HomeMy WebLinkAbout09-9921 CITY OF ZEPHYRHILLS
5335 - 8TH STREET '
' (813)780 -0020 9921
FIRE SPRINKLER SYSTEM PERMIT
..w. 7 HST. > `1 E ..fig a ¢:. "A $'`i, e :I:'.a 1 - .. .a'
Permit Number: 9921 Address: 4241 SKY DIVE LN
Permit Type: FIRE SPRINKLER SYSTEM ZEPHYRHILLS, FL.
Class of Work: FIRE - SPRINKLER SYS Township: Range: Book:
Proposed Use: COMMERCIAL Lot(s): Block: Section:
Square Feet: Subdivision: CITY OF ZEPHYRHILLS
Est. Value: � ; arcel Number: 18- 26 -22- 0010 - 08600 -0000
Improv. Cost: 15,247.00 LL ':* w ` - �: p
Date Issued: 12/22/2009 t t!, i.L?et■ ` Name: CITY OF ZEPHYRHILLS
Total Fees: 830. ■ • Address: 4241 SKY DIVE LN
Amount Paid: 83 ►.0"" et_ ZEPHYRHILLS, FL. 33542
Date Paid: 3/02/28 0 Phone:
Work Desc: SPRINKLE ' SYSTRM INSTAL ' ION -FEE WAIVED
AAA - - - • • V N e' 1 s 0.00 - IN' - I ■• N F 155.00
VIEW FEES 150.00 FIRE PLAN REVIEW FEES 200.00
= - ECTION FEES 175.00 FIRE SPRINKLER SYS 50.00
ei05-e- a ' -2% ( (efire t - 3°
r i t
U S ‘c if ' 5 1(-\11\1 1 ' , \.5
IF I' . ti
/1
r iti ri, i l/
IV •r,_ , 3 —Z `\t ab IDA4
I = - RE
FIRE ACCEPTANCE Final
Chapter 633, Florida Statutes, authorizes the City to charge and collect user fees to pay for the costs of fire
prevention and protection related activities such as inspections, plan review, administrative fees, and other
costs related to the aforementioned.
Complete Plans, Specifications and Fee Must Accompany Application. Commencement of work without written approval of
the Fire Department's Fire Marshal or required permits or opening up for commercial activity without an approved final
inspection shall be charged double permit fee per day of operation or a minimum of $100.00, whichever is greater. All
work shall be performed in accordance with City Codes and Ordinances.
"WARNING TO OWNER: YOUR FAILURE TO RECORD A NOTICE OF
COMMENCEMENT MAY RESULT IN YOUR PAYING TWICE FOR
IMPROVEMENTS TO YOUR PROPERTY. IF YOU INTEND TO OBTAIN
FINANCING, CONSULT WITH YOUR LENDER OR AN ATTORNEY BEFORE
RECORDING YOUR NOTICE OF COMMENCEMENT."
4 _ it esF y-ApP k.
CONTRACTOR SIGNATURE ` ri 1 - 7 - IC R
PERMIT EXPIRES IN 6 MONTHS WITHOUT APPROVED INSPECTION
CALL FOR INSPECTION - 8 HOURS NOTICE REQUIRED
ZEPHYRHILLS FIRE RESCUE DEPT - Fire Marshal Office - 813- 780 -0041
CITY OF ZEPHYRHILLS
5335 - 8TH STREET
(813)780 -0020 9921
FIRE SPRINKLER SYSTEM PERMIT
O ,t • e „ , : . i m 7T , s . ,`e$ 'q''' - - :i 'ma ° 1 § s . S a s ,' °s i d a Z4
a"
Permit Number: 9921 Address: 4241 SKY DIVE LN
Permit Type: FIRE SPRINKLER SYSTEM ZEPHYRHILLS, FL.
Class of Work: FIRE - SPRINKLER SYS Township: Range: Book:
Proposed Use: COMMERCIAL Lot(s): Block: Section:
Square Feet: Subdivision: CITY OF ZEPHYRHILLS
Est. Value: Parcel Number: 18- 26 -22- 0010 - 08600 -0000
Improv. Cost: 15,247.00 '" 73
Date Issued: ` Name: CITY OF ZEPHYRHILLS
Total Fees: 405.001 Address: 4241 SKY DIVE LN
Amount Paid: 405. ZEPHYRHILLS, FL. 33542
Date Paid: 12/22/2009 Phone:
Work Desc: SPRINKLER INSTALLATION -FEE WAIVED
v 2A6;4, ..7=7:777717.:r!,' p ;V s 4 ate
AAA I • •N N FIR -` NKL - 100.00 I TI *NJ' 155.00
FIRE PLAN REVIEW FEES 150.00
... , ._ s;;., a a.• , . C , s "r *,._ ... , 3 .s. . `"5u'o ..,`.'' 3 �'ry'sb g•
IRE 1' TE
FIRE ACCEPTANCE Final
Chapter 633, Florida Statutes, authorizes the City to charge and collect user fees to pay for the costs of fire
prevention and protection related activities such as inspections, plan review, administrative fees, and other
costs related to the aforementioned.
Complete Plans, Specifications and Fee Must Accompany Application. Commencement of work without written approval of
the Fire Department's Fire Marshal or required permits or opening up for commercial activity without an approved final
inspection shall be charged double permit fee per day of operation or a minimum of $100.00, whichever is greater. All
work shall be performed in accordance with City Codes and Ordinances.
"WARNING TO OWNER: YOUR FAILURE TO RECORD A NOTICE OF
COMMENCEMENT MAY RESULT IN YOUR PAYING TWICE FOR
IMPROVEMENTS TO YOUR PROPERTY. IF YOU INTEND TO OBTAIN
FINANCING, CONSULT WITH YOUR LENDER OR AN ATTORNEY BEFORE
RE ORDING YOUR OTICE OF COMMENCEMENT."
