HomeMy WebLinkAbout08-7916
CITY OF ZEPHYRHILLS
5335 - 8TH STREET
(813)780-0020
FIRE STANDPIPES PERMIT
7916
Permit Number: 7916
Permit Type: FIRE HOOD SUPPRESSION SYS
Class of Work: FIRE-HOOD SUPPRESSION SYS
Proposed Use: COMMERCIAL
Square Feet:
Est. Value:
Improv. Cost:
Date Issued:
Total Fees:
Amount Paid:
Date Paid:
Work Desc:
Address: 5963 GALL BLVD
ZEPHYRHILLS, FL.
Township: Range: Book:
Lot(s): Block: Section:
Subdivision: CITY OF ZEPHYRHILLS
Parcel Number: 10-26-21-0020-00000-0021
1,975.00
6/10/2008
130.00
130.00
6/10/2008 Phone:
INSTALLATION OF FIRE SUPPRESSION SYSTEM FOR HOOD
Name: ABC RESTAURANT
Address: 5963 GALL BLVD
ZEPHYRHILLS, FL. 33542
N
FIRE INSPECTION FEES
30.00
~'n& b
~,1-1r D ~{I..
Chapter 633, Florida Statutes, authorizes the City to charge and collect user fees to pay for the costs of fire
prevention and protection related activities such as inspections, plan review, administrative fees, and other
costs related to the aforementioned.
Complete Plans, Specifications and Fee Must Accompany Application. Commencement of work without written approval of
the Fire Department's Fire Marshal or required permits or opening up for commercial activity without an approved final
inspection shall be charged double permit fee per day of operation or a minimum of $100.00, whichever is greater. All
work shall be performed in accordance with City Codes and Ordinances.
"WARNING TO OWNER: YOUR FAILURE TO RECORD A NOTICE OF
COMMENCEMENT MAY RESULT IN YOUR PAYING TWICE FOR
IMPROVEMENTS TO YOUR PROPERTY. IF YOU INTEND TO OBTAIN
FINANCING, CONSULT WITH YOUR LENDER OR AN ATTORNEY BEFORE
RECO NG YO R NOTICE OF COMMENCEMENT."
CONTRACTOR SI URE I
PERMIT EXPIRES IN 6 MONTHS WITHOUT APPROVED INSPECTION
CALL FOR INSPECTION - 8 HOURS NOTICE REQUIRED
ZEPHYRHILLS FIRE RESCUE DEPT - Fire Marshal Office - 813-780-0041
!.13-780-0020
Date Received
Owner's Name
Owner's Address
City of Zephyrhills Fil'e
Permit Application
Fee Simple Titleholder Name
Fee Simple Titleholder Address
Job Address
Sub Division
G~//
g/v ,\
~1q{~
Fax-813-780-0021
Phone Contact for Permit
Owner's Phone Number
I Titleholder Phone Number I
II
II
Parcel #
/lo.u.z./
~ Lrn'
~ {)()lLJ - DOOQ:)
I
I
I I
-a:JZII
D Fire Alarm Installation
D Fire Pumps
D Fire Works
D Flammable Application- ANNUAL I I 'J? S, cru l Valuation of Project
D Fuel Tanks ~
"mwWJ,ga_1f$lm~~_~~tE~f?~~~41l~L~_~~,w___l
Contractor I Company I
Signature Registered Y I N Fee Current Y I N .1
Address I License # I
ELECTRICIANI Company
Signature . Registered Y I N Fee Current Y I N I
Address I License # I
PLUMBER
Signature
Address I
MECHANICALI
Signature .
Address
OTHER
Signature
Address
w ~
Directions:
D
D
D
D
D
D
Bio-Hazard Waste Storage - ANNUAL
Comm Exhaust Kitchen Hood/Duct
Controlled Bum
Emergency Generator < 30 kw
Emergency Generator> 30 kw
Fire Protection Maintenance - ANNUAL
~~~~
Sprinkler D 0 0 0 L-I
Do ooc=J
Do ooc=J
[XI 0 0 0 IM<<1
Fire Alarm
Hood Cleaning
Hood Suppression
D
D
D
D
D
D
D
D
D
D
D
D
Fumigation Tent
Hazardous Material (Tier II or RQ Facility) ANNUAL
Hood Installation
LP/Natural Gas-Installation
LP/Natural Gas-ANNUAL Sale
Places of Assembly-ANNUAL
Recreational Bum
Sparklers
Sprinkler System Installations
Standpipes (Sprinkler Sys)
Torch RoofinglTar Kettle
Waste Tire Storage ANNUAL
Company
Registered
Y/N
Fee Current
Y/N
License #
Company
Registered
Y I N I
I
~1/~~r:f4f @~ Il~
. .__~=-!!.!t~.;!l~-Lta,~_-1---t
Y/N
Fee Current
License #
Company
Registered
Fill out application completely.
