HomeMy WebLinkAbout08-8597 (2) ■ GENERAL NOTES: O 1 . EXHAUST FAN SHALL REMAIN ON UPON ACTIVATION () OF SYSTEM 2. FRESH AIR TO SHUT DOWN UPON ACTIVATION OF SYSTEM. Z 3. K CLASS EXTINGUISHER TO BE INSTALLED W LC) NO- MORE THAN 3OFT FROM HOOD. rn 4. LOCAL HORN STROBE TO SOUND UPON ACTIVATION OF SYSTEM Q E-- o z o 36° 5. ALL ELECTRICAL OUTLETS, APPLIANCES AND GAS VALVE Z) w w UNDER HOOD SHALL SHUTDOWN UPON SYSTEM ACTIVATION. rn 6 PULL STATION TO BE INSTALLED IN PATH OF EGRESS. z W z o 7. FIRE SYSTEM TO BE INSTALLED IN ACCORDANCE W Q N cw W W -o z WITH NFPA 17A, 96 AND MANUFACTURES SPECS. O W c M w 36 8. ALL PENETRATIONS TO HOOD FOR PIPE AND CONDUIT z LL. -J ° SHALL HAVE A LIQUID TIGHT SEAL OR CONTINUOUS 0 �-�- z = w TO WELD OR SHALL BE SEALED BY A LISTED DEVICE. r Q Cj.< 9. SYSTEM SHALL L INSTA E ONLY WITH LISTED EQUIPMENT THAT IS REFERENCED BY MANUFACTURER. Q 36° 10. BALLOON TEST SHALL BE DONE AFTER INSTALLATION z WITH LOCAL AUTHORITY HAVING JURISDICTION. IL 11 . EXHAUST FAN TO OPERATE IN NIGHT MODE Q 12. ALL PIPING MUST BE 3/8" SCHEDULE 40 BLACK IRON 12. TYPE 2 HEAT HOOD NO PLENUM & DUCT COVERAGE (I)z w 0 5 ► w cr U) w o a o N 1. (Y) 0O ANSUL m N uw _ _ AUTOMATIC 8102 N N GAS SHUT-OFF 3. OGL. z t N w e Lii SYSTEM 1 TANK 1 NOZZLE CHART VALVE w 5 I ANSUL R102 3 GALLON NOTICE: USING OF 11 FLOWS POSSIBLE 2 THIS DRAWING AND THE DATA THER48"� A. F. F. USED,ON SHALL O OR DISCLOSEDT E DUPLICATED, 0 OTHERS FOR PROCUREMENT OR MANUFACTURING APPLIANCE QTY NOZZLE TYPE FLOWS LENGTH/WIDTH PULL STATION PURPOSE, EXCEPT AS OTHERWISE CHAIN BROILER 8 1 N NOZZLE 8 43"X31 ' AUTHORIZED BY CONTRACT,WITHOUT THE WRITTEN PERMISSION OF OWNER. TOTAL FLOW PTS. 8 PAGE No. lofi GENERAL NOTES: 0 1 . EXHAUST FAN SHALL REMAIN ON UPON ACTIVATION ( ) OF SYSTEM 2. FRESH AIR TO SHUT DOWN UPON ACTIVATION OF SYSTEM. Z 3. K CLASS EXTINGUISHER TO BE INSTALLED W U, 0O NO MORE THAN 3OFT FROM HOOD. a) 4. LOCAL HORN STROBE TO SOUND UPON ACTIVATION OF SYSTEM 36 5. ALL ELECTRICAL OUTLETS, APPLIANCES AND GAS VALVE w ti ° UNDER HOOD SHALL SHUTDOWN UPON SYSTEM ACTIVATION. LJ 6 PULL STATION TO BE INSTALLED IN PATH OF EGRESS. z W w o 7. FIRE SYSTEM TO BE INSTALLED IN ACCORDANCE CL W W < N C" WITH NFPA 17A, 96 AND MANUFACTURES SPECS. 0 W a M w 36° 8. ALL PENETRATIONS TO HOOD FOR PIPE AND CONDUIT z L.t i LL SHALL HAVE A LIQUID TIGHT SEAL OR CONTINUOUS 0 v- z = w I'O WELD OR SHALL BE SEALED BY A LISTED DEVICE. F-- C��/N 9. SYSTEM SHALL BE INSTALLED WITH ONLY LISTED EQUIPMENT MFR THAT IS REFERENCED BY MANUFACTURER. 36° 10. BALLOON TEST SHALL BE DONE AFTER INSTALLATION z WITH LOCAL AUTHORITY HAVING JURISDICTION. -___ w 11 . EXHAUST FAN TO OPERATE IN NIGHT MODE 0 12. ALL PIPING MUST BE 3/8" SCHEDULE 40 BLACK IRON 12. TYPE 2 HEAT HOOD NO PLENUM & DUCT COVERAGE Cl) z 0 w w cu w o cn o _ U- m a N M M co ANSUL m U N AUTOMATIC R102 N o N GAS SHUT-OFF 3. OGL. z a U N VALVE w = i- o SYSTEM 1 TANK 1 NOZZLE CHART O = Q z ANSUL R102 3 GALLON __I NOTICE: USING 8 OF 11 FLOWS POSSIBLE THIS DRAWING AND THE DATA -�-- 48" A. F. F, THEREON SHALL NOT BE DUPLICATED, USED, OR DISCLOSED TO OTHERS FOR APPLIANCE QTY NOZZLE TYPE FLOWS LENGTH/WIDTH PROCUREMENT OR MANUFACTURING PULL STATION PURPOSE,EXCEPT AS