Loading...
HomeMy WebLinkAbout6107 SILVER OAKS DR Electrical Notes 2002 Electrical Code G.L. Steve 6107 Silver Oaks Dr. 210.8(A): All 125 -volt, single- phase, 15- and 20- ampere receptacles installed in the locations specified in (1) through (8) shall have ground -fault circuit - interrupter protection for personnel. (1) Bathrooms (2) Garages (3) Outdoors (6) Kitchens — where the receptacles are installed to serve the countertop surfaces 210.11(C)(3): In addition to the number of branch circuits required by other parts of this section, at least one 20- ampere branch circuit shall be provided to supply the bathroom receptacle outlet(s). Such circuits shall have no other outlets. Exception: Where the 20- ampere circuit supplies a single bathroom, outlets for other equipment within the same bathroom shall be permitted to be supplied in accordance with 210.23(A). 210.12(B): All branch circuits that supply 125 -volt, single phase, 15- and 20- ampere outlets (RECEPTACLES, LIGHTS, SMOKE DETECTORS) installed in dwelling unit bedrooms shall be protected by an arc -fault circuit interrupter listed to provide protection of the entire branch circuit. 210.52(A)(1): Receptacles shall be installed so that no point measured horizontally along the floor line in any wall space is more than 1.8 m (6 ft) from a receptacle outlet. 210.52(c)(1): A receptacle outlet shall be installed at each wall counter space that is 300 mm (12 in.) or wider. Receptacle outlets shall be installed so that no point along the wall line is more than 600 mm (24 in.) measured horizontally from a receptacle outlet in that space. 250.50: If available on the premises at each building or structure served, each item in 250.52(A)(1) through (A)(6) shall be bonded together to form the grounding electrode system 406.8(A): A receptacle installed outdoors in a location protected from the weather or in other damp locations shall have an enclosure for the receptacle that is weatherproof when the receptacle is covered (attachment plug cap not inserted and receptacle covers closed). 406.8(B)(1): 15- and 20- ampere, 125- and 250 -volt receptacles installed outdoors in a wet location shall have an enclosure that is weatherproof whether or not the attachment plug cap is inserted. 08/23/02 8:04 AM 905.1.2 - 905.2.5 has a direct exit to the outside of the building and 905.1.5.4 Audible Alarms. Audible alarm indicating the building is three stories or less in height. appliances shall provide a distinctive sound which shall 2. Groups A, B. E, F. H, M. and R I. R2. R3 and R4 not be used for any purpose other than that of a fire Small Facilities. The manual fire alarm boxes alarm. Such devices shall provide a sound pressure required in 905.1 may be omitted in buildings level of 15 dBA above the average ambient sound level meeting all of the following requirements: in every occupied space within the building. The mini- 1. The building is equipped with an