4,„ i - _.rl* ji
CONTRACTOR SIGNATURE r g I _ IC R
PERMIT EXPIRES IN 6 MONTHS WITHOUT APPROVED INSPECTION
CALL FOR INSPECTION - 8 HOURS NOTICE REQUIRED
ZEPHYRHILLS FIRE RESCUE DEPT - Fire Marshal Office - 813- 780 -0041
7 b ,
813 - 780 -0020 City of Zephyrhills "Fire � ) 1 3' ;�- � X-813-780-0021 trqq 2/1
Permit Application ► O sv N&
•
Date Received _ ., 0 . �._
P Cwrtactfor Permit L' lf� i•S��/11 'I
Owner's Name I 46/7y OF ,..c1' L*ie/i /X -S I Owner's Phone Number l 1 1 1
Owners Address `
Fee Simple Titleholder Name Titleholder Titleholder Phone Number I ( 1 1
l
Fee Simple Titleholder Address
Lot #
! &
°��., -: � v*� ° .°sue . ,e � sa'mfsfi a :',''"� ... _.,. � o-. .. •.. >rkxa t. � ,r .��.� v.?. o sz;. ,.. .,s , _., �w .. , - .. 'S:a` ..M ,
._...,..d.,,,. .'�'S" =. ,( � . ,`� ..H�: Yn�e;t°;x ems. <. „ i:� :
Job Address . 1 �< y d) 1 V � � cti ZP°l �� r G, • I l `
1 J I Parcel # 1
Sub Division , . .. _
n Bio-Hazard Waste Storage - ANNUAL n Fumigation Tent
0 Comm Exhaust Kitchen Hood/Duct n Hazardous Material (Tier II or RQ Facility) ANNUAL
El Controlled Bum 0 Hood Installation
n Emergency Generator < 30 kw n tura
LP/NaI Gas - installation
n Emergency Generator> 30 kw 1 LP/Natural Gas - ANNUAL Sal:
n Are Protection Maintenance - ANNUAL n Places of Assembly- ANNUAL
z ,bens) ] puler
Sprinkler ED ❑ ❑ ❑ I Recreational Bum
Fire Alarm 0 ❑ ❑ ❑ I ( i I S pa re
Hood Cleaning in ❑ ❑ ❑ I I Eg'S System Installations
Hood Suppression n ❑ ❑ ❑ I I n Standpipes (Sprinkler Sys)
n Fire Alarm Installation n Torch Roofing/Tar Kettle
M Fire Pumps n Waste lire Storage ANNUAL
Fire Works
Flammable Application- ANNUAL ez2y 7 .15D I Valuation of Project
Fuel Tanks
IN Other:
. ' :8ta: ,.!s :..r •ew. z, ,.�iu ;sr « �±+ a.. : ;.n...,.a_.,<:;.44..K A� ..n- ;�hx¢, awm -r-- ..�.,e. - .-...r K..'... • w • _�':`° .,.* a sac' - u.;x c?..i.s,.a. ; :n v,x .,wr 'u �t- &:c . >%c? ,,. b�••5:n.'„ r.
Contractor ,, ,4 , Company ,. A F r€. - CinOAss 125-2
Signature C, VV Registered *AM Fee Current Ilro__
Add = ss ; 5 0 s - 6 t t. 0 ril'Fs:24 P u -f • — rp . 7L. 1 License # i 4 10 4 9-7 3 a a o 1 o o7I
ELECTRIC • Company
Signature Registered Y/ N I Fee Current 1 Y / N
Address I I License # I
PLUMBER Company
Signature Registered Y/ N I Fee Current I Y/ N i
Address I I License # I
MECHANICAL Company
Signature Registered Y/ N 1 Fee Current 1 Y/ N I
Address 1 I License #
OTHER • Company ��T•a��; ; • AJ vt
Signatu : Registered Y / N Fee Current Y / N ilA
Ad ress wG pY /� �Etju .r..s&I /i License # $' a I • • •7Q0
Direction "
All out application completely.
Owner & Contractor sign back of application, notarized (Or, copy of signed contract with owner)
If over $2500, a Notice of Commencement is required (Mechanical work over $5000)
Supply two (2) sets of drawings with applicable documentation
Allow 10 -14 days for review after submittal date. Parcel # - obtained from Property Tax Notice (http:/ /appraiser.pascogov.com)
. NOTICE OF:DEED RESTRICTIONS: The undersigned understands that this permit may be subject :to - "deed ":restrictions"
.. whiob may be more restrictive than County regulations. The undersigned assumes responsibility for-compliance•with any
applicable deed restrictions.
UNLICENSED CONTRACTORS AND - CONTRACTOR RESPONSIBILITIES: If the owner has hired - :a ~contractor or
contractors 19 undertake work, they may be required to be licensed in accordance with state and local regulations. If the
contractor is not licensed as required by law, both the owner and contractor may be cited for a misdemeanor violation
under state law. If the owner or intended contractor are uncertain as to what licensing requirements may :apply for the
intended work, they are advised to contact the Pasco County Building Inspection Division — Licensing Section at 727 -847-
8009. Furthermore, if the owner has hired . a contractor or contractors, he is advised to have the contractor(s) sign
portions of the "contractor Block" of this application for which they will be responsible. If you, as 'the owner sign as the
contractor, that may be an indication that he is not properly licensed and is not entitled - to permitting privileges in Pasco
County.
CONSTRUCTION LIEN LAW (Chapter713, Florida Statutes,as amended): If valuation of work is $2,500.00 or more, I
certify that I, the applicant, have been provided with a copy of the "Florida Construction Lien Law — Homeowner's
Protection Guide" prepared by the Florida Department of Agriculture and Consumer Affairs. If the applicant is someone
other than the "owner ", I certify that I have obtained a copy of the above described document and promise in good faith to
deliver it to the "owner" prior to commencement.
CONTRACTOR'S /OWNER'S AFFIDAVIT: I certify that all the information in this application is accurate and
that all work will be done in compliance with all applicable laws regulating construction, zoning and land
development. Application is hereby made to obtain a permit to do work and installation as indicated. I certify
that no work or installation has commenced prior to issuance of a permit and that all work will be performed to
meet standards of all laws regulating construction, County and City codes, zoning regulations, and land
development regulations in the jurisdiction. I also certify that I understand that the regulations of other
government agencies may apply to the intended work, and that it is my responsibility to identify what actions I
must take to be in compliance.
If 1 am the AGENT FOR'THE OWNER, I promise in good faith to inform the owner of the permitting conditions set forth in
this affidavit prior to commencing construction. I understand that a separate permit may be required for electrical work,
plumbing, signs, wells, pools, air conditioning, gas, or other installations not specifically included in the application. A
permit issued shall be construed to be a license to proceed with the work and not as authority to violate, cancel, alter, or
set aside any provisions of the technical codes, nor shall issuance of a permit prevent the Building Official from thereafter
requiring a correction of errors in plans, construction or violations of any codes. Every permit issued shall become invalid
unless the work authorized by such permit is commenced within six months of permit issuance, or if work authorized by
the permit is suspended or abandoned for a period of six (6) months after the time the work is commenced. An extension
may be requested, in writing, from the Building Official for a period not to exceed ninety (90) days and will demonstrate
justifiable cause for the extension. If work ceases for ninety (90) consecutive days, the job is considered abandoned.
