HomeMy WebLinkAbout08-7892 CITY OF ZEPHYRHILLS
5335-8TH STREET
(813)780-0020 7892
COMM EXHAUST HOOD/DUCT PERMIT
Permit Number: 7892 Address: 5131 GALL BLVD
Permit Type: FIRE COMM EXH HOOD/DUCT ZEPHYRHILLS, FL.
Class of Work: FIRE-COM EXH KITCHEN HOOD/ UClrownship: Range: Book:
Proposed Use: NOT APPLICABLE Lot(s): Block: Section:
Square Feet: Subdivision: CITY OF ZEPHYRHILLS
Est. Value: Parcel Number: 11-26-21-0010-18500-0030
Improv. Cost: 4,800.00
Date Issued: 5/29/2008 Name: BBHARTI INVESTMENTS INC
Total Fees: 242.50 Address: 2151 SOUTHERN OAKS LN
Amount Paid: 242.50 LAKELAND FL 33813
Date Paid: 5/29/2008 Phone: (863)409-6422
Work Desc: INSTALL COMM EXHAUST KITCHEN HOOD/DUCT_
WENDLE SHEET METAL INC FIRE PERMIT FEES v 50.00 MECHANICAL FEE 82.50
FIRE PLAN REVIEW FEES!- 50.00 FIRE INSPECTION FEES 1 60.00
FIRE LIGHT TEST-Final
MECHANICAL FINAL
Chapter 633, Florida Statutes,authorizes the City to charge and collect user fees to pay for the costs of fire
prevention and protection related activities such as inspections, plan review,administrative fees,and other
costs related to the aforementioned.
Complete Plans, Specifications and Fee Must Accompany Application. Commencement of work without written approval of
the Fire Department's Fire Marshal or required permits or opening up for commercial activity without an approved final
inspection shall be charged double permit fee per day of operation or a minimum of$100.00, whichever is greater. All
work shall be performed in accordance with City Codes and Ordinances.
"WARNING TO OWNER: YOUR FAILURE TO RECORD A NOTICE OF
COMMENCEMENT MAY RESULT IN YOUR PAYING TWICE FOR
IMPROVEMENTS TO YOUR PROPERTY. IF YOU INTEND TO OBTAIN
FINANCING, CONSULT WITH YOUR LENDER OR AN ATTORNEY BEFORE
RECORDING YOUR NOTICE OF COMMENCEMENT."
CONTRACTOR SI NATURE P IT OFFICER
PERMIT EXPIRES IN 6 MONTHS WITHOUT APPROVED INSPECTION
CALL FOR INSPECTION - 8 HOUR NOTICE REQUIRED
ZEPHYRHILLS FIRE RESCUE DEPT- Fire Marshal Office- 813-780-0041
CITY OF ZEPHYRHILLS
5335-8TH STREET
(813)780-0020 7892
COMM EXHAUST HOOD/DUCT PERMIT
Permit Number: 7892 Address: 5131 GALL BLVD
Permit Type: FIRE COMM EXH HOOD/DUCT ZEPHYRHILLS, FL.
Class of Work: FIRE-COM EXH KITCHEN HOOD/ UClrownship: Range: Book:
Proposed Use: NOT APPLICABLE Lot(s): Block: Section:
Square Feet: Subdivision: CITY OF ZEPHYRHILLS
Est. Value: Parcel Number: 11-26-21-0010-18500-0030
Improv. Cost: 4,800.00
Date Issued: Name: BBHARTI INVESTMENTS INC
Total Fees: 242.50 Address: 2151 SOUTHERN OAKS LN
Amount Paid: LAKELAND FL 33813
Date Paid: Phone: (863)409-6422
Work Desc: INSTALL COMM EXHAUST KITCHEN HOOD/DUCT
WENDLE SHEET METAL INC FIRE PERMIT FEES 50.00 MECHANICAL FEE 82.50
FIRE PLAN REVIEW FEES 50.00 FIRE INSPECTION FEES 60.00
e4ISir Cr At.f4 7
FIRE LIGHT TEST-Final
MECHANICAL FINAL
Chapter 633, Florida Statutes,authorizes the City to charge and collect user fees to pay for the costs of fire
prevention and protection related activities such as inspections, plan review,administrative fees,and other
costs related to the aforementioned.