Owner & Contractor sign back of application, notarized (Or, copy of signed contract with owner)
If over $2500, a Notice of Commencement is required (Mechanical work over $5000)
Supply two (2) sets of drawings with applicable documentation
Allow 10-14 days for review after submittal date. Parcel # - obtained from Property Tax Notice (http://appraiser.pascogov.com )
NOTICE OF DEED RESTRICTIONS: The undersigned understands that this permit may.be subjectto-"deed":restrictions"
which may be more restrictive than County regulations. The undersigned assumes responsibility for:compliancewith any
applicable deed restrictions.
UNLICENSED CONTRACTORS AND CONTRACTOR RESPONSIBILITIES: If the owner hashired:a-contractor or
contractors to undertake work, they may be required to be licensed in accordance with state and local regulations. If the
contractor is not licensed as required by law, both the owner and contractor may be cited for a misdemeanor violation
under state law. If the owner or intended contractor are uncertain as to what licensing requirements may apply for the
intended work, they are advised to contact the Pasco County Building Inspection Division-Licensing Section at 727-847-
8009. Furthermore, if the owner has hired a contractor or contractors, he is advised to have the contractor(s) sign
portions of the "contractor Block" of this application for which they will be responsible. If you, as the owner sign as the
contractor, that may be an indication that he is not properly licensed and is not entitled to permitting privileges in Pasco
County.
CONSTRUCTION LIEN LAW (Chapter 713, Florida Statutes, as amended): If valuation of work is $2'500.00 or more, I
certify that I, the applicant, have been provided with a copy of the "Florida Construction Lien Law-Homeowner's
Protection Guide" prepared by the Florida Department of Agriculture and Consumer Affairs. If the applicant is someone
other than the "owner", I certify that I have obtained a copy of the above described document and promise in good faith to
deliver it to the "owner" prior to commencement.
CONTRACTOR'S/OWNER'S AFFIDAVIT: I certify that all the information in this application is accurate and
that all work will be done in compliance with all applicable laws regulating construction, zoning and land
development. Application is hereby made to obtain a permit to do work and installation as indicated. I certify
that no work or installation has commenced prior to issuance of a permit and that all work will be performed to
meet standards of all laws regulating construction, County and City codes, zoning regulations, and land
development regulations in the jurisdiction. I also certify that I understand that the regulations of other
government agencies may apply to the intended work, and that it is my responsibility to identify what actions I
must take to be in compliance.
If I am the AGENT FOR THE OWNER, I promise in good faith to inform the owner of the permitting conditions set forth in
this affidavit prior to commencing construction. I understand that a separate permit may be required for electrical work,
plumbing, signs, wells, pools, air conditioning, gas, or other installations not specifically included in the application. A
permit issued shall be construed to be a license to proceed with the work and not as authority to violate, cancel, alter, or
set aside any provisions of the technical codes, nor shall issuance of a permit prevent the Building Official from thereafter
requiring a correction of errors in plans, construction or violations of any codes. Every permit issued shall become invalid
unless the work authorized by such permit is commenced within six months of permit issuance, or if work authorized by
the permit is suspended or abandoned for a period of six (6) months after the time the work is commenced. An extension
may be requested, in writing, from the Building Official for a period not to exceed ninety (90) days and will demonstrate
justifiable cause for the extension. If work ceases for ninety (90) consecutive days, the job is considered abandoned.
WARNING TO OWNER: YOUR FAILURE TO RECORD A NOTICE OF COMMENCEMENT MAY RESULT IN YOUR
PAYING TWICE FOR IMPROVEMENTS TO YOUR PROPERTY. IF YOU INTEND TO OBTAIN FINANCING, CONSULT
WITH YOUR LENDE AN A ORNEY BEFORE RECORDING YOUR TICE 0 COMMENCEMENT.
FLORIDA JURAT (F.S.
OWNER OR AGENll ~
Subscribed and sworn to (or affirmed) before me this
by
Who is/ar~f ,"onally 11.'10""".-5 me 0: has!hav~ produced
. -- as Identification.
