold orifice is 1757 psia
Concentrations
Area
95%
Time Cu Ft
Volume (sec) INERGEN
Maximum
Concentration
at Max. Temp.
Minimum
Concentration
at Min. Temp.
Requested
Concentration
at Min Temp.
DATA
1056.0 50 572.0 42.4% at 800F 41.8% at 700F 34.2% at 700F
Sea level equivalent oxygen: 12.1 % at 800F
Free Vent Calculation
Peak Maximum Wall Minimum Free
Area Rate Strength Vent Area
DATA 1143.6 cfm 5.0 Ibs./sq.ft. 44 sq. in.
Pressure Drop Results
Sec Sec Nominal Length Equiv Elev Tee/ Start Term Flow
Start End Pipe Size (ft) Length(ft) (ft) Mfld psia psia (cfm)
1 2 1/2 40T 0.0 38.0 0.0 MFLD 1377 1343 573.
2 3 3/4 80 T 1.0 1.0 1.0 MFLD 1343 1344 573.
3 4 ORIFICE .185 INCHES DRILL NO. 13 1344 614 573.
4 5 3/4 40T 3.0 3.0 3.0 614 806 573.
5 6 3/4 40T 7.0 7.0 0.0 806 804 573.
6 7 3/4 40T 4.5 4.5 0.0 804 802 573.
7 301 1/2 40T 2.0 4.6 -1.0 THRU 802 800 286.6
1 (Continued)
ANSUL
INERGEN DESIGNER
UL listed EX4510. FM ADDroved (P.I.) 3022155. ULC listed CEx1151
Version 5. 1. 3
ata file: Z:\Jobs\Nestle Waters\Nestle Waters Data Room.inr
,b ,~umber: 07 -896TP
ure Drop Results (Continued)
Sec Nominal Length Equiv Elev Tee/ Start Term Flow
1 End Pipe Size (ft) Length(ft) (ft) Mfld psia psia (cfm)
302 1/2 40T 2.0 6.7 -1.0 SIDE 802 799 286.3
31culation based on 70 degree Fahrenheit pre-discharge Pipeline Temperature
Pipe and Fittings
:; Sec Nominal Length Side Thru Unions/ Eql
1 End Pipe Size (ft) 90's Tee Tee Cplgs (ft)
2 1/2 40T 0.0 0 0 0 0 Cyl Valve 38 ft
3 3/4 80T 1.0 0 0 0 0
4 3/4 80T 0 0 0 0 Man. Orifice
5 3/4 40T 3.0 0 0 0 0
6 3/4 40T 7.0 0 0 0 0
7 3/4 40T 4.5 0 0 0 0
301 1/2 40T 2.0 1 0 1 0
302 1/2 40T 2.0 1 1 0 0
Nozzle Performance Summary
~zle Nominal Drill Drill Quantity (cu ft) Area
nber Pipe Size Number Diameter Discharged Name
301 1/2 40T 13 0.185 286.1 DATA
~02 1/2 40T 13 0.185 285.9 DATA
;ages/Errors
\NSUL 200 bar INERGEN DESIGNER Version number 5.1.3
:alculation done on 12/5/2007 at 1 :08:40 PM
2 (Continued)