Complete Plans, Specifications and Fee Must Accompany Application. Commencement of work without written approval of
the Fire Department's Fire Marshal or required permits or opening up for commercial activity without an approved final
inspection shall be charged double permit fee per day of operation or a minimum of$100.00, whichever is greater. All
work shall be performed in accordance with City Codes and Ordinances.
"WARNING TO OWNER: YOUR FAILURE TO RECORD A NOTICE OF
COMMENCEMENT MAY RESULT IN YOUR PAYING TWICE FOR
IMPROVEMENTS TO YOUR PROPERTY. IF YOU INTEND TO OBTAIN
FINANCING, CONSULT WITH YOUR LENDER OR AN ATTORNEY BEFORE
RECORDING YOUR NOTICE OF COMMENCEMENT."
CONTRACTOR SIGNATURE P IT OFFICER
PERMIT EXPIRES IN 6 MONTHS WITHOUT APPROVED INSPECTION
CALL FOR INSPECTION - 8 HOUR NOTICE REQUIRED
ZEPHYRHILLS FIRE RESCUE DEPT- Fire Marshal Office- 813-780-0041
ZEPHYRHILLS FIRE DEPARTMENT
6907 Dairy Road, Zephyrhills, FL 33542
Fire Chief Keith Williams Bus (813)780-0041 Fax (813)780-0044
FIRE SERVICE USER FEES
Occupancy No.:
Plan No.: &—clSi Contractor:
Business Name: two a S Billing Address: A) /�.�et - .. b&
Business Address: _512 ) G>, -%A t Sv>-iJ
Business Phone No.: Billing Phone No.: —�S6 —�ZI`7
Business Fax No.: Billing Fax No.:
Contact: Contact:
PLAN REVIEW FEES INSPECTION FEES PERMIT FEE FALSE ALARM FEE
Site Plan N/C Annual N/C Sprinkler $50 1st Alarm N/C
Multi-Family/Commercial .06 sf 1st Re-inspection N/C Standpipes $50 2nd Alarm N/C
(Minimum Charge$25.00 2nd Re-inspection $100 Fire Pump $50 3rd Alarm N/C
Plan Revisions DBL 3rd Re-inspection $250 Hoods $50 4th Alarm $100
4th Re-Inspection $500 Fire Alarm $50 5th Alarm $150
SPRINKLER SYSTEMS (Business closed until LP Gas $50 6th Alarm $200
0-25 Heads $50 violations corrected) Natural Gas $50 NON COMPLIANCE $150
26 plus Heads $100 SPRINKLER SYSTEMS Fuel Tanks- per tank $50
STANDPIPE SYSTEM Hydro Undergrounds $45 Sparklers $100
Per Riser $50 Hydrostatic Test $65 per system Fire Works $500
FIRE PUMP Acceptance Test $45 per system Camp Fire $25
Per Pump $100 Hydrant Flow $75 Controlled Bum $100
FIRE ALARM SYSTEM Hood/Duct
8 0-25 Devices $50 FIRE ALARM SYSTEM Place of Assembly Annual
26 plus Devices $100 8 System Acceptance $50 Fire Protection $25
RE SUPPSSION SYSTEMS Recall Acceptance $50 Flammable Application $50 Annual
Wet $50 OTHER Waste Tire Storage $50 Annual
Dry $50 Fire Wall/Smoke Wall $15 per wall Generator<KW $100
CO2 $50 LP Gas $25 pertank Generator>30 KW 150
Other $50 Natural Gas $25 per system Bio-Hazard Waste $100 Annual
KITCHEN EXHAUST Fumigation Tenting $50
Hood/Ducts ; 0 Tent 10x10'or greater $15 per tent Torch Pot/Applied $50
OTHER 0J Fire Pump $45 Haz.Materials $100 Annual
LP Installation per tank $50 Fire Suppression $30
Fuel Tank Installation $50 System Acceptance
❑ (Per Tank) $50 Exhaust HoodlDuct $30 XZ
Natural Gas Installation $50 Re-inspection D
(Per System) (other than annual)
LI Spray Booth $50 Inspection scheduled DBL
and cancelled less than
24 hours
Construction Insp. N/C
Emergency Vehicle Act $50 i FALSE ALARM
PLANS TOTA ^ INSPECTION TOTAL[j PERMIT TOTAL L TOTA
L
GRAND TOTAL -
Comments:
Date:_____`�`L
Insl ctor: W lYnY
__ --� .. N4 c aB cow,,..; • 2088TH 7229 VIII h�INIIINI ICI
Permit No. .
yrNo_ ii __ _2j_ 17O11.O I _S_ L
•.THE t NDERSI NED bureby give informs you that theiiovflit will be made to eezlam raw p upady,and•in acc deice with•
•Secbam 713.13 of the'Fiorida Si us.s,the o��wJe in tioema diva•is providgd is this NOTICE OF I�y�TT:
+T1 of ?-EPMy"AuS 16. 1 .•PGt- S!+ i.-r 7-( . if-C.L. i c
I Descriptim pf propetty-(kgol ) t • '7T$L,
• a)Sorest Add, s: 1 .1 c.. • t . .