WARNING TO OWNER: YOUR FAILURE TO RECORD A NOTICE OF COMMENCEMENT MAY RESULT IN YOUR
PAYING TWICE FOR IMPROVEMENTS TO YOUR PROPERTY. IF YOU INTEND TO OBTAIN FINANCING, CONSULT
WITH YOUR LENDER OR AN ATTORN BEFORE RECORDING Y• R NOTICE OF COMMENCEMENT.
FLORIDA JURAT (F.S. th7.03) / ,�f
—
OWNER OR AGENT i,_ • _AL .1 . . NT
- - - CORA
Syy bs��. and sworn to (or affirmed) b� me + i � Sub y . „ (or affirmed) before me this
,
IC> ' by I O L i -. W /� ) �` , by '1: A ■ _ ii
V s/are personally known to me or has/have produced Who is/are persona knov 0,to me or ha - ve produced
A as identification. iv , as identification.
i � ��, . / h._ ' , • J . / / Notary Public /h./ k' `ilex Notary Public
Co mission No. Commission No.
1, 1 A.)4a Ri eitiche4as A, Woe 'i r.�,h4ie�s
Name of Notary typed, printed or stamped • Name of Notary typed, prior stamped
UNDA RI r ' ` , 528
E '°.'1
Commission DD 808 DD 8 July
Expires July 24, 2012 -- Expires
BadedT mT,oyFaiiMIssan 8 7919 ' ;t`;+, •' Bo
Expire
Zephyrhills Fire Rescue
6907 Dairy Road, Zephyrhills, FL 33542
Fire Marshal Bus (81 3) 780 -0041
Kerry Barnett Fax (813) 780 -0044
E-mail: k.barnett@fire.zephyrhi I ls. fl .us
Plan Review #: 09 -110
Project: Fire Sprinkler Installation
Number of Pages: 1
December 21, 2009
I have received and reviewed the plans for the installation of a fire sprinkler system
located at 4241 Sky Dive Lane and will allow the project to move forward. Please note
that this review does not eliminate any further requirements as the project continues
moving forward. By receiving permit, contractor acknowledges to comply with the items
listed below. Should anyone have any questions, please do not hesitate to contact the Fire
Marshal's office.
1. Provide license to show company is certified to install the underground.
2. Provide spec /cut sheets on all (sprinkler heads, DCVA, FDC, piping, valves,
etc...) this was noted on the previous review.
3. Tamper switches required on double backflow assembly.
4. FDC Sign to be posted at FDC location. Sign to be minimum 6' high with 6"
red reflective letters "FDC" on white background.
5. Thrust blocking shall be used on underground. Blocking shall be formed in a
wedge style.
6. Riser shall not be obstructed. Owner may want to install a chain link fence
around riser to prevent obstruction and /or tampering.
NOTE: #1 and #2 are required prior to work being started. Sheets can be faxed to number
at top of this comment sheet.
2
Inspections Required:
I. Underground Flush (Contractor shall provide all equipment to conduct flush
in accordance to the code. Flush shall be conducted through a large diameter
hose with a drain bag at the end. The bag will allow the water to be checked
for sediment.
2. Underground Pressure Test
3. Pressure test on sprinkler system
4. Acceptance Test (in conjunction w /fire alarm system)
A
40,yiltfai
' / EETT, FIRE MARSHAL
** *Please be advised this review of plans submitted is a cursory review to assist the contractor in
compliance with applicable fire safety codes. This review is not intended to be a final approval of the
submitted plans. It is the contractor's sole responsibility to ensure that the plans are in complete compliance
with all applicable NFPA codes and local ordinances. In the event that further examination or site
inspection reveals areas of non - compliance, it shall be the contractor's sole responsibility, at their sole
expense to bring those areas in compliance. The City assumes no responsibility for the contractor's failure
to be in compliance with all applicable NFPA codes and local ordinances.
ZEPHYRHILLS FIRE DEPARTMENT
6907 Dairy Road, Zephyrhills, FL 33542
Fire Chief Keith Williams Bus (813)780 -0041 Fax (813)780 -0044
FIRE SERVICE USER FEES •
Occupancy No.: ,
Plan No.: 1 . - //d t Contractor: ,,, 14,/e4G/7 /!iz/�G 'j
Business Name: S // Y 1il/e C -r Billing Address: 2 2 Sco�c . .
Business Address: 4 � � 1Y! F�s
,I/ ; /, � � - 6°4
Business Phone No.: Billing Phone No.:
Business Fax No.: Billing Fax No.:
Contact: Contact:
PLAN REVIEW FEES _ INSPECTION FEES PERMIT FEE FALSE ALARM FEE
Site Plan N/C
— Annual N/C ,�ISprinkler 11 1st Alarm N/C
Muni - Family /Commercial .06 sf — 1st Re- inspection N/C f Standpipes -�: � ■ 2nd Alarm N/C
(Minimum Charge $25.00 _ 2nd Re- inspection 5100 V Fire Pump 550 1 3rd Alarm N/C
fl Plan Revisions DBL _ 3rd Re- inspection $250 , Hoods 550 11 4th Alarm $100
4th Re- Inspection $500 . Fire Alarm $50 . 5th Alarm $150
SPRINKLER SYSTEMS (Business closed until 1 LP Gas 550 1 6th Alarm $200
0 - 25 Heads $50 violations corrected) , Natural Gas $5D . NON COMPLIANCE $15D
6 plus Heads DD SPRINKLER SYSTEM 111 Fuel Tanks- per tank $50
STANDPIPE SYS r,d, Hydro Undergrounds 1 , Sparklers
5100
Per Riser
550 Hydrostatic Test rsystem , Fire Works $500
FIRE PUMP lAcceptance Test OP per system , Camp Fire 525
0 Per Pump 5100 11 Hydrant Flow I*• , Controlled Bum 5100
FIRE ALARM SYSTEM , Hood/Duct $50
—
_ 0 - 25 Devices $50 _ FIRE ALARM SYSTEM "Place of Assembly 550 Annual
26 plus Devices $100 — System Acceptance 550 , Fire Protection $25
SUPPRESSION SYSTEMS _ Recall Acceptance $50 11 Flammable Application 550 Annual
Wet
CO2
Other
$50 _ OTHER ,Waste Tire Storage 550 Annual
Dry 550 _ Fire Wall /Smoke Wall $15 per wall , Generator < KW $100
$5D LP Gas
$50 $25 pertank , Generator KW 150
_Natural Gas 525 per system , Bio-Hazard Waste $100 Annual
KITCHEN EXHAU
–.– $25
Fumigation Tenting $50
Hood/Ducts $50 _ Tent 105(10' or greater 515 per tent . Torch Pot/Applied 550
OTHER _ Fire Pump $45 11 Haz. Materials .1 annual
_ LP Installation per tank $50 ` Fire Suppression $30 04l4(
— Fuel Tank Installation $50 — System Acceptance —
(Per Tank) $50 _ Exhaust Hood/Duct $30
0 Natural Gas installation $50 _ Re- inspection DBL
(Per System) (other than annual) _
0 Spray Booth 550 fl Inspection scheduled DBL
and cancelled less than _
_ 24 hours
_ Construction Insp. N/C
— Emergency Vehicle Aci $50 _ ,,.4 f FALSE ALARM PLANS TOTAL ri% INSPECTION TOTAL PERMIT TOTAL /N .,"" TOTAL
GRAND TOTAL
Comments: //
Date: f 2 /
InsA ctor: / _ ., v'
.� :krmfb Rif ��
eat
City of Zephyrhills: i 10‘,'"'
Building Department
Phone: (813)- 780 -0020
Fax: (813)- 780 -0021
TO: donna FROM: jackie
k FAX #: 813 - 882 -3703 FAX #:
DATE: 12 -11 -09 # OF PAGES including cover sheet: 3
i €
1 #
1
€
#
MESSAGE: donna per our phone conversation I am faxing over to you the rejection
comment sheet given by kerry the fire marshall.