CONTRACTOR
Subscribed and sworn to (or affirmed) befOre me this
by
Who is/are pe
nown fo ~e or has/have produced
- as identification.
ry Public
Notary Public
Zephyrhills Fire Rescue
6907 Dairy Road, Zephyrhills, FL 33542
Fire Marshal
Kerry Barnett
Bus (813) 780-0041
Fax (813) 780-0044
May 30, 2008
I have reviewed and approved the plans for a commercial hood suppression system
located at 5963 Gall Blvd. I have attached the comments for the plan approval. If there
are any questions please contact my office at 813-780-0041.
1. System shall be installed in accordance with all applicable NFP A codes, latest
editions.
2. Exhaust fan shall stay on w/make up air shutting down on system activation.
3. All electric and gas under hood shall shut down on system activation.
Inspections Required
1. Acceptance test. This would be done in coordinating with the alarm company.
Fire Chief Keith Williams
ZEPHYRHILLS FIRE DEPARTMENT
6907 Dairy Road, Zephyrhills, FL 33542
Bus (813)780-0041 Fax (813)780-0044
FIRE SERVICE USER FEES
Occupancy No.:
Plan No.: ?-$~
Business Name: G- ~
Business Address: S~ A-tl
Business Phone No.:
Business Fax No.:
Contact:
PLAN REVIEW FEES
B Site Plan N/C
Multi-Family/Commercial .06 sf
(Minimum Charge $25.00
D Plan Revisions DBL
SPRINKLER SYSTEMS
B 0 - 25 Heads $50
26 plus Heads $100
STANDPIPE SYSTEM
D Per Riser $50
FIRE PUMP
D Per Pump
FIRE AlARM SYSTEM
B 0 - 25 Devices $50
26 plus Devices $100
SUPPRESSION SYSTEMS
Wet $50
D~ $50
C02
~
KITCHEN EXHAUST
HoodIDucts
OTHER
B LP InstaJlation per tank
Fuel Tank Installation
(Per Tank)
D Natural Gas Installation
(Per System)
D Spray Booth
PLANS TOTALl3:&J
Comments:
$100
INSPECTION FEES
Annual N/C
1st Re-inspection N/C
2nd Re-inspection $100
3rd Re-inspection $250
4th Re-Inspection $500
(Business closed until
violations corrected)
SPRINKLER SYSTEMS
~ Hydro Undergrounds $45
Hydrostatic Test $65 per system
Acceptance Test $45 per system
Hydrant Flow $75
Cornraaor. ~~ ~
Billing Address: ~ '/.$*'.4;; tAl!:
7~o~ n ~"'f\p.J<:i
Billing Phone No.: ' I~- <;;s -3'3S-""7
Billing Fax No.:
Contact:
PERMIT FEE
$50
$50
Sprinkler
Standpipes
Fire Pump
\ Hoods S'1f
ire Alarm
LP Gas
Natural Gas
Fl;J8I Tanks- perlank
Sparklers
Fire Works
Camp Fire
Controlled Bum
Hood/Duct
Place of Assembly
Fire Protection
Flammable Application
Waste Tire storage
Generator < I<JN
Generator >30 KW
Bic-Hazard W~
Fumigation Tenting
Torch Pot/Applied
Haz. Materials
B
FALSE ALARM FEE
1st Alarm N/C
2nd Alarm N1C
3rd Alarm N/C
4th Alarm $100
5th Alarm $150
6th Alarm $200
NON COMPLIANCE $150
~
$50
$50
$50
$50
$100
$500
$25
$100
$50
$50 Annual
$25
$50 Annual
$50 Annual
$100
150
$100 Annual
$50
$50
$100 Annual
FALSE ALARM
TOTAL I
~
PERMIT TOTAL Lit:J
l?>o
FIRE ALARM SYSTEM
B System Acceptance $50
Recall Acceptance ~
OTHER
~ Fire WalllSmoke Wall $15 per wall
LP Gas $25 per tank
Natural Gas $25 per syam
$50
~ent 1 0'x1 0' or greater $. 1,5 per lent
Fire Pump rEJ
ire Suppression $30
System Acceptance
B Exhaust HoodIDuct $30
Re-inspection DBL
(other than annual)
D Inspection scheduled DBL
and cancelled less than
24 hours
B Construction Insp. N/C
Emergency Vehicle Ao $50
INSPECTION TOTAL~'
$50
$50
$50
$50
$50
GRAND TOTAL
Date: SL?D I () t{
InslJ!!Clor. '(i,- "'/ &r iUU/ -~
~ . ~ '.