2.Oaiural description of improve: z jTp y 1Ae7i iN
3.Ownor Infocrosdad • dt01
• a)Name'aad'addz ss: L V� Yrlart S .. h G•
• b)Name aiddtss ade •of Sea simple tit ebolder(�adw isa'earns) • .
e),X crest in pmpe:ty
4.Codorador Iulbrneation 2151- rte.rte.
a)Noma and address: �t N :s♦. atJ- �.�; �✓n Ttn�• i-
b)Telephone No.: f�i1 s' FvocNo.,(�) •%3L-_. .. .
• • a)Name 5 Suety I��and adde+se: � .�_P_•_-_.
• .
b)Amount ofB md:
c)Telegbooe No.: ' . . • • 'Fax No.(Opt) R t:1182130 Rave: 10.198
6.Leadar ' . .. IT: 0.
00
•a)1�Tameandaddtisa: • J '� 05/22/08 -- - Ofr Clark
. 1
7.Tdi_y of petaou•within the Scam of Flat<xla dojgIaj by amw upon wiom,sodas or odmr i .iit may be aervted.
• a)Naima sand address: `'
b)TelcpbbmNo.: , • Fax No.(OPL)
8 I sdditian,to bimoeif ow nw desigxwamAs SaIiowiag prison m mceivc a copy of tbo Li®ar'sNotice as provided,isi Seetaon
713.13(1x)N address: •a A K •P� • 21S1 �► , Y13 �c
•b)Tclaphohallo.: . _ ' _ -piat.Nd,(Opt) x I:
• 9.Expicat'ton date of Notice of Conomweemsat(the 4 date is one'yee ftm ibe deft ofzccwdbigimksa a ditlriaof dais .
WARNING TO OQYNEII: ANY PAYM R S MADE BY THE OWNER AFTER THE EXPIRATION OF THE NOTICZ OF
COMb=CEMENT ARE CONSIDERED IMPYtOPER PAYMENTS UNDBRyCBAPM 713,J'ART I,SECTION 713J3 .. .
PLORWA STAT ThU AND CAN RI$ULT IN YOUR PAYING Tt+VIC •MfR OV TIB TO YOUR JIOFZRT V
A NOTICE OF OODMENCEMENT MUSS'lei RECO*DED AND•PO TED ON THE 30B MM M OORE 72M FIRST . C.
•IN 'ECTTON. IF YOU-INTEND•TO OBTAIN YINANC NG1 CONSULT YOUR LENDER O!AN ATTO NEY BEFORE •
COM1Y INiCING WORK OR RECORDING.YOUR NOTICE OF CObawmc aw. • : • • . • �''►-
COMM OF! illy�1ilr SMIe d :',• _.�=`'`"s� .{� r
•
ZV't101aMllalaa�Mle0alS1.aw S�erDa�eaCC�f.aerart)wadsAiaYariad
tlMttaltflea W P,iaaNasc ti I.1>`! r'l
The f egom�g.fossnmàit b. ue me ibis day of 1'A'r�? -by +�13.3. -
7[L �
tr ( 6f=dtcd ',c.&-a_oQ.tsuatee.i4my
.
• m fact) (name of petty on ba�half of w►Lom erne aaaeasbd). •
Pe ally Known OR Produced Idao,fieadi a Notary Sigesthwe
Type.of Idcntificstian Produced fL1 rridki Namt(pmt) !a'1 4t
Vesificatioo pursamnt to Scctioa.92.SL5,Florida Statmca.•U nda'paadtica of parjtsy,I declasa.that I bava reed the rogoiag emd d t
« ;n tt a fee to d16 bast of my know1ed a and belief. .
City of Zephyrhills
BUILDING PLAN REVIEW COMMENTS
Contractors eowner:
L/' ngtt, . JAZI
Date Received: ��—
Site: /J J -
Permit Type: cLt 1
Approved w/no comments:❑ Approved w/the below comments: Denied w/the below comments: ❑
This comment sheet shall be kept with the permit and/or plans.