E #
Jackie
i €
r #
€ 1
7 #
9 €
f 1
€ €
€ #
1 1
E #
3 1
1 1
E #
1 €
# #
E 1
€ 1
# €
€ 1
E E
E #
€ E
# E
P. 01 /0
TRANSACTION REPORT
DEC /11 /2008 /THU 00:19 PM
FAX(TX)
# DATE START T. RECEIVER COM.TIME PAGE TYPE /NOTE FILE
01 DEC /11 00:18PM 818138823703 0:01:08 3 OK G3 9800
City of.Zephyrhills: i r,
Buildin g Department
b ..,,_: w,_, :.........:......n_
Phone: (813)- 780 -0020 :. =. >.
•
Fax: (813)- 780 -0021
TO: donna FROM: jackie
• FAX #: 813- 882 -3703 FAX #:
DATE:12 -11 -09 # OF PAGES including cover sheet: 3
MESSAGE: donna per our phone conversation I am faxing over to you the rejection
comment sheet.given by kerry the fire marshall.
Jackie
•
Zephyrhills Fire Rescue
6907 Dairy Road, Zephyrhills, FL 33542
Fire l4arshal Bus (813) 780 -0041
Kerry Brett Fax (813) 780 -0044
E -mail: kbarnettna
Plan Review #: 10 -014
Project: Fire Sprinter Revision
Number of Pages: 1 plus Packet
Itch 1, 2010
I have received and reviewed the plans for the fire sprinkler installation located at 4241
Sky Dive Lane and will allow the project to move forward. Please note that this review
does not eliminate any further requirements as the project continues moving forward. By
receiving permit, contractor acknowledges to comply with the items listed below. Should
anyone have any questions, please do not hesitate to contact the Fire Marshal's office.
1. Installation shall be in accordance to NFPA 13, latest edition.
2. Underground shall be flushed and witnessed by Fire Marshal.
3. Underground shall have thrust blocking.
4. Tampers are required on double backflow preventor.
5. 5" Storz shall be a 30 degree turn down, drawing shows it straight.
6. An FDC sign shall be mounted on a post by FDC. Lettering shall be 6" red
reflective letters on white background.
7. Cut sheets /details /spec sheets required on double backflow, underground
pipe and connections, valves, tampers, sprinkler heads, etc.. This shall be
provided before the first inspection is completed.
Fiona Required:
1. Underground Flush
2. Underground Pressure Test
3. Sprinkler Pressure Test
4. e Test in conjunction w/Fire Alarm
49
KERRY • ' TT, FIRE MARSHAL
** *Please be advised this review of plans submitted is a cursory review to assist the contractor in
compliance with applicable fire safety codes. This review is not intended to be a final approval of the
submitted plans. It is the contractor's sole responsibility to ensure that the plans are in complete compliance
with all applicable NFPA codes and local ordinances. In the event that further examination or site
inspection reveals areas of non - compliance, it shall be the contractor's sole responsibility, at their sole
expense to bring those areas in compliance. The City assumes no responsibility for the contractor's failure
to be in compliance with all applicable NFPA codes and local ordinances.
ZEPHYRHILLS FIRE DEPARTMENT
6907 Dairy Road, Zephyrhills, FL 33542
Fire Chief Keith Williams Bus (813)780 -0041 Fax (813)780 -0044
FIRE SERVICE.USER FEES
Occupancy No.:
Plan No.: /D o/9 Contractor: AAA Fyp f/e
Business Name: S'XY /)r1 £ Billing Address: 8'S o 7 , Su i nr e.S�
Business Address: t i24// , '7 , 4<, -- 2..A...) j p P2 334341
Business Phone No.: Billing Phone No.:
Business Fax No.: Billing Fax No.:
Contact: Contact:
PLAN REVIEW FEES _ INSPECTION FEES PERMIT FEE _ FALSE ALARM FEE
_ Site Plan N/C _ Annual N/C I7 Sprinkler $50 _ 1st Alarm N/C
Multi- Family /Commercial .06 sf — 1st Re- inspection N/C Il Standpipes $50 2nd Alarm N/C
(Minimum Charge $25.00 _ 2nd Re- inspection $100 , Fire Pump $50 3rd Alarm N/C
—
Plan . ns DBL 3rd Re- inspection $250 . Hoods $50 _ 4th Alarm $100
4th Re- Inspection $500 , Fire Alarm $50 _ 5th Alarm $150
SPRINKLER SYSTEMS (Business closed until 1 LP Gas $50 _ 6th Alarm $200
0 - 25 Heads $50 violations corrected) II Natural Gas $50 NON COMPUANCE $150
26 plus Heads SPRINKLER SYSTEMS , Fuel Tanks - per tank $50
STANDPIPE SYSTEM Hydro Undergrounds $45 , Sparklers $100
El Per Riser $50 Hydrostatic Test $65 per system , Fire Works $500
FIRE PUMP Acceptance Test $45 per system , Camp Fire $25
El Per Pump $100 Hydrant Flow $75 , Controlled Bum $100
FIRE ALARM SYSTEM , Hood/Duct $50
0 - 25 Devices $50 _ FIRE ALARM SYSTEM 11 Place of Assembly $50 Annual
26 plus Devices $100 — System Acceptance $50 ' I Fire Protection $25
SUPPRESSION SYSTEMS _ Recall Acceptance $50 , Flammable Application $50 Annual
Wet $50 _ OTHER , Waste Tire Storage $50 Annual
Dry $50 _ Fire WalUSmoke Wall $15 per wan , Generator < KW $100
CO2 $50
— LP Gas $25 per tank , Generator >30 KW 150
O ther $50 _ Natural Gas $25 per ■ Bio-Hazard Waste 5100 Annual
KITCHEN EXHAUST _ 1 Fumigation Tenting $50
El Hood/Ducts $50 _ Tent 10'x10 or greater $15 pertent , Torch Pot/Applied $50
OTHER _ Fire Pump 545 ! Haz. Materials i p $100 Annual
LP Installation per tank $50 _ Fire Suppression $30 ►.Q 1) 11Xyrb 7 50
Fuel Tank Installation $50 _ System Acceptance
(Per Tank) $50 Exhaust Hood/Duct $30
El Natural Gas Installation $50 Re- inspection DBL
(Per System) (other than annual) _
0 Spray Booth $50 fl Inspection scheduled DBL _
and cancelled less than
—
_ 24 hours
Construction Insp. N/C
_ Emergency Vehicle Ao $50 FALSE ALARM
PLANS TOTAL INSPECTION TOTAL r h — PERMIT TOTAL ) TOTAL
GRAND TOTAL 1 L 1 - 7 -c
•
Comments:
- ..h
•
.