. .'C .......;, .
.
.
TECHNICAL MANUAL
COMPONENTS
DESIGN
INSTALLATION
MAINTENANCE
1-" p n,~rl;r.."h~",
\,n,~, <'.lJyHV.J,t.'h'
1'rlJiT< <>" ,--ih. 0 ol~
Florida Ere ~ <.u<U- '--
t'.ffPA t: :?:>nhvrhills
COMi\.JERCIALFIB..E
, . EQU IPMENT CO.
Exbngul~ . Exit & Emergency Lighting. Restaurant Hoods
Llc.#385042000288 & Lic.#385042000188
BRUCE VARNADOE , ,_ ",'
P.O t.{131 \l~4<,J:,!
. . Box 2442' Brandon. R. 33509 E\.\ (liDi ()Sj,,'H,j,
r
IJ (I Li:I/
Specification
Sheet
TO
FUSIBLE
UNKS
TO DISCHARGE
PIPING
I
TO REMOn: MANUAL
PULL STATION
/
rBl
o
00
\
28.125
OPTIONAL
MINIATURE
SWITCH
CONNECTION
~
.
c
~
B
D
+-A-4
lJ028.41PC
Flow Mounting
Model Point Bracket
004882 No. A B C D Capacity Weight Used
I. 13.125 I. 10.625 ~I ~ PCl-160 7.00 19.62 25.37 17.31 5 33lbs. MB-15
~ PCl -300 8.00 25.06 30.81 22.75 10 531bs. MB-15
r (FRONT) TO GAS (SIDE) PCl-460 10.00 25.06 30.81 22.75 15 83lbs. MB-15
SHUT-QFF
PCl-SOO 10.00 35.81 41.56 33.50 20 1081bs. MB-1
OPTIONAL CYUNDER ENCLOSURE ALL DIMENSIONS IN INCHES
~
FEATURES
. UL and ULC Approved
. Complies with NFPA Standard 17 A and 96
. Meets the requirements of the Building Officials and Code
Administrators (BOCA)
. Approved by the City of New York Material and Equipment
Acceptance Division (MEA)
~
GENERAL
The KITCHEN KNIGHT~ 1/ Restaurant Kitchen Fire Suppression
System is a pre-engineered solution to appliance and ventilating
hood and duct grease fires. The system is designed to maximize
hazard protection, reliability, and installation efficiency. Automatic or
manual system activation releases a throttle discharge of potassium
carbonate solution on the protected area in the form of fine droplets
to suppress the fire and help prevent reignition after the discharge is
complete.
r
SYSTEM OPERATION
The KITCHEN KNIGHT II Restaurant Kitchen Rre Suppression
System has been designed for protecting kitchen hood, plenum,
exhaust duct, grease filters. and cooking appliances (such as fryers,
griddles, rangetops, upright broilers, charbroilers and woks) from
grease fires. The versatile state-of-thecart wet chemical distribution
technique, combined with dual, independent activation capability _
automatic fusible link or manual release - provides efficient, reliable
protection the moment a fire is detected. Once initiated, the
pressurized wet chemical extinguishing agent cylinder discharges a
potassium carbonate solution through a pre-engineered piping
network and out the discharge nozzles. The wet chemical discharge
pattern is maintained for a duration of time to ensure suppression
and inhibit reignition. Expanded capability provides remote manual
actuation, gas equipment shutdown, and electrical system shutdown.
This optional equipment will enhance the basic system functions and
be applicable when designing custom configurations to suit a
particular customer's needs and/or comply with local codes.
The operating temperature range of the Pyre-Chern KITCHEN
KNIGHT 1/ System is 32"F to 120"F (O"C to 49 "C).
8/112005
PC2oo1192(2)
The file &uppf! . Jill sysIem should be of1be sIlnd ~ wet
cheMlcBlpI8...:1~""naz:zI8~~by
~Ac:adxlndialddeUIIIIli~I8~In~..
wiIh I8IIIy Sp- III ...... .....-c-eo1G" end 4Ih!I!I be 1-.t _the ..
pIBIIIIIIIIc .11 11I~ d8IIice tar....... 1'h8~ .... bean .