4i4g
ill Burgess— uilding Official Date Contractor and/or Homeowner
(Required when comments are present)
813-780-0020 City of Zephyrhills Fire 2/ Fax-813-780-0021
Permit Application
Date ReceivedPhone Contact for Permit (� I
Owner's Name Cj Owner's Phone Number ® p p
Owner's Address etri
Fee Simple Titleholder Name Titleholder Phone Number
Fee Simple Titleholder Address
T
Job Address 1 c i 2 e h r k i Is Lot#
Sub Division Parcel# o ` ( -OO S 0' 0e301
30
Bio-Hazard Waste Storage-ANNUAL Fumigation Tent
Comm Exhaust Kitchen Hood/Duct Hazardous Material(Tier 11 or RQ Facility)ANNUAL
Controlled Bum Hood Installation
Emergency Generator<30 kw LP/Natural Gas-Installation
Emergency Generator>30 kw LP/Natural Gas-ANNUAL Sale
Fire Protection Maintenance-ANNUAL Places of Assembly-ANNUAL
y e-mi ®nOther
Sprinkler O ❑ ❑ Recreational Bum
Fire Alarm ❑ O O I Sparklers
Hood Cleaning ❑ ❑ ❑ II L1 Sprinkler System Installations
Hood Suppression ❑ ❑ O I Standpipes(Sprinkler Sys)
Fire Alarm Installation Torch Roofing/Tar Kettle
Fire Pumps Waste Tire Storage ANNUAL
Fire Works
Flammable Application-ANNUAL // p(Q, O O Valuation of Project
fl Fuel Tanks
Other:
..., ,::...,. a�a�Cc -^�xsr.�.._.s..;-•�a� ,'.�`,'""»'e:�z��:�� �,5&�` T � .,.�': .sd,�`�' Y' :�`.1 ':
Contractor Company
Signature Registered Y/N Fee Current Y/N
Address License#
ELECTRICIAN Company
Signature Registered Y/N Fee Current I Y/N
Address License#
PLUMBER Company
Signature Registered Y/N Fee Current Y/N
Address r ' License#
MECHANI r z Company Q Q
Signature i Registered Y/N Fee Current Y/N
Address _Ur f, 'cense#
OTHER Company
Signature Registered Y/Nj Fee Current Y/N
Address License#
x�'�?'n�:�s�......<a�ta. ,. ,�...,,,�.a�....,�.• ��,.� .���w.rw�.,�;�— -- x ... ..,-- r 's��. _ .. ' a s.....�,..s.:�:�.�.v,...,<.a�, ..,�:.c e.
Directions:
Fill out application completely.
Owner&Contractor sign back of application,notarized(Or,copy of signed contract with owner)
If over$2500,a Notice of Commencement is required(Mechanical work over$5000)
Supply two(2)sets of drawings with applicable documentation
Allow 10-14 days for review after submittal date. Parcel#-obtained from Property Tax Notice(http://appraiser.pascogov.com)
NOTICE OF DEED RESTRICTIONS: The undersigned understands that this permit may subject'to"deed",restrictions"
which may be more restrictive than County regulations. The undersigned assumes responsibility for compliance with any
applicable deed restrictions.
UNLICENSED CONTRACTORS AND CONTRACTOR RESPONSIBILITIES: If the owner has hired :a contractor or
contractors to undertake work, they may be required to be licensed in accordance with state and local regulations. If the
contractor is not licensed as required by law, both the owner and contractor may be cited-for a misdemeanor violation
under state law. If the owner or intended contractor are uncertain as to what licensing requirements may apply for the
intended work, they are advised to contact the Pasco County Building Inspection Division—Licensing Section at 727-847-
8009. Furthermore, if the owner has hired a contractor or contractors, he is advised to have the contractor(s) sign
portions of the "contractor Block" of this application for which they will be responsible. If you, as the owner sign as the
contractor, that may be an indication that he is not properly licensed and is not entitled to permitting privileges in Pasco
County.
CONSTRUCTION LIEN LAW(Chapter713, Florida Statutes, as amended): If valuation of work is $2,500.00 or more, I
certify that I, the applicant, have been provided with a copy of the "Florida Construction Lien Law—Homeowner's
Protection Guide" prepared by the Florida Department of Agriculture and Consumer Affairs. If the applicant is someone
other than the "owner", I certify that I have obtained a copy of the above described document and promise in good faith to
deliver it to the"owner" prior to commencement.