Date: 3 1 t \ 10
Ins�ctor. ht N� th — r
Sky Dive City Drawing Date: 2/17/10 14 :30
HYDRAULIC DESIGN INFORMATION SHEET Ati . f
hr
Job Name: Sky Dive City 4
Location: 4241 Sky Dive Lane
Zephyrhills, FL
Drawing Date: Remote Area Number: 2
Contractor: AAA FPS, Inc. Telephone:813.886.8869
8502 Sunstate Street
Tampa, Florida 33634
Designer: RTS
Calculated By:SprinkCAD
www.sprinkcad.com
451 N. Cannon Ave.
Lansdale, PA 19446
Construction: Wood Occupancy:Light
Reviewing Authorities:Fire Marshal
SYSTEM DESIGN
Code:NFPA 13 Hazard:Light System Type:WET
Area of Sprinkler Oper. 400 sq ftl Sprinkler or Nozzle
Density (gpm /sq ft) 0.100 1 Make: TYCO
Area per Sprinkler 330.0 sq ftl Model: TY -FRB
Hose Allowance Inside 0 gpm 1 K- Factor: 8.00
Hose Allowance Outside 250 gpm 1 Temperature Rating: 155
CALCULATION SUMMARY 2 Flowing Outlets
gpm Required: 316.0 psi Required: 29.6 @ City Supply
WATER SUPPLY
Water Flow Test 1 Pump Data 1
Date of Test 11/20/2009 1 Rated Capacity 0 gpm 1
Static Pressure 77.0 psi 1 Rated Pressure 0.0 psi 1
Residual Pres 61.0 psi 1 Elevation 0 1
At a Flow of 1240 gpm 1 Make: 1
Elevation 2'0" 1 Model: 1
Location: 1000 ft South of Site
Source of Information: AAA Fire Protection Services, In
SYSTEM VOLUME 94 Gallons
Notes: Covered Concessions Area Proof lj
1
:.00u o °
ai 000 to
a
P.
a
0 o o - - - - -- —
a 1
c
O
LL
0
_ E 4
to a
a0)
00
, 0aio
—
dj
as
E'.2 $2
7 cd cu
CL CC CC ,
0
0
F00
�
0
a) a) 7
o��
2.0
1 I F
EE. - 1 -- I -
u) gain 1 a1 I I I I CO
a0) o)a 1 0 _
in I j I _ 1 {
a) N 1 , ,
Q ' , 1 , ...
O t%= 0 > I j
a)>
L� EE a W 1
CC a cn c� c4 = !
1 1
1t
u) u) i
000 a) I
N 1 1 N CA .. E. .
y O9 T + - 1
-
N N cn
0
E N 1 1 0I -ea r O
,- O - O O
0
...= 65 2
i
0
G h
J O
N
a) -I ..
> L m - Ne 00 ci) �, a
.0 > a E N
. r
O N a) a) 4
-3 CA.:1-NCC -- — - •
1 T
0
N p co co �O O
N
Sky Dive City Drawing Date: 2/17/10 14:30
HYDRAULIC CALCULATION DETAILS
HYDRAULIC FLOW LOSS
QTY DESCRIPTION LENGTH C ID gpm psi TOTALS
Hydr Ref W Required at Hyd Area 2 66 19.4 psi
1 4" Grvd 90 Ell 10' 120 4.026 66 0.0
1 Pipe 4" 10x21 10' 120 3.260 66 0.0
1 4" Grvd Shotgun Valve "90" 21' 120 4.026 66 0.0
1 4" Flngd Butterfly Valve "A" 12' 120 4.026 66 0.0
Elevation Change 10'0" 4.3
Hydr Ref R1 Required at Base of Riser 66 23.9 psi
1 Pipe 6" DIx18 Cl 350 120' 140 6.338 66 0.0
3 6" MJ 90 Ell 42' 120 6.065 66 0.0
1 6" Flngd Back Flow Valve Watts "709 CHART LOSS 66 3.2
1 Pipe 6" DIx18 Cl 350 40' 140 6.338 66 0.0
1 6 "Gate Valve Kennedy "4071" PIV 3' 120 6.065 66 0.0
1 6" MJ Tee 30' 120 6.065 66 0.0
Fixed Flow Outside Hose Stream 250 gpm
1 Pipe 6" DIx18 Cl 350 1000' 140 6.338 316 2.5
Hydr Ref R2 Required at City Supply 316 29.6 psi
Water Source 77.9 psi static, 61.9 psi residual @ 1240 gpm 316 gpm 76.6 psi
SAFETY PRESSURE 47.0 psi
NOTE: Water Source has been adjusted to include a change of elevation of
2'0" flow test to point of connection
Available Pressure of 76.6 psi Exceeds Required Pressure of 29.6 psi
This is a safety margin of 47.0 psi or 61 % of Supply
Maximum Water Velocity is 5.3 fps
Sky Dive City Drawing Date: 2/17/10 14:30
Page 3
FITTING NAME TABLE
ABBREV. NAME
C Coupling
E 90' Standard Elbow
F 45' Elbow
S Straight Flow Thru Tee
T 90' Flow Thru Tee
✓ Valve
LEGEND
HYD REF Hydraulic reference. Refer to accompanying flow diagram.
K FACTOR Flow factor for open head or path where Flow (gpm) = K x - \/P
Qa Flow added or subtracted
Qt Total flow
DIA Actual internal diameter of pipe
C Hazen Williams pipe roughness factor
Pf /ft Friction loss per foot of pipe
PIPE Length of pipe
FTNG'S Number of fittings. See table above.