automat- mum sound pressure levels shall be: 70 dBA in build - ic fire detection or automatic sprinkler sys- ings of Group R occupancy, 90 dBA in mechanical tem covering all areas. equipment rooms: and 60 dBA in all other occupancy 2. Actuation of the automatic fire detection or classifications. The maximum sound pressure level for automatic sprinkler system will activate the audible alarm indicating appliances shall not exceed fire alarm system. 130 dBA at the minimum hearing distance from the 3. Provisions are made to manually activate audible appliance. the fire alarm system at a minimum of one centrally located station. 6-905.1.5.5 Accessibility. Alarm systems required to 2 be accessible by 11 -4.1 shall comply with 11 -4.28. 905.1.2 Manual fire alarm boxes shall be located not more than 5 ft (1524 mm) from the entrance to each exit. 905,2 Automatic fire detection 905.2.1 Approved single- station or multiple- station smoke 905.1.3 Each floor shall be zoned separately. No one zone detectors shall be installed in accordance with NFPA 72, may exceed 15,000 sq ft (1394 m A zone indicator Chapter 2, within every dwelling and every dwelling unit panel shall be located at grade level at the normal point of within an apartment house, condominium or townhouse; fire department access or at a constantly attended building and every guest or sleeping room in a motel, hotel or dor- security control center. mitory and sleeping rooms in residential care /assisted liv- Exception: Automatic sprinkler system zones shall not occupa to n installed w th r ind dwell is exceed the area permitted by NFPA 13. the detectors shall be wired in such a manner that the actu- 905.1.4 Upon completion of the fire alarm system, all ation of one alarm will actuate all of the alarms in the indi- alarm initiating devices and circuits, alarm indicating vidual unit. appliances and circuits, supervisory signal initiating devices and circuits, signaling line circuits and primary 905.2.2 In dwellings and dwelling units, a smoke detector and secondary power supplies shall be subjected to a 100 shall be mounted on the ceiling or wall at a point central- percent acceptance test in accordance with NFPA 72. ly located in the corridor or area p giiving access to each group of rooms used for sleeping purposes. Where the 905.1.5 Alarm indicating appliances dwelling or dwelling unit contains more than one story, 905.1.5.1 Required. Alarm indicating appliances list- detectors are required on each story including basements, ed for the purpose shall be provided. but not including uninhabitable attics, and shall be located in close proximity to the stairway leading to the floor 0905.1.5.2 Accessibility. Every required fire alarm above. 