OTHERWISE CHAIN BROILER 8 1 N NOZZLE 8 43"X 31 AUTHORIZED BY CONTRACT,WITHOUT THE WRITTEN PERMISSION OF OWNER. TOTAL FLOW PTS. 8 PAGE No. lofi Pee be advised the revteW of plans clitted is alwyre"WtoasssttheoonV ►nonpli�rl,ew.th GENERAL NOTES: O appl'�ablef�esafelyoodes. review is not ' f?r'^rj• 1 . EXHAUST FAN SHALL REMAIN ON UPON ACTIVATION to be a final approval of the vibmimd Pla.s. I+ t` U 10ensurelba' the p! ;e in OF SYSTEM contractor'ssateresPons!bY iicab NcPAco s a ,d 2. FRESH AIR TO SHUT DOWN UPON ACTIVATION OF I"— oomplee thF that cr exam r oII ,r SYSTEM. Z loc aal liai�rre, it ail ue "bintXlP 3. K CLASS EXTINGUISHER TO BE INSTALLED site mspectan re s LLE D W site00 the racWssol oneib ty,stthelrsc4eexpen: to NO MORE THAN 3OFT FROM HOOD. C `0 b&gftoareasirloernpilaticBaTlle City assumes n 4. LOCAL HORN STROBE TO SOUND UPON ACTIVATION OF SYSTEM G m 360 /N ponsibi�ity for the contWtor's f9pure to be in compliance NFPA Codes and Iocal ordinances. 5. A I--- o LL ELECTRICAL OUTLETS, APPLIANCES AND GAS VALVE UNDER HOOD SHALL SHUTDOWN UPON SYSTEM ACTIVATION. W �_ 0,, 6 PULL STATION TO BE INSTALLED IN PATH OF EGRESS. • • Q", z w5z 7. FIRE SYSTEM TO BE INSTALLED IN ACCORDANCE > w WITH NFPA 17A, 96 AND MANUFACTURES SPECS. W W M z 366 6� A 8. ALL PENETRATIONS TO HOOD FOR PIPE AND CONDUIT O SHALL HAVE A LIQUID TIGHT SEAL OR CONTINUOUS z - FTC WELD OR SHALL BE SEALED BY A LISTED DEVICE. O 9. SYSTEM SHALL BE INSTALLED WITH ONLY LISTED EQUIPMENT ~ m Q Q THAT IS REFERENCED BY MANUFACTURER. 360 �N 10. BALLOON TEST SHALL BE DONE AFTER INSTALLATION WITH LOCAL AUTHORITY HAVING JURISDICTION. z 11 . EXHAUST FAN TO OPERATE IN NIGHT MODE W 12. ALL PIPING MUST BE 3/8" SCHEDULE 40 BLACK IRON Q z O ► 1N ,yo w I �N ► 1N ��� 1 � ► 1N �► W 1N Ll! � ► 1N W o0 1N a L Z O c 1", '4S ► 1N ii 1N` }. ► :1N' N ANSUL ANSUL M 3U iM1T`2"ED PLAN(S)HAVE BEEN REVIEWED AU TO MAT I C R102 8102 BY ZEPHYRHILLs Fl MARSHAL'S OFFICE . Date: GAS SHUT .-OFF 3. o�L. 5 G L w 2 € N Reviewer; VALVE O = V Q z Cn ¢ 0 � NOTICE: HART SYSTEM, HANK _ -SYSTEM 1 N FLOWS PO ANSUL M NOZZLE CHART --_---- T ---- - THIS DRAWING AND THE DATA 1�TANK ' 1 NOZZLE C 8102 T� L R102 1. ,GALLON THEREON SHALL NOT BE DUPLICATED, usING POSSIBLE USING, _ of IfIFLO WS POSSIBLE _�_ __ — Q.8�� A. F. F. USED, OR DISCLOSED TO OTHERS FOR APPLIANCE QTY NOZZLE TYPE FLOWS LENGTWWIDTH m-uARE MIN HEIGHT MAX HEIGHT TOTAL FLOW PTS. APPLIANCE QTY NOZZLE TYPE FLOWS WITIV AREA LENGTH MIN HEIGHT MAXHEIGHTr TOTAL FLOW PTS. PROCUREMENT OR MANUFACTURING CHAIN BROILEF 6 1N NOZZLE 1 43" 31" N/A NIA 6 CHAIN BROILEF 6 1N NOZZLE 1 31" 43" WA 6 PULL STATION PURPOSE, EXCEPT AS OTHERWISE ,TOME AUTHORIZED BY CONTRACT,WITHOUT NOZZLE NOZZLE THE WRITTEN PERMISSION OF OWNER. PLENUM QTY NOZZLE TYPE FLOWS WITH/AREA LENGTH MIN HEIGHT MAX HEIGHT TOTAL FLOW PTS. NOZZLE 2 1N ; NOZZLE 1 4' 10' NIA WA 2 PLENUM QTY NOZZLE TYPE FLOWS WFTN/AREA LENGTH MIN HEIGHT MAX HEIGHT TOTAL FLOW PTS. PAGE No. DUCTS QTY NOZZLE TYPE FLOWS MAX SIDE PERIMETER TOTAL FLOW PTS. N/A NOZZLE 1 2W NOZZLE 2 16" 16" 32" 100" 2 DUCTS QTY NOZZLE TYPE FLOWS MAX SIDE PERIMETER TOTAL FLOW PTS. TANK TOTAL FLOW PTS.; 10 N/A NOZZLE O I /� - -- - - - - TANK TOTAL FLOW PTS.j 6