CONTRACTOR'S/OWNER'S AFFIDAVIT: I certify that all the information in this application is accurate and
that all work will be done in compliance with all applicable laws regulating construction, zoning and land
development. Application is hereby made to obtain a permit to do work and installation as indicated. I certify
that no work or installation has commenced prior to issuance of a permit and that all work will be performed to
meet standards of all laws regulating construction, County and City codes, zoning regulations, and land
development regulations in the jurisdiction. I also certify that I understand that the regulations of other
government agencies may apply to the intended work, and that it is my responsibility to identify what actions I
must take to be in compliance.
If I am the AGENT FOR THE OWNER, I promise in good faith to inform the owner of the permitting conditions set forth in
this affidavit prior to commencing construction. I understand that a separate permit may be required for electrical work,
plumbing, signs, wells, pools, air conditioning, gas, or other installations not specifically included in the application. A
permit issued shall be construed to be a license to proceed with the work and not as authority to violate, cancel, alter, or
set aside any provisions of the technical codes, nor shall issuance of a permit prevent the Building Official from thereafter
requiring a correction of errors in plans, construction or violations of any codes. Every permit issued shall become invalid
unless the work authorized by such permit is commenced within six months of permit issuance, or if work authorized by
the permit is suspended or abandoned for a period of six (6) months after the time the work is commenced. An extension
may be requested, in writing, from the Building Official for a period not to exceed ninety (90) days and will demonstrate
justifiable cause for the extension. If work ceases for ninety(90)consecutive days, the job is considered abandoned.
WARNING TO OWNER: YOUR FAILURE TO RECORD A NOTICE OF COMMENCEMENT MAY RESULT IN YOUR
PAYING TWICE FOR IMPROVEMENTS TO YOUR PROPERTY. IF YOU INTEND TO OBTAIN FINANCING, CONSULT
WITH YOUR LENDER OR AN ATTORNEY BEFORE RECORDING YOUR NOTICE OF CO NT.
FLORIDA JURAT(F.S.117.03) %'
OWNER OR AGENT d before me this C NTRA ORs r or affi 1J�)
Subscribed and sworn to(or affirmed) rmed)before me this
by by
Who is/are personally known to me or has/have produced Who is/are personally known to me or has/have produced
as identification, as identification.
Notary Public Notary Public
Commission No. Commission No.
Name of Notary typed,printed or stamped Name of Notary typed,printed or stamped
Wendle Sheet Metal Inc. Jobsite: Bbharti Investments
#CSC056662—335 N Buena Vista Drive 5131 Gall Blvd
Lake Alfred, FL 33850 Zephyrhills FL
Phone 863-956-2217—Fax 863-956-5102 Contact: Patel
863-409-8987
Mininum 10 ft clearance
1785 CFM
filtered
replaceme t
2100 cfm air fan
upblast
xhaust fan
40' 4/12
grease 4 pitched r�
duct cup 18' shingle
roof
support hinged
flange mineral curb
wool
duct
4 ft Supply flex
per NFPA approx.
96-4.2.3.2
12 ft 7'- drywo.11- ovftr, d ceiling
12' x 12' 16 18•
ga externally
welded stack
sized for a
rein. 1500 fpm t31,ILJiNu,SHj.LL Q.vIP?,`e wITt;
velocity A.I.,?:AI'YLI ,r;BI O.UILD?NG,
1.EC"RICAL, '_l':MBT G AN1L
f )'S
baffle "" '--'.
type / 4 F
grease y 1 T
filters
front supply
plenum
grease
cup fire extinguishing system by
42• others
3'
standoff 7 ft galvanized,
drywall min, type 1 hood with
over 6 78' front supply plenum
block wall
Cooking
equipment Exhaust flow based on
by others medium temperature cooking
equipment per FBC 507.13.2
Note: Hood, grease removal devices, exhaut fan, and duct shall have a
clearance of 18' to combustible materials, 3' to limited combustible
material and 0' to non combustible material per NFPA 96-4.2.1. Where not
possible a clearance reduction system of 22 gage on 1' mineral wool
batts reinforced with wire mesh spaced out 1' on non combustible
spacers is provided for a 3' l arance to combustible material per NFPA
96-4.2.3.2 APR'O'VEb
i'y Fire Marsha'. of Zephyrhilis
with conr pro ides wit plan(s)
Wendle Sheet Metal Inc. Jobsite: Bbharti Investments
#CSC056662—335 N Buena Vista Drive 5131 Gall Blvd
Lake Alfred, FL 33850 Zephyrhills FL
Phone 863-956-2217—Fax 863-956-5102 Contact: Patel
863-409-8987
HOOD SPECIFICATIONS
HOOD: 7 FT X 42"- 18 GA GALVANIZED,24 INCHES HIGH AS PER NFPA CODE 96-
5.1,5.3&6.2.AND FMC 507.4 AND FMC 507.7,507.12-13. DESIGNED TO
COMPLETELY COVER COOKING EQUIPMENT AND EXTEND MINIMUM 6"BEYOND
THE EDGE OF THE COOKING SURFACE ON ALL OPEN SIDES.