2. system s include visible alarm indicating appli- ances in public and common areas. For more specific 905.2.3 In dwelling units with split levels and without an accessib requirements related to alarm indicating intervening door between the adjacent levels, a smoke appliances, refer to 905.1.5.5 and 11 -4.28. detector installed on the upper level shall suffice for the adjacent lower level provided that the lower level is less 905.1.5.3 Activation. The alarm indicating appliances than one full story below the upper level. shall be automatically activated by all of the following where provided: 905.2.4 Smoke detectors connected to a fire alarm system 1. Smoke detectors, other than single- station or shall be installed in accordance with NFPA 72. multiple - station smoke detectors, as required by 905.2. Activation of the alarm system by smoke 905.2.5 In dwelling, dwelling units and sleeping rooms in detectors shall be by either two cross -zoned residential care /assisted living occupancies, smoke detec- smoke detectors within a single protected area or tors shall be hardwired into an ac electrical power source a single smoke detector monitored by an alarm and shall be equipped with a monitored battery backup in verification zone or an approved equivalent all new construction. A monitored battery power source method. shall be permitted in existing construction. 2. Sprinkler water -flow devices; 3. Manual fire alarm boxes; and 4. Other approved types of automatic fire detection device suppression systems. 9.5 FLORIDA BUILDING CODE — BUILDING STILES RESIDENCE SILVER OAKS SUBDIVISION ZEPHYRHILLS FLA PASCO COUNTY 6� x c7 w J Z m 0 I NvEl1i 41' FRONT ELEVATION REAR ELEVATION 24" OVERHANG I F- x c� w x t7 z m F- Z W 12" OVER", 4 DRAWN BY R S HANLEY I ALL THE INFORMATION ON THIS PAGE IS INTENDED TO BE CORRECT BUT MISTAKES CAN BE MADE AND IT IS THE RESPONSIBILITY OF THE 7/15/02 1 CONTRACTOR TO VERIFY ALL INFORMATION PRIOR TO CONSTRUCTION. WE WILL BE AVAILABLE TO HELP RESOLVE ANY PROBLEMS. "C-.1vlr •. AUG 2 3 X002 D.W. SMITH ENGINEERING - FLORIDA # 53608 RIGHT ELEVATION LEFT ELEVATION re V- PRINT REt..'(iJli2E0 PAGE 1 SCALE: 1/4" = V -0" MECHANICAL & ARCHITECTURAL ENGINEERING I HEREBY CERTIFY THAT THESE PLANS AND SPECS ARE IN COMPLIANCE WITH THE 9909 WALLASTON DRIVE DADE CITY ,FLA. 33525 FLORIDA BUILDING CODE 2001 FOR 110 MPH (3 SECOND GUST) WIND ZONE. 352 -521 -0865 OFFICE 352 - 521 -0867 FAX. KEEP FLOUR ELEtiA'fiJN 8" ABOVE ROAD m pd v p j" jj\ 2S U'- STILES RESIDENCE c N1 --k V v f 2 MAIN FLOOR PLAN SILVER OAKS SUBDIVISION ZEPHYRHILLS FLA PASCO COUNTY ELECTRICAL SYMBOLS — LIGHT FIXTURE p POT LIGHT STANDARD SWITCH ff] EXHAUST FAN $a 3 —WAY SWITCH Q5 SMOKE DETECTOR 110v OUTLET Q WALL MOUNTED LIGHT 220v OUTLET COQ DBL FLOOD LIGHT ELEC. PANEL CEILING FAN WITH A LIGHT KIT ALL WORK SHALL COMPLY WITH PREVAILING CODES STANDARD BUILDING, PLUMBING, MECHANICAL, NEC. AND ALUMINUM. ALL OF THE PRODUCTS SPECIFIED ON THIS DRAWING OR ANY OTHER PAGE IN THIS PLAN MAY BE REPLACED WITH THOSE OF GREATER OR EQUAL VALUES. LIVING AREA .......................... 1747 SF COVERED PORCH .................. 112 SF GARAGE ... ............................... 