.,... _ 01 the c:anIRII.... r... 1'h8'" cr..w......
... ayInder.... be a DAT.-nd8d....._ lIIamd..... of
225 pII(g. end a..-........... be........ an" 0JIndIr
"... for....II~..oQ. 1be.,...... be........ of......-c
and___-~~~.,.....,.......pIDlIIdBdby-
....D{JoI..lUJ1berol...... ......."'. ..-*iidlIn..... an a
... 11' , ........1nput.. to.. ccnIUI '-L...... -~
shaI be provided byllllnQl a..... an the pdaIIIiy........by
~ -'"
.. ~
1. CYUNDER COHJ'ROL HEAD-1nIBgnJI d8sign I8qUi8S no
sepe.* ........... c:yIncIes:. ~..... CIbIa......
lines far -*'... fu8IbIe InIc8 end apIianII naoI8 puI aIIIIIDn
pnMde _Idled me&8IA of""" An....,..~ -.........
.... .......... ~ moplan for...........fuIIbIe
b anc:I. ~.. an Iac8I ClIDCIIe. CI8Il be.... In... of 8
..... nwnueI pu118IBIIan. ~ faaIpn:d IBl:hnIque tDr
echIlM1g nee 1 n I _y Input.. CIbIe IiInIIIDn.
2. PIPING-UabIII8IWledPl*vDllitWrllk...... - ~"'~-tdelfgn
end. - - .... ......110 ....._ ___ toGDllDBllt......
... .........10 ~..... tIII8III ~.......... SdI8duIa40
bIedc IRJn, ~ or... I I...... prpe -.a be ...
.. 3. CYl.NlEFIS-~ Pym.a.n ~l '.., CWbu......
c:M...... ..... .... 81225 pIIg. 1nl:IudIs...... JI8UII8 far
... a.......... c:hecIra. 1.6. s.o. ..... end 8.D-g11aa....
JIRIIllIde 5. 10. 15. end 2D aa. ... ClJlI8AIUI!IMI*'-_ ......
8.... renge of ...6JaIb...-.
4. JI(l77I~ - CluJ be IxIId or lied will a..... ...... tIIIwIing
Ihe IIQZ2Ie to be toIaIIId BfIPlklud.t>A.~ .. ta 81 cfnIaIaoa..
-- -r--"- ---1':",- ,.- ---..- ....._... _ _____ __.___ __... _~_.
&ne to 1he canInII head.
1bB 8JIIIIlm .... haVB ~ 1BsIBd 10 Ihe Ul SIandan:J for Fire
~ ~- for Ph....... of ResI8unmt Coddno.Area.
UI.3DO. and I.III8d by lJwlde.w4IaoLabot..... Inc. It 8haII be
inIIIIIIlId In ~1Ce will.......... File PI.... ~~aIIon
Sl8uda.d No. 17A Wet CIBnIc8I ect.",wS)*.:n... end No. 96 -
. ___ for.. 1n.1" - - -. of EIMJnB1tb'the Removal at SIiDce
... __.......".. flam eamo...... CaoIdng EquIpment,
end caqIIy...... ~ 8IdJr8lllle aodIIs and ....... ReIer 10
~ J01 De EN IQIBiTI R8IIIIuImt FII8 8uppr;elslOlI
SJ*m ....... Pert No. 551274. far dBI8IIed ~ and
- ~''''''''JC6 iJIIn.JcIans,
/'"
./
5. REMOTE MANUAL PUU.SDmON'n~ apelaliug
fnBIIucIIans lIlIIh dcII.tie acIIan release 8Vdds caI1IIess system
dIlId~ MDimum i. - r ... d 150.. cable run wJIh 1116 in..
CllI1Ie end 40 comer....,. appIJ. A......,.., .. cable iq)ut
"'10 1ba QJInder canInlI.... pIUlIIdBs a 1nJe beck up in the
eII8nt.. fa8IbIe InII8 818 fouled.
B.. AJSIBLE l.N( Ul::11:\i11Ulll EQUIPMENT -ADco,....~ both
.... end tIImIn8I pIIIDeI_1l to mWI.b IIWenby 1R18ImpIfy
......... M .. r n I<.}o .COmPaIBIIB _Included tDr eIIcienl
! .... ... . . - r -.. FulIIbIe iniss RIIIIId for maximum
...... .._..... must be 0IdInd 1IIIp8I8IeIy. M8Icimum
.....- of 2D fcJIIbIB inial an 8 150" cable run will 40 c:omsr
....,. pnM:ie ~......... CCMMB(!or
7. AU'RJIMI1C GASstIJT.OFFVAlllE-~wIIl
.....-_.. .........10.. 8hut 011 of fueI_ .....Ib.d by
JlFM 17A. C8n "18lIIIl8l canImI.... .... RIgUIar
.........n: u 1lII... CII-* lor CCIRwfilo.tc& to .mea 1lIc:triciao..