FILTERS: HIGH VELOCITY BAFFLE TYPE AS PER NFPA CODE 96-6.1,6.2.3 AND FMC 507.11.
FILTERS INSTALLED AT A MINIMUM ANGLE OR 45 DEGREES TO THE
HORIZONTAL AND ARRANGED TO CAPTURE AND DRAIN GREASE TO GREASE
CUP
HOOD HEIGHT: APPROXIMATELY 6 FT 8 INCHES FROM THE FLOOR.CEILING CLEARANCE
MINIMUM 18"TO COMBUSTIBLES PER NFPA 96-4.2.1
EXHAUST STACK: EXHAUST DUCT SYSTEM IS AN INDEPENDENT SYSTEM DESIGNED FOR THE
REMOVAL OF KITCHEN EXHAUST WITHOUT ANY OBSTRUCTIONS THAT MAY
COLLECT GREASE/RESIDUE.CONSTRUCTED OF 16 GAGE METAL, EXTERNALLY
WELDED(CONTINUOUS, LIQUID-TIGHT) SIZED FOR A MINIMUM OF1500 FPM
VELOCITY.TERMINATES 18"ABOVE ROOF LINE WITH WELDED FLANGE FOR
SUPPORT.AS PER NFPA CODE 96-7.5,96-7.3,96-7.8 AND FMC 506.3.3,506.3.4,
506.3.6 PROTECTED AS PER NFPA CODE 96-4.2.3 AND FMC 308.6. DUCT TO
HOOD CONNECTIONS TO BE WELDED LIQUID TIGHT.
ACCESS DOOR: AN OPENING SHALL BE PROVIDED AT EACH CHANGE IN DIRECTION OF THE
DUCT FOR PURPOSES OF INSPECTION AND CLEANING.THIS ACCESS DOOR
SHALL BE MADE TO BE REMOVED WITHOUT THE USE OF TOOLS PER FMC
506.3.10 AND NFPA 96-7.3
EXHAUST OUTLET: LOCATED AT LEAST 10 FT FROM AIR INTAKE AS PER FMC 506.3.14, 507.16 AND
NFPA CODE 96-7.8.
EXHAUST FAN: 2100 CFM @ 1/2"S.P., EXHAUST AIR FLOWS AWAY FROM THE SURFACE OF
ROOF AS PER NFPA CODE 96-7.8.2, 96-8 AND FMC 507.13.1-4
EXHAUST DISCHARGE: ROOF TERMINATION TO BE 40 INCHES ABOVE THE ROOF LINE AS PER FMC
506.3.14.1 AND NFPA CODE 96-5-8.2.
REPLACEMENT AIR: 1785 CFM FILTERED AIR INTO A SUPPLY PLENUM AT THE FRONT OF THE HOOD
AS PER NFPA CODE 96-8.3, AND FMC 508.1.
Note: Hood,grease removal devices,exhaust fan and duct shall have a clearance of 18"to combustible
material, 3"to limited combustible material and 0"to non combustible material per NFPA 96-4.2.1.Where not
possible a clearance reduction system of 22 gage on 1"mineral wool bats reinforced with wire mesh spaced
out I"on non combustible spaces is provided for a 3"clearance to combustible material per NFPA 96-
4.2.3.2.
BUILDING SHALL '"'OMP),
ALL APPLICid3I.r° i! i_. )?Nz .
EL.EC"..-RICAL iT i.' ''i 8NC_
n.t
haLttc E"ai�
'- ---.-..._.- w_......... .......
l I
,
Measurements B
..
DU8FA 13 12 19314 11/2 19 93/4 13 20
F f' DUBFA I 131/2 193/4 11/2 19 93/4 13 20
DU16FA 151/2 24 1112 19 115/8 13 35
DU25L/HFA 233/4 24 1/2 1 1/2 21 203/4 16 50
DU30LIHFA 23 3/4 24 1/2 1 1/2 21 20 3/4 16 50
- _ DU33L/HFA 23 3/4 241/2 11/2 21 203/4 16 50
DU50LIHFA 2512 281/4 112 21 23 16 55
# ^' DU75LIHFA 28 1/4 31112 2 243/4 23 20 60
r, s.
sn?r DU85L/HFA 28 1/4 311/2 2 243/4 23 20 80
Motor Availability
FeatPjrres S, Benefits _
ComDleteiy enclosed drive compartment
protects moor from airborne contaminates
Forced fresh air cools the motor compartment,
ensures long motor life DU8FA na na na
Variaole speed control is standard on DU8FA thru DUBFA 11111 na na na
DU75FA,allows up to 50%reduction in speed OU16FA na na na
Non overloading backward inclined wheels,blades DU25LIHFA na * na na
and islets fabricated from 3003-H14 aluminum DU30UHFA na
All sizes car be wall mounted na na
Quick release latches allow for easy access to DU33UHFA na na
motor compartment DU5OL/HFA na * na
Standard emergency disconnect switch DU75LIHFA na na
DU85LIHFA I na consult na
C ptioms
Fate:'Speed control can be wired for either Low or High speed
Bird Screen Three phase motors are open drip proof
Grease Collection Box (DU25&larger)
Back Draft Damper Certifications
Roof Curbs
Epoxy Coating U Models DU8FA thru DU16FA are Listed under UL705(Electrical).Models DU25FA thru
®� DU85FA are UL762 Listed(Restaurant Exhaust Appliance).
Performance shown is for installation Type A,Free Inlet,Free Outlet.Performance includes effect of bird
Static Pressure In Inches W.G. screen in the air stream;Speed(RPM)shown is nominal and performance is based on actual speed of test-
. . ... �. . . , r
DU8FA 1/8 1690 3485 365 320 275 185 70 - - - -
DU9FA 1/8 1725 4064 585 515 440 360 250 140 - _ _
DU16FA 1/8 1620 4665 1010 900 815 690 580 410 230
DU 25L FA 1/4 1000 3077 783 654 520 389 237 - -
DU25HFA 1/4 1150 3538 900 825 746 651 542 233 - - -
DU30LFA 1/4 1500 4614 1182 1127 1072 1013 954 884 810 636
DU30HFA 1/4 1600 4922 1261 1202 1143 1081 1017 943 864 679
DU33LFA 1/3 1520 4999 1281 1221 1161 1098 1033 958 878 690
DU33HFA .e3 1700 5229 1342 1290 1238 1179 1115 1051 985 831 -
DU50LF/: i 1/2 1450 5220 1934 1859 1780 1694 1604 1511 1403 1164 909
. DU5f1FA ( 1/2 1670 6012 2181 2117 2052 1988 1922 1855 1787 1616 1419
D'J75LFA 3/4 1125 4639 2497 2372 2246 2089 1946 1785 1609 - -
DU75HFA 3/4 1150 4742 2596 2475 2352 2218 2084 1932 1773 1349 -
DU85LFA 3/4 1400 5040 3205 3039 2909 2763 2606 2445 2309 1987 1703
DU85HFA 3/4 1550 5580 3337 3212 3108 2994 2882 2774 2657 2381 2124
GALVANIZED SUPPLY FAN
aq, FILTER
AIR INTAKE THROUC}I FILTER
SUPPLY FAN
ELECTR[CAL DROP"~ °2
CURB WITH 20 GA CONSTRUCTION
3' t UNTINWUS SLASHING
Wheel Diweeler CFM AIR DELIVERY t3 RPM Shorn
Over Rim Over BladesM.) 0.0• o.r . .5 SP SP 0 f 0.r No. Volts Stock
VlfitBh SP SP SP SP Speeds RPM HP 60 Hr .
Amps No. Earh YA.