TOTAL Total length (PIPE + FTNG'S)
Pt Total pressure (psi) at fitting
Pe Pressure due to change in elevation
where Pe = 0.433 x change in elevation
Pf Friction loss (psi) to fitting
where Pf = 1 x 4.52 x (Q /C) ^1.85 / ID ^4.87
Pv Velocity pressure (psi)
where Pv = 0.001123 x Q ^2 /ID ^4
Pn Normal pressure (psi), where Pn = Pt - Pv
NOTES:
- Pressures are balanced to 0.01 psi. Pressures are listed to
0.1 psi. Addition may vary by 0.1 psi due to accumulation of
round off.
- Calculations conform to NFPA 13.
- Velocity Pressures are not considered in these Calculations
Sky Dive City Drawing Date: 2/17/10 14:30
Page 4
NODE ELEVATION SPRINKLER PRESSURE ACTUAL MINIMUM ACTUAL
NUMBER K- FACTOR FLOW FLOW DENSITY
(FT) (GPM /(PSI ^1/2)) (PSI) (GPM) (GPM) (GPM /SQ.FT)
50 10.00 8.00 17.0 33.0 33.0 0.10
51 10.00 8.00 17.0 33.0 33.0 0.10
60 10.00 17.1
61 10.00 17.1
B1 10.24 19.4
B2 10.24 19.4
W 10.24 19.4
Max velocity of 5.25 occurs in the pipe from 61 TO 51
Sky Dive City Drawing Date: 2/17/10 14:30
Tyco Fire Products Page 5
HYD. Qa DIA. FITTING PIPE Pt Pt
REF "C" TYPES FTNG'S Pe Pv * * * * * ** NOTES * * * * * **
POINT Qt Pf /ft TOTAL Pf Pn
PATH 1 FROM HYDRAULIC REFERENCE 50 TO W (PRIMARY PATH)
33.00 1.610 1.13 17.0 17.0 K = 8.00
50 C =120 0.00 0.0 0.0
33.00 0.041 1.13 0.0 17.0 Vel = 5.25
1.682 3E 47.80 17.1 17.1
60 C =120 1T 24.75 -0.1 0.0
33.00 0.033 72.55 2.4 17.1 Vel = 4.81
3.260 10.03 19.4 19.4
B1 C =120 0.00 0.0 0.0
33.00 0.001 10.03 0.0 19.4 Vel = 1.28
33.02 3.260 1E 4.70 19.4 19.4
B2 C =120 9.41 0.0 0.0 See PATH 2
66.02 0.005 14.11 0.1 19.4 Vel = 2.56
W 66.02 19.4 K = 14.98
PATH 2 FROM HYDRAULIC REFERENCE 51 TO B2
33.02 1.610 1.13 17.0 17.0 K = 8.00
51 C =120 0.00 0.0 0.0
33.02 0.041 1.13 0.0 17.0 Vel = 5.25
1.682 3E 47.56 17.1 17.1
61 C =120 1T 24.75 -0.1 0.0
33.02 0.033 72.31 2.4 17.1 Vel = 4.81
B2 33.02 19.4 K = 7.50
UNITS - DIAMETER (INCH) LENGTH (FOOT) FLOW (GPM) PRESSURE (PSI)
❑ N /
I
0 +10 61 +10
- ❑ 0 -11 2
1 -9 2 -10 N �2) EC HSW PROVIDED FOR PROTECTION 1 N 5
I ( OF COVERED WOOD DECK ATTACHED
1 -21 1 Q I I �, �, ❑ o N
SPECTOR'S TEST VALVE TO BUILDING - -
NCO
N CO N C.O N c 0 N CO CO N CD CO O O
5 r
�O o 3 CD 3 CD I 3 ° 3 12 ° 12
❑ ❑ ❑ ❑ ❑
� 9 1 NCO E _ �o I I _ I r❑
I [ : 4]
_
2 � W
4i
r , lO N o
CN
12 12 12 12 z
12 12
z� O
* I
12
I,
4' - 10' 4' - 10" — 5' -0 1/8' J 5' -0 1/8' -- --I- -- 4' -11 b „ -0 1/8' - - -- 4' -11 1 /2' 5' -�1 I 4' -4' CF) 5'-0 1/8'
Li
I
m N N m C'4 ID m N M m N m N m N h w < o
a
N N N w I .- > _
j O wo w
OVERHEAD DOOR COILS AND _
DOES NOT OBSTRUCT FLOOR °
2 6❑ I I SPACE 1 1 1 1 m
8'C” TALL WALL 3RACED -- - °
5' -6 1/2
N N I 1 N I N I N I N I
I I
�
Ln � Ln I � LC) r- Ln I r- L0 Ln
� I —
1 N
C. r
I � I
O Q o r � o o r o r• I o �- o � �
12 12 12 12 1 _12 1 2 O 12 J O 12 N o0 12 I 12
W � J � J - J - J I I I I � M J
a- a
O j
Q)
o N O
o N O
o 0
0 0
0
o o
o
N O N
o� N
NEW HYDRANT AND NEW STORZ CONNECTION /B
DEVICE SHALL BE LOCATED WITHIN 50' OF ONE
ANOTHER (GC TO COORDINATE LOCATIONS).
❑
O 0
1
s-- N
�- N
(
I
o
o
M
Q)
l/ 1
0
X r
N
N
N
N
I N
N
-- I N
N
( N
iC) N
-
r
.-
r
r
D
-
�� r
.--
•
L,
U
r-
.-
�-
0
O
�
U
�_
I
T
I
T
T I
I
Z
�
OVERHEAD DOOR COILS AND
I
a
DOES NOT OBSTRUCT FLOOR
o
SPACE
I
I
� J _ _ I _ _ I _
Z 1 1 0 N I Q w , N N N N N c N N N N N
W F ca5 L I cV v Z Q N N Q N N N N Q N N Q N N Q N N ( Q N N Q N N ( Q N N Q N N
a Y to Q `_ I I I I O' " I
Z W , p, �- N r- N r- N c- N I N N N c- N 0 U
4 M �J
c7S 11
V Q o m Q I Z_ � O
o I W
W� m L S
0
'V 0 1
o a � � X 12 J � � X 12 J L 12 J 12 _12 ` 112 X 12 12 J 12 12 J oW Z' 0 i x o I I I - -- -
In X Ix
LU
Li ❑ Al '� �`� AZ '� o�� A 3 �` ��' '` ��' I r�Ais o (AGE AREA '` �� `` �� `` o�� I r B '` �� ❑2
� N N O/ \ \ N NI `\' O N , N 0 - - - - N `� N `v O�
Q rn CV L J sue- cV r - Cv J - �- N / ❑ N r N N � i1' -9 3/4"
3 a ° 3 ° ° ° ° ° ° ° ° 3 3 ° ° 0 3 3 �° 3 C° 3 3 3°
0 -4 9 -8 9 -10 1- 8- 0 _ 09 1 2 -2 ' 7 -10 9- 1 2 3 - 6 - 10 1 2 9 - 4 - 9 1 2 5 - 2 - °
A6 I A5 ❑ =A2 ..