.......... A, - - .... 01100 ft. CIIIlIe JUI1 wIIb SO IXlITIIIr pulleys
pnJllIde ---,..,..,
8. CORM:R PUU..EYSAND ACCESSORIe&- De8Ig..-j 10 ensure
18111b18....... funcIan a1Bstlld by lIndeIWiI..... I..aboIaIooIes.
/.
Pyro-Chem
Kitchen Knight II
PCL-300/460/600
Nozzle, Coverage Summary Sheet
KITCHEN ~.~~
KNIGHl: II Jj- e
Width Length Min. Max.
Nozzle Flow (In) (In) Height Height
Appliance Type Points Max. Side Area Sq. In (in) (in)
Deep Fat FJyer - Vat 2H 24 48
2 19 1/2 19 In.
Deep Fat Flyer (Low PraldmiIy) - Vat 2L 13 24
Deep Fat F/)'8r - Drip Pan (Vat 18" x 18" max.) 2H 24 48
2 Zl314 500 Sq. In.
Deep Fat F/)'8I" (Low ProxImity) ~ Drip Pan (Vat 18" x 18" max.) 2L 13 24
Deep Fat F/)'8r - Drip Pan (Vat 19 1/2 x 19" max.) 2H 24 48
2 25 3/8 495 Sq. In.
Deep Fat Fryer (low Proximity) - Drip Pan (Vat 19 112" x 19" max.) 2L 13 24
Two Burner Range 1H 40 50
1 12 28 In.
Two Burner Range (Low Proximity) 1L 13 24
Four Burner Range 2L 2 28 28 In. 34 48
Small Wok 1H 24 48
1 24" dia. 6" deplh
Small Wok (Low ProximIty) 1L 13 24
Large Wok 2H 24 48
2 30" elia. S" deplh
Large Wok (low Proximity) 2L 13 24
Small Griddle 1H 24 48
1 36 1080 Sq. 'n.
Small Griddle (low Proximity) 1L 10 24
Large Griddle 2H 24 48
2 48 1440 Sq. In.
Large Griddle (Low Proximity) 2L 10 48
Gas Radiant Char-Broiler 1H 24 48
1 26 624 Sq. In.
Gas RadIant Char-Broiler (Low Proximity) 1L 13 24
Large Gas Radiant Char-BmiIer 2H 36 48
2 36 864 Sq. In.
Large Gas Radiant Char-Broiler (low PraldmiIy) 2L 13 36
Lava Rock Char-Broiler 2L 2 26 624 Sq. In. 15 35
Natural Chan:oal Char-Broiler(max. fuel depth 6") 1H 24 35
1 24 480 Sq. In.
Natural Charooal Char-Broier (Low ProximIty) 1L 15 24
Mesquite Char-Broiler (max. fuel depth 6j 1H 24 35
1 24 480 Sq. In.
Mesquite Char-Broiler (low ProximIty) 1L 15 24
UprightISaJamander Broiler 1L 1 36W 280 Front edge;
above !he grate
Chain Broiler (Inlemal Chambeq 1L 1 ZlW 380 Front edge;
1-3" above !he chain
TIt SIdIIetJB/aisin Pan Covetage limilaIions are based on fiyer sizes includlng'!he drip boards.
Exception: Tilt SkiIIeIs and Bral&ing Pans may exceed maximum of 6 sq. ft.
- ,- ,- *"~~~~~.
Nozzle Flow Width Length Nozzle Placement (See
Plenum Type Points (It) (ft) manual for more detail)
SIngle BankJV Bank 1H 1 4 10 (J' - 6" from
end of plenum
-- .. .' lfi
" - "
Nozzle Flow Max. Side Perimeter Diameter Length
Duct Type Points (in) (in) (in) (in)
ReclangIelCiraJIar 2D 2 34 100 31 718 UnJinited
RectanglelCiraJlar (2) 2D 4 51 150 47 1/2 Unlinited
PC2001189(2)