9'% 9'h Th # 992 961 915 864 726 513 — 1 1075 1/6 115 2.8 ✓
$173.75 23.0
9''hs 9'h 9'h # 1529 1517 1483 1416 1326 926 397 1 1075 1/4 175 4.0 ✓
# 1938 1798 1739 1656 1543, 1407 1b84 1033 199.00 29.0
9 9'h 91h # 1495 1492 1461 1406 1342 1122 803 4 1024 1/3 115 5.1 ✓
# 1325 1325 1319 1284 1212 990 722 965 250.50 31.0
# # 1165 1164 1142 1033 836 510 913
WheelDiameter CFM MR DELIVERY*RPM SHOWN
Over Rim Over BladeM)Nfidlh SP SP SP SP SP SP 1. l.r No. Volts Stock
SR SP Speeds RPM HP 60 Hz Amps No. Each
WI
# # # 1824 1704 1456 932 — 1024
111/8 10% 8 # 1653 1616 1550 1470 1010 568 — 915 1430 1392 1341 1255 871 479 — 4 830 1/2 115 8.8 ✓ S280.50 32.0
# 1266 1219 1159 1050 631 405 — 802
# # 2374 2218 2021 1793 1643 1294 1078
11'h 10% 10% # # 2093 1991 1828 1499 1029 558
# # 1819 1740 1587 981 678 526 4 892 3/4 115 11.2 ✓ 325.00 40.0
# # 1547 1467 1129 663 558 '474 803
Wheel Diameter M•) 1.1' l.r aM MR EUV RY®R M l SHIOF�MI l.r l.8• No.
Over Rim Over Blades Wiidlh SP SP SP SP SP SP SP SP Speeds RPM l P 6060 Hv Amps No. Each NII.
# 2780 2775 2740 2660 2530 2170 1850 951 13156 12% 9'h # 2370 2360 2310 2200 2020 1815 1555 3 893 1 115 14.0 ✓ $374.25 520
230 7.5
# 1940 1910 1855 1805 1750 1650 — 884 ✓ 374.25 52.0
For Stock 5hpp Blares No •. Position No. Per Pair VVt.
Bottom&Up $19.34 1.4
& Any Four 10.82 1.3
No. _ & Any Four 14.43 1.5
Any Four 20.86 2.7
Ob=Shipped Directly from Manufacturer ✓=Extended Warranty Available *=New Item NaRADI OW. 1 4045
Ill.-
B-LINE SPANS TWO ROOF JOIST
3' CLEARANCE REDUCTIDU I N
METHOD PER NFPA 96
16 GA. WELDED EXHAUST DUCT
/ 1' NON-COMBUSTIBLE SPACER
8 COMBUSTIBLE MATERIAL
3/8' ALLTHREAD
1B, rWIREMESH (P SILET METAL
RAL WOOL BAT
HANGER WELDED TO HOOD . GA. SHEET METAL
13'�-DUCT--A3'I
HOOD
SECTION VIEW
0$
V NON-COMBUSTIBLE SPACER
''/ wood rafter
3/8' truss 16 GA. WELDED EXHAUST
bolt STACK
3/8'
coupling V AIR SPACE
lHhillII )x( Jjjfff 1' THICK MINERAL WOOL
PANELS OM
'IIIIIHIIIIHI Z N I11llhIIIII1HO4-COMBUSTIBLE
aUthread SPACERS
COMBUSTIBLE MATERIAL
hanger welded _i
to hood 13' DUCT 3
hood
PLAN VIEW
Hanger Detail n
BUILDING SHALL 1TOMPI;v `:^r'1`r1
ALL AYPI.Ii r;k3L LfLIILI)!NG.
EL.EC"t'R.ICA.L; PLUMB NG AN
Zephyrhills Fire Rescue
6907 Dairy Road, Zephyrhills, FL 33542
Fire Marshal Bus(813) 780-0041
Kerry Barnett Fax(813) 780-0044
May 21, 2008
Plan Review Comments
I have reviewed and approved the plans for a commercial hood located at 5131 Gall Blvd.
under the following conditions. My comments have been placed below. Please contact
me if you have any questions with regards to my comments.
1. Hood and duct shall comply with all current standards of NFPA 96.
2. Roof top fan shall be hinged and have a grease cup.
3. Hood duct shall be wrapped with fire rated insulating blanket
4. From the hood down to the floor and width of hood exposure protection shall be
provided on wall. Stainless steel or tile will be acceptable..
Inspections required:
1. Light test on hood and duct. Duct shall be tested before being installed; hood shall
be tested prior to being installed. After hood and duct has been installed a light
test shall be conducted at the connection seam.
2. Test and balance required on hood(3rd party)with copy supplied to Fire Marshal
at final test.
3. Hood final will be conducted during acceptance test on suppression system.