..
-- -�
. .
-- — ' ELL i — -- '
_ „ 4x3" GRWD REDUCING COUPLING . SYSTEM
` - -
STAGE - 16 HIGH RAISED FLOOR CONSTRUCTED OF (>i -x 0) 4 FIRE RISER W \
NON COMBUSTIBLE METAL STUDS AND FIRE RATED
4" SWITCH
PLYWOOD AS DECKING. NO COMBUSTIBLE MATERIAL WILL ( R NG
W BY O THERS) � to Q 1•
BE STORED WITHIN THIS CONCEALED SPACE. NO SPRK'S 6 HEAD SPRINKLER
5 PER NFPA 13. 8.15.16. ❑ CABINET WITH HEADS FROM BRANCH LINE
a
J
Q)
-- PRPOSED 24' WIDE
1
GRAVEL DRIVEWAY
NEW EIRE HYDRANT P20MDFD .BY an-a-,
ZEPHRYHILLS UTILITIES DEPT..
NEW HYDRANT AND NEW STORZ CONNECTION /B
DEVICE SHALL BE LOCATED WITHIN 50' OF ONE
ANOTHER (GC TO COORDINATE LOCATIONS).
F_
I
I
V Al
AAA FPS, Inc WORK TO START AFTER GATE VALVE
a WITH UG TO DDVC AND UG TO BLDG SERVICE RISER
2 6' PIPE BOLLARDS BY OTHERS
4' CHECK VA WITH 5" 30 DEG STORZ FDC
ON DISCHARGE OF BACKFLOW DEVICE.
UG SHALL BE DR -14 FOR FD PUMPER
PRESSURES AND BLDG CONTROL VALVE
O SHALL BE DELETED FROM RISER.
- -
- - - - -- -� � --- --- --------------------------------
/,�
15'0 I � ` `
1 5' STORZ FDC MOVED TO
120' 6' DR 14 UG SUPPLY DISCHARGE OF BACKFLOW DEVICE
FROM BACKFLOW DEVICE 1
L--------------
6' WATER MAIN EXTENSION 5' BACKFLOW DEVICE PER AHJ STANDARDS. 4' RISER LOCATION
NEW HYDRANT, NEW TAP BACKFLOW DEVICE AND STORZ CONNECTION
AND NEW GATE VALVE TO BE LOCATED WATHIN 15' OF WESTERN EDGE OF
(BY CITY OF ZEPHRYHILLS THE EXST PAVED ROAD SURFACE.❑ Z
UTILITES DEPARTMENT) i
a / WATER FLOW SUMMARY: /
a TEST DATE: 11 -20 -2009
PERFORMED BY. AAA FPS, INC. /
` LOCATION: 1,000 FT FROM SITE /
I STATIC = 62 PSI
RESIDUAL = 40 PSI
FLOW = 1060 GPM /
REDUCED SITE PLAN
NO SCALE /
UNDERGROUND FIRE PROTECTION PIPING SHOWN ENTIRELY FOR THE PURPOSE
11. BACKFLOW PREVENTOR PER AHJ STANDARDS
D
[BACKFLOW PREVENTOR DETAIL
NIO SCALE
SMOOTH BORE CORROSION
RESISTANT OUTLET GIVING
FLOW EQUIVALENT TO ONE
SPRINKLER.
INSPECTOR'S TEST (WET P IPE
NO SCALE
I
STORZ FDC
:CK VALVE
42 [UPRIGHT
AND WRENCHES
ALARM BELL "
(WIRING BY OTHERS)
SUBMITYED PLAN(S) HAVE BEEN REVIEWED -- 5" STORZQ
13Y ZEPH E YRHILLS - I: MARSHAL'S OFFICE - DELETED -
Date: 4 CHECK VALVE EXTERIOR WALL
SHOTGUN RISER CHECK 1" BALL VALVE SET
VALVE WITH (2 ) Q2
AT 5' -O" A.F.F.
't� viewer: - PRESSURE GAUGES AND -DELETED -
e/ DRAIN ASSEMBLY
• GR. BUTTERFLY VALVE
6'x4' REDUCING
-DELETED -
� Q '
ease be advised this review of plans submitted 13
1ti COUPLING GALVANIZED NIPPLE
�t
(IQry r$YIeW t0 assist the contractor I }� BASE OF RISER o GALVANIZED 45' ELL
licahle f ire sa fety codes. This review is not intended .
app
rovai of tlW2 Submitted plans. It ; the •
to be a final app pla ns are In 6" UNDERGROUND. SEE
cconvactoes sole responsibility to.eAVICe s, l REDUCED SITE PLAN FOR
W'Aplete compliance with all a pp licable NAPA co des and CONTINUATION.
local ordinances. In the event that further xam t shalt f
site inspection reveals areas of nor comp 6 PRESSURE RATED
the contract Of S sole responsibility, at q4s Sole expense t4 A UNDERGROUND SUUPLY RISER DETAIL z�
bring those areas in compliance. The Cray assumes no
NO SCALE
responsibility for the contractor's failure to be in com
1�jjh all applicable RFPA Codes and 10" n CHECK VALVE AND STORZ CONNECTION
DISCHARGE SIDE OF BACKFLOW DEVICE
BEAM CLAMP
STEEL A.T.ROD
0
I HANGER RING
HANGER DETAIL
NO SCALE
0
C� 4.) r N
� CID
w
w E 4;
1:22"���
w �
0
0
Lei
a�
N
r
a
014-
� z
o 0
m m m
N
J
x
W
N
O U
O
U
y 1=
Z
O a
� o m �
CL
w O
0 C U
w
0.; � Y a
0
EL °w
J
Q Z �
Z
o a
E
o 0 3
g 0
aa<
H M D 00
Q � N
GENERAL NOTES
1, AAA FIRE PROTECTION SERVICES INC (AAA FPS, INC.) SCOPE OF WORK
STARTS AT DISCHARGE 6' UG GATE VALVE TO BLDG RISER. UG WATER
MAIN, TAPPING SLEEVE AND VALVE BY OTHERS.
2. ALL WORK PERFORMED SHALL COMPLY WITH NFPA 13, 24 AND 25
STANDARDS, LOCAL AHJ REQUIREMENTS, AND STATE FIRE MARSHAL
REQUIREMENTS.