416 SF ENTRY ........ ............................... 34 SF TOTAL UNDER ROOF ..............2309 SFI ma- W.11a.A ELECTRICAL PLAN [ RAGE 2 SCALE: 1/4" = V -O" DRAWN BY R S HANLEY I ALL THE INFORMATION ON THIS PAGE IS INTENDED TO BE CORRECT BUT MISTAKES CAN BE MADE AND IT IS THE RESPONSIBILITY OF THE 7/14/02 I CONTRACTOR TO VERIFY ALL INFORMATION PRIOR TO CONSTRUCTION. WE WILL BE AVAILABLE TO HELP RESOLVE ANY PROBLEMS. D.W. SMITH ENGINEERING - FLORIDA # 53608 MECHANICAL &ARCHITECTURAL ENGINEERING I HEREBY CERTIFY THAT THESE PLANS AND SPECS ARE IN COMPLIANCE WITH THE 9909 WALLASTON DRIVE DADE CITY ,FLA. 33525 FLO lIDA BUILDING CODE 2001 FOR 110 MPH (3 SECOND GUST) WIND ZONE. 352-521-0865 OFFICE 352 - 521.0867 FAX. ALL WORK SHALL COMPLY WITH PREVAILING CODES STANDARD BUILDING, PLUMBING, MECHANICAL, NEC. AND ALUMINUM. ALL OF THE PRODUCTS SPECIFIED ON THIS DRAWING OR ANY OTHER PAGE IN THIS PLAN MAY BE REPLACED WITH THOSE OF GREATER OR EQUAL VALUES. STILES RESIDENCE As ZEPHYRHILLS FLA PASCO COUNTY STANDARD GABLE ENDS WITH 12 " OVERHANGS - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1 1 1 1 ------------------------ ------------------------- -- - - - r - - - - I STEP -DOWN FLOOR 4" MIN 1 , , I IO DENOTES FILLED CELL - - --------------------------- 1 1 ' 1 1 1 1 ; 1 1 I 1 ; 4" 12500 PSI CONCRETE SLAB WITH tL 6X6 10/10 WIRE MESH LAPPED 12" AND TIED 4' OC. A 6 MIL. VISQUEEN VAPOR BARRIER IS TO BE Lip U6' :' AND TAPED OVER A CLEANN LTREATE AND COMPACTED FILL WITH A VALUE OF 2000 PSI. (FIBERMESH OPTIONAL) ' 1 , S VVV 1 I ` I i 1 1 I I 1 1 THE PLUMBING CONTRACTOR IS TO LAYOUT THE PLUMBING FIXTURES -- USING THE FLOOR PLAN. 1 I 1 1 I I 1 1 I � 1 I 1 1 •� ` 1 1 ` I I������������������� 1 1 I 1 1 1 1-- 1----- --- ----- - - - - -- ' I I I I 1 t0 I ------------- ----- - - - --- -- STEP -DOWN FLOOR 4" MIN 1 I 1 � 1 1 STEP -DOWN I � FLOOR 4" MIN ; p , 1 i I , ENTRY r --- - - - - -- -- ; THICKENED EDGE ; 1 I I 1 1 I I I I I 1 I __ _______ ___ _____________ ___________ ____ _ - -- ----------------------------------- 10 -2 1!4 10 -4 5/8 , ' -- - - - - - - - - - - - - - - - - - - - - - - , 1 1 1 1 1 ----------- --- - - - - -- - -------- - - - - - - - � ; I 20' -6 718" 1 1 , 1 1 1 1 1 1 I 1 1 I 1 I I 1 1 1 1 1 I 1 I � � o I 1 I I I I 1 I � I I I I I I 1 I I I I I 1 1 1 1 I 1 I 1 I I 1 I FOUNDATION PLAN _____________ ____________ ____________ ______ 14 I I I , i ' 1 I , , I � 1 , , I 1 1 1 1 1 1 1 I I I I 1 1 1 1 I 1 1 1 1 I 1 1 1 I I I I I 6/12 EXT PITCH 1 1 1 I I I I I 1 � I , I 1 I 1 1 1 , , , , , , 1 I 1 I 1 , , I I 1 1 1 I 1 1 I I I I , 1 1 1 1 1 1 I I I 1 1 I I I 1 I 1 1 I 1 1 1 1 I I � I 1 1 1 I 1 1 � I ; 1 1 1 1 ; 1 1 I I I 1 1 1 I I I I I 1 1 1 1 1 COA6^TRUSSESWITF ANFADDTIONA I I I 1 ; 1 1 75# PLF ON THE BOTTOM CHORD FOR SOME TYPE QF ATTIC STORAGE ; ; I 1 1 1 1 1 � I I ; I I 1 1 1 1 I 1 � � � 1 1 1 1 t � I 1 � 1 1 1 � � 1 1 I 1 1 � 1 1 1 I 1 � 1 1 1 � I 1 1 I 1 I 1 1 � 1 ' I ' � t- -\ --------- - - - --- r