3. AAA FPS, INC. SCOPE OF WORK DOES NOT INCLUDE ANY WIRING OF
DEVICES OR PAINTING OF PIPE, ETC.
4. ALL SPRINKLERS SHALL BE STANDARD COVERAGE (QUICK RESPONSE)
ORDINARY TEMPERATURE (UNLESS OTHERWISE NOTED).
5. SPRINKLERS TO BE PROVIDED BELOW ALL EXPOSED DUCT, SUSPENDED
EQUIPMENT AND MEZZANINES EXCEEDING 48" IN WDTH.
6. ALL PENETRATIONS IN FIRE /SMOKE WALLS TO BE PROVIDED WITH A WITH
A U.L. LISTED FIRE STOP ASSEMBLY.
7. UNDERGROUND PIPING SHALL BE FLUSHED PRIOR TO SPRINKLER SYSTEM
BEING TIED -IN.
B. ENTIRE SYSTEM TO BE FLUSHED AND HYDRAULICALLY TESTED IN
ACCORDANCE WITH NFPA -13.
9. SPRINKLER SYSTEM HAS BEEN DESIGNED NTH A MAXIMUM WORKING
PRESSURE OF 175 PSI.
10. ENTIRE SPRINKLER SYSTEM TO BE INSTALLED IN A MANNER THAT THE
ENTIRE SYSTEM CAN BE DRAINED. WHERE REQUIRED AUXILIARY DRAINS
WILL BE PROVIDED.
OCCUPANCY CLASSIFICATIONS
THE FACILITY IS PROTECTED BY A WET -PIPE FIRE SPRINKLER SYSTEM,
BASED ON THE FOLLOWING OCCUPANCIES AND DESIGN CRITERIA:
OFFICES AND LIKE SPACES: LIGHT HAZARD OCCUPANCY, 0.10 GPM /SQFT
DENSITY, 225 SOFT MAX SPRINKLER SPACING, 100 GPM COMBINED HOSE
STREAM DEMAND.
MECHANICAL, KITCHEN, JANITOR, AND LIKE SPACES: ORDINARY HAZARD
(GROUP 1) OCCUPANCY, 0.15 GPM /SOFT DENSITY, 130 SOFT MAX SPRINKLER
SPACING, 250 GPM COMBINED HOSE STREAM DEMAND.
STORAGE SPACES: ORDINARY HAZARD (GROUP II) OCCUPANCY, 12'0'
MAXIMUM STORAGE HEIGHT, 0,20 GPM /SQFT DENSITY, 130 SQFT MAX
SPRINKLER SPACING, 250 GPM COMBINED HOSE STREAM DEMAND.
e
PERMIT No: N / A
CONTRACT No: C09 -250
APPROVAL: CBT
DRAWN BY: RTS
SCALE: 1/4" = 1' -0'
DATE: 11/19/2009
FLOOR PLAN
FIRE PROTECTION
A
SPRINKLER LEGEND
FINISH ITEMP I K INPT ISIN iMODEL# F p
— BRASS 155 5.60 1/2" GLM15 GLOBE GL SERIES
Y: \Engineering \Project CAD dwgs \Sky Dive City\_Acad \sky dive city - Plot.dwg 2/18/2010 5:03:09 PM
Q)
Q)
l/ 1
0
C\2
4_j
0
i~
0
U
''°'
0
O
�
U
GENERAL NOTES
1, AAA FIRE PROTECTION SERVICES INC (AAA FPS, INC.) SCOPE OF WORK
STARTS AT DISCHARGE 6' UG GATE VALVE TO BLDG RISER. UG WATER
MAIN, TAPPING SLEEVE AND VALVE BY OTHERS.
2. ALL WORK PERFORMED SHALL COMPLY WITH NFPA 13, 24 AND 25
STANDARDS, LOCAL AHJ REQUIREMENTS, AND STATE FIRE MARSHAL
REQUIREMENTS.
3. AAA FPS, INC. SCOPE OF WORK DOES NOT INCLUDE ANY WIRING OF
DEVICES OR PAINTING OF PIPE, ETC.
4. ALL SPRINKLERS SHALL BE STANDARD COVERAGE (QUICK RESPONSE)
ORDINARY TEMPERATURE (UNLESS OTHERWISE NOTED).
5. SPRINKLERS TO BE PROVIDED BELOW ALL EXPOSED DUCT, SUSPENDED
EQUIPMENT AND MEZZANINES EXCEEDING 48" IN WDTH.
6. ALL PENETRATIONS IN FIRE /SMOKE WALLS TO BE PROVIDED WITH A WITH
A U.L. LISTED FIRE STOP ASSEMBLY.
7. UNDERGROUND PIPING SHALL BE FLUSHED PRIOR TO SPRINKLER SYSTEM
BEING TIED -IN.
B. ENTIRE SYSTEM TO BE FLUSHED AND HYDRAULICALLY TESTED IN
ACCORDANCE WITH NFPA -13.
9. SPRINKLER SYSTEM HAS BEEN DESIGNED NTH A MAXIMUM WORKING
PRESSURE OF 175 PSI.
10. ENTIRE SPRINKLER SYSTEM TO BE INSTALLED IN A MANNER THAT THE
ENTIRE SYSTEM CAN BE DRAINED. WHERE REQUIRED AUXILIARY DRAINS
WILL BE PROVIDED.
OCCUPANCY CLASSIFICATIONS
THE FACILITY IS PROTECTED BY A WET -PIPE FIRE SPRINKLER SYSTEM,
BASED ON THE FOLLOWING OCCUPANCIES AND DESIGN CRITERIA:
OFFICES AND LIKE SPACES: LIGHT HAZARD OCCUPANCY, 0.10 GPM /SQFT
DENSITY, 225 SOFT MAX SPRINKLER SPACING, 100 GPM COMBINED HOSE
STREAM DEMAND.
MECHANICAL, KITCHEN, JANITOR, AND LIKE SPACES: ORDINARY HAZARD
(GROUP 1) OCCUPANCY, 0.15 GPM /SOFT DENSITY, 130 SOFT MAX SPRINKLER
SPACING, 250 GPM COMBINED HOSE STREAM DEMAND.
STORAGE SPACES: ORDINARY HAZARD (GROUP II) OCCUPANCY, 12'0'
MAXIMUM STORAGE HEIGHT, 0,20 GPM /SQFT DENSITY, 130 SQFT MAX
SPRINKLER SPACING, 250 GPM COMBINED HOSE STREAM DEMAND.
e
PERMIT No: N / A
CONTRACT No: C09 -250
APPROVAL: CBT
DRAWN BY: RTS
SCALE: 1/4" = 1' -0'
DATE: 11/19/2009
FLOOR PLAN
FIRE PROTECTION