I - - - - --- r - 1 ' I I I 1 ; ,' ♦, I ♦♦ 1 a 1 a 1 I I 1 1 I I � � W 1 uJ 1 1 1 , 1 • ♦ S - - - - -- - - - -- - - -- 1 �'� ♦�♦ i 140° ' , 1 , � ♦ 1 I I 1 I - - - - - - - - - - - - - - - - - - - - - - - - - F_ ' STANDARD GABLE ENDS WITH 12 "OVERHANGS -- ------ ROOF FRAMING PLAN #30 ROOFING FELT USE SIMPSON META 16 EMBEDDED TRUSS ANCHORS ON ALL TRUSSES. ANCHORS SHOULD BE EMBEDDED A MIN. OF 4" INTO POURED CONCRETE LINTLE AND ATTACHED TO THE HEELS OF THE PRE ENG TRUSSES WITH 11 -10d X1.5" NAILS FOR A MAX UPLIFT OF 1365# SEE THE DETAIL SHEETS FOR ADDED INFORMATION FIBERGLASS SHINGLES EXT. PITCH ON ELEVATIONS 1/2" CDX PLYWOOD OR OSB NAILED W /81) COMMONS 6 "'OC EXCEPT AS NOTED IN DETAI FASTENERS PRE ENG. TRUSSES 24'0 C MAX SPACING 110 MPH WIND LOADING R -30 INSULATION ALUM. DRIP EAVE 2X SUB - FASCIA VINYL SOFFIT AND FASCIA PRECAST LINTEL AND LINTEL BLOCK WITH (1) #5 REBAR CONT. OF HOUSE 1 SINGLE HUNG WINDOWS I SEE DETAIL SHEETS PRECAST SILL 8 "X16" CONCRETE BLOCKS STUCCO FINISH EXISTING GRADE 8" X 16" CONT. CONCRETE FOOTER WITH (2) d5 REBARS ON ROD CHAIRS BENT AND TIED A MIN. LAP OF 25" UPRIGHTS BENT AND TIED A MIN. LAP OF 25 ". 8' O.C. MAXIMUM SPACING AND BESIDE EACH OPENING. ( FIBERMESH OPTIONAL) I I I I 1 1 1 I 1 1 1 1 ROOF TRUSSES ;---------------------------- il II DBL OP PLAT I COVER KNEEWALL WITH 1/2" CDX OR OSB NAILED WITH 8d COMMONS 3" OC TOP AND BOTTOM EDGES 6" OC SIDE EDGES PT BOTTOM PLATE 12 " INTERIOR E__ _ _ ____ ____________ _ ____ SIMPSON HETA16 EMBEDDED TRUSS ANCHORS 48 "OC MAX KNEEWALL DETAILS EXTERIOR BLOCK WALLS SCALE: 1/4" = V -0" DRAWN BY R S HANLEY 7/14/02 I HEREBY CERTIFY THAT THESE PLANS AND SPECS ARE IN COMPLIANCE WITH THE FLORIDA BUILDING CODE 2001 FOR 110 MPH (3 SECOND GUST) WIND ZONE. 1/2" CEILING DRYWALL 1/2" DRYWALL OVER 3/4" RIGID INSULATION AND 1X2 FURRING STRIPS PAGE 3 i- ac L7 w 2 z J w U 0 0 4" / 2500 PSI CONCRETE SLAB WITH 6X6 10/10 WIRE MESH LAPPED 12" AND TIED 4' OC. A 6 MIL. VISQUEEN VAPOR BARRIER IS TO BE LAPPED 6" AND TAPED OVER A CLEAN TREATED AND COMPACTED FILL WITH A MIN. VALUE OF 2000 PSI. ENGINEER'S NOTES: ALL WORK IS TO BE COMPLETED IN ACCORDANCE WITH THE FLORIDA BUILDING CODE THE BASIC DESIGN WIND SPEED = 110 MPH (3 SECOND GUST) THE IMPORTANCE FACTOR =1.0 ( RESIDENTIAL) THE EXPOSURE CATEGORY = B THE INTERNAL PRESSURE COEFFICIENT = +/- 0.18 THE DESIGN WIND PRESSURE MWRFS = 201 -24 PSF THE DESIGN WIND PRESSURE COMPONENTS AND CLADDING = 221 -29 NOTE: THE MANUFACTURER OF THE WINDOWS AND DOORS ARE TO CERTIFY THEIR ABILITY TO WITHSTAND THE SPECIFIED DESIGN WIND PRESSURE RESULTING FROM THE 110 MPH WIND SPEED AND SUPPLY THE CONTRACTOR WITH INSTALLATION SPECIFICATIONS. ALL WINDOWS AND DOORS ARE TO BE INSTALLED PER MANUFACTURER'S SPECIFICATIONS. MASONRY CONSTRUCTION/ WINDOW INSTALLATION HEAD WINDOW HEIGHT A B SILL A B IUALLY PACE VCHORS JII 6" MIN. 6" MIN. 1) #8 INSTALLATION ANCHORS MUST BE OF SUFFICIENT LTH. TO ACHIEVE MIN. EMBEDMENT OF 1 1/8" INTO 2X BUCK STRIPS 2) THE FASTENING SCHEDULE OF #8 FASTENERS IN THE HEAD 6" IN FROM EACH JAMB #8 FASTENERS IN EACH JAMB 6" OC MIN. SPACING 17" OC MAX. SPACING FOR ALL WINDOW SIZES UP TO 517/8" X 95" (34.22SF ) WITH A DESIGN PRESSURE OF UP TO 70 PSF 3) CAULK BEHIND WINDOW FIN AT HEAD AND JAMBS WITH DUO -SIL ADHESIVE CAULK OR APPROVED EQUAL. USE LATEX CAULK OR EQUAL FOR THE PERIMETER SEAL. 4) CAULK BETWEEN BUCK STRIPS AND MASONRY OPENING THIS INFORMATION WAS OBTAINED THROUGH KINCO , LTD. OF 5245 OLD KINGS ROAD JACKSONVILLE FLORIDA 32254 FROM ENGINEERING PROVIDED FOR THE INSTALLATION OF THEIR PRODUCT. IF OTHER THAN KINCO WINDOWS ARE INSTALLED THE CONTRACTOR WILL NEED TO OBTAIN THE PROPER INSTALLATION ENGINEERING FROM THE MANUF. OF CHOICE. SINGLE HUNG WINDOW SIZES CODE SIZE WINDOW SIZE M.O. 3' - 1 " WIDTH X HEIGHT 1x BUCK STRIPS SH 12 19118X26 19314X26 SH 13 19118X38318 19314X38318 SH 14 19118X50518 19314X50518 SH 15 19118X63 19314X63 SH 16 19118X76 19314X76 SH 3312 26112 X 26 27118 X 26 SH 3312 26112 X 38 318 27 118 X 38 3/8 SH 34/2 26 1/2 X 50 518 27 118 X 50 518 SH 35/2 26112 X 63 27 118 X 63 SH 3612 26112 X 76 27118 X 76 SH 22 37 X 26 37 5/8 X 26 SH 23 37X38318 37518X383/8 SH 24 37X50518 37518X50518 SH #2WE (EGRESS) 37 X 57 314 37 518 X 57 3/4 SH 25 37X63 37518X63 SH 26 37 X 76 37 5/8 X 76 SH 32 53118X26 53314X26 SH 33 53118X38318 53314X38318 SH 34 53 118 X 50 518 53 3/4 X 50 5/8 SH #3WE (EGRESS) 53 118 X 57 314 53 3/4 X 57 314 SH 35 53118X63 533/4X63 SH 36 53118X76 53314X76 ADD 1 112" TO WINDOWS ROUGH OPENING SIZE WHEN USING 2X BUCK STRIPS AND FLANGED WINDOWS THE WINDOWS SPECIFIED ON THIS PLAN ARE BASED OF THE SIZES IN THIS CHART. IT IS THE BUILDERS RESPONSIBILITY TO VERIFY THAT THE SIZES OF THE WINDOWS OF CHOICE ARE THE SAME OR ALLOWANCES MADE WHEN FRAMING IN THE ROUGH OPENINGS. ALL WORK SHALL COMPLY WITH PREVAILING CODES STANDARD BUILDING, PLUMBING, MECHANICAL, NEC. AND ALUMINUM. ALL OF THE PRODUCTS SPECIFIED ON THIS DRAWING OR ANY OTHER PAGE IN THIS PLAN MAY BE REPLACED WITH THOSE OF GREATER OR EQUAL VALUES. DRAWN BY R S HANLEY 7114102 MASONRY WINDOW INSTALLATION WI 1X BUCK STRIPS 6- 6" MIN.( I MIN •--- w c a. w 6 " MIN. STILES RESIDENCE SILVER OAKS SUBDIVISION ZEPHYRHILLS FLA PASCO COUNTY 4 11 MIN. TAPCON 24" I TAPCON 1 16" 1 TMCDN 8" TAPCON 1 16" TAPCON 24" TAPCON 4" MIN. z 3 H 0 W 0 z Vl z Ce O O 0 0- N 00 X w_ L m �x z a , 0 VU O z CL 24" OJ m z _ a. w ~- 611 i TAPCON 4 11 MIN. MIN. SINGLE DOOR 6' -8" 6" 6" LINTLE OVER OPENING MIN. MIN. 3" 1 3 3^ 3 "1 3" I MIN. 6 MIN. CL Y U m w Q a. a w PAGE 4 6 MIN. V) CL Y U m EXTERIOR BLOCK WALL 6 11 6 11 l� MIN. MIN. SINGLE DOOR OR DBL DOOR W / SIDELIGHT SINGLE DOOR 8 0" EXTERIOR BLOCK N Y m WALL V) CL_ fY 6" MIN. THERMA -TRU IN -SWING 1 OUT -SWING DOOR MASONRY SYSTEM ALL THE INFORMATION ON THIS PAGE IS INTENDED TO BE CORRECT BUT MISTAKES CAN BE MADE AND IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY ALL INFORMATION PRIOR TO CONSTRUCTION. WE WILL BE AVAILABLE TO HELP RESOLVE ANY PROBLEMS. D.W. SMITH ENGINEERING - FLORIDA # 53608 1 HEREBY CERTIFY THAT THESE PLANS AND SPECS ARE IN COMPLIANCE WITH THE MECHANICAL &ARCHITECTURAL ENGINEERING 9909 WALLASTON DRIVE DADS CITY ,FLA. 33525 FLORIDA BUILDING CODE 2001 FOR 110 MPH (3 SECOND GUST) WIND ZONE. 352 - 521 -0865 OFFICE 352 -521 -0867 FAX. S ol, N a LINTLE OVER OPENING BUCK STRIPS HE #8 ANCHOR SCREWS ARE ONLY FOR INSTALLATIO VITH A 2X BUCK STRIP WHEN USING A 1X BUCK STRIP )NLY THE TAPCON ANCHORS ARE REQUIRED. 114" MAX. SHIM SPACE 2X BUCK STRIP W/ LOAD BRG SHIM /INTERIOR FINISH WINDOW FRAME JAMB, \ 1 X FURRING #8 ANCHOR WOOD SCREW 1 118" MIN. EMBEDMENT X 3116" TAPCON CONCRETE SCREW WITH A 1 1/4" MIN. EMBEDMENT EXTERIOR BLOCK WALL 1) CAULK BETWEEN BUCK AND MASONRY WALL 2) CAULK BETWEEN FLANGE AND WOOD BUCK 3) PERIMETER CAULK ALL EDGES 4) BUCK STRIP WIDTH PER CONTRACTOR MIN. WIDTH 2X4 MASONRY WINDOW INSTALLATION W/ 2X BUCK STRIPS � 1/4" MAX. SHIM SPACE W/ LOAD BRG SHIM WINDOW FRAME JAMB \ FLANGt:� 1JY_IND0� r WINDOW WIDTH X BUCK STRIP INTERIOR FINIS URRING 3116" TAPCON CONCRETE SCREW F WITH A 1 114" MIN. EMBEDMENT EXTERIOR BLOCK WALL 1) CAULK BETWEEN BUCK AND MASONRY WALL 2) CAULK BETWEEN FLANGE AND WOOD BUCK 3) PERIMETER CAULK ALL EDGES 4) BUCK STRIP WIDTH PER CONTRACTOR MIN. WIDTH 1X4 TAPCON PLACEMENT FOR 2X BUCK STRIPS BUCK STRIPS ARE TO BE A CONTINUOUS PIECE ON THE TOP AND SIDES OF OPENINGS USEING 1X OR 2X #2 PT PINE LUMBER (T -NAILS ARE NOT TO BE USED IN 2X BUCKS, ONLY TAPCON SCREWS) USE VIKING .097" X 13/8" HIGH CARBON T -NAILS AT SPACING INDICATED BELOW BASED ON TOTAL ROUGH OPENING SIZE. MAXIMUM OPENING HEIGHT MAXIMUM OPENING WIDTH T -NAIL SPACING AT TOP AND SIDES 5' - 4 " 3' - 1 " 12" OC 7' -0" 61 -411 91, 0C 7' -0" 12' -0" 6" OC 12' -0" 6" OC USE A MIN OF (3) T -NAILS PER EACH BUCK STRIP THIS INFORMATION WAS FURNISHED BY THERMA -TRU CORPORATION 1687 WOODLANDS DRIVE MAUMEE OHIO PH. (800) 537 - 8827 IF OTHER THAN THERMA -TRU DOORS ARE USED THEN IT WILL BE THE BUILDERS RESPONSIBILITY TO OBTAIN THE ENGINEERED INSTALLATION INSTRUCTIONS FOR THE DOORS OF CHOICE. NOTE: THIS SYSTEM HAS BEEN EVALUATED FOR USE IN LOCATIONS ADHERING TO THE FLORIDA BUILDING CODE AND WHERE PRESSURE REQUIREMENTS AS DETERMINED BY ASCE 7 MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES DO NOT EXCEED THE DESIGN PRESSURE RATINGS LISTED HEREIN. 14" MAX. w v a cn 4 w Ac DESIGN PRESSURE RATING SINGLE DOOR POS 67.0PSF NEG. 67.0 PSF SINGLE WITH SIDELIGHTS POS. 60.0 PSF NEG 60.0PSF DOUBLE W 1 WO SIDELIGHTS POS 47.0 PSF NEG. 47.0 PSF USE A #8 / 2 112" PHILLIPS HEAD WOOD SCREW AT ALL ARROW LOCATIONS AND ONLY ON 2X BUCKS 6" MIN. 14" MAX. DOUBLE DOORS LINTLE OVER OPENING BUCK STRIP 3" r] 1 3" a _ m LINTLE OVER OPENING O 3" 11. MAX. 18" 1 MAX. 18" 11 3" z l IV ? 4 " 0 6^ 6 " MIN.) I MIN. MIN. TAPCON O z 3. I s^ MIN. 2 4 " V? z U) w w TAPCON N O 0 -- a. . ® EXTERIOR a. N - BLOCK WALL = 2411 Y m d s— w — i � v O u. M a `n (n x TAPCON z r ad O O . -- —. V V 14" MAX. DOUBLE DOORS LINTLE OVER OPENING BUCK STRIP 3" r] 1 3" a _ m j.. j THIS BUILDING HAS BEEN DESIGNED TO CONFORM TO THE =LORIDA BUILDING CODE 2001. ENGINEER'S NOTES: THE BASIC DESIGN WIND SPEED = 110 MPH (3 SECOND GUST) THE IMPORTANCE FACTOR =1.0 THE EXPOSURE CATEGORY = B THE INTERNAL PRESSURE COEFFICIENT = +!- 0.18 THE DESIGN WIND PRESSURE MWRFS = 20 I -24 PSF THE DESIGN WIND PRESSURE COMPONENTS AND CLADDING = 221 -29 NOTE: THE MANUFACTURER OF THE WINDOWS AND DOORS ARE TO CERTIFY THEIR ABILITY TO WITHSTAND THE SPECIFIED DESIGN WIND PRESSURE RESULTING FROM THE 110 MPH WIND SPEED AND SUPPLY THE CONTRACTOR WITH INSTALLATION SPECIFICATIONS. ALL WINDOWS AND DOORS ARE TO BE INSTALLED PER MANUFACTURER'S SPECIFICATIONS. PLUMBING ALL PLUMBING FIXTURE LOCATIONS ARE TO BE DETERMINED BY THE PLUMBING CONTRACTOR. THE PLUMBING CODE REQUIRES THAT AT LEAST ONE 3" VENT STACK PIPE WILL BE VENTED THROUGH THE ROOF. EXTERIOR OPENINGS ALL WINDOW AND DOOR OPENING INSTALLATION METHODS ARE DETAILED IN THIS PLAN, BUT IT WILL BE THE CONTRACTORS RESPONSIBILITY TO INSURE THAT THE WINDOWS ARE INSTALLED AS PER THE MANUFACTURES ENGINEERED DRAWINGS AND THAT A COPY OF SAID DRAWINGS ARE ON THE JOBSITE AT THE TIME OF INSTALLATION. ROOF TRUSSES / FLOOR TRUSSES ALL TRUSS BRACING WILL BE SPECIFIED BY THE TRUSS COMPANY EXCEPT FOR GABLE END DIAPHRAGM BRACING DESIGNED FOR THIS PLAN. THIS WILL INCLUDE THE TEMPORARY TRUSS BRACING THAT WILL BE FURNISHED WHEN THE TRUSSES ARE DELIVERED. T- BRACING THAT IS SPECIFIED ON SOME ENGINEERED TRUSS DRAWINGS MAY BE SUBSTITUTED WITH ALTERNATE BRACING. (1) 2X4 CLB MAY BE SUBSTITUTED FOR (1) 1X4 "T" BRACE AND (2) CLB's MAY BE SUBSTITUTED FOR (1) 2X4 "T" BRACE. CLB's ARE TO BE EQUALLY SPACED. ( CLB - CONTINUOUS LATERAL BRACING) THIS INFORMATION WAS OBTAINED THROUGH ALPINE ENGINEERED PRODUCTS 1950 MARLEY DRIVE HAINES CITY FLORIDA 33844 (941) 422 -8685 WALTER P. FINN P.E. PRE - ENGINEERED ROOF TRUSSES 24" OC MAXIMUM SPACING TC LL 30.0 PSF TC OL 7.0 PSF BC DL 10.0 PSF BC LL 0.0 PSF 10d TOT.LD. 47.0 PSF DUR.FAC. 1.33 DEFLECTION MEETS L ! 360 LIVE AND L 1240 TOTAL LOAD DESIGN CRITERIA: FLOOR TRUSSES SPACING 16" AND 24" OC DEPTH 16" TC LL 40.0 PSF TC DL 10.0 PSF BC DL 5.0 PSF TOTAL LOAD 55.0 PSF DURATION FACTOR 1.00 DEPTH AND SPACING MAY VARY GABLE TRUSS VERT WEB L- BRACING NO BRACING REQUIRED FOR WEBS UP TO 4' -1" IN LENGTH. USE (1) 1X4 L -BRACE FOR WEBS UP TO 6' -1" USE (1) 2X4 L -BRACE FOR WEBS UP TO 8' -0" USE (2) 2X4 L -BRACE FOR WEBS UP TO 9' -8" USE (1) 2X6 L -BRACE FOR WEBS UP TO 12' -6" USE (2) 2X6 L- BRACES FOR WEBS UP TO 14' -0" NAIL L- BRACES WITH 10d NAILS 2" OC IN 18" END ZONES AND 4" OC BETWEEN ZONES PROVIDE FOR CONNECTIONS OF 160 PLF OF UPLIFT OVER CONTINUOUS BEARING 112" CDX OR OSB SHEATHING NAILED WITH 8d COMMON NAILS 6" OC IN ALL AREAS EXCEPT IN THE AREA 8' IN ON EACH GABLE TO BE NAILED 3" OC. RIDGE VENT PER SEC. 2309.7 2X4 DIAGONAL BRACING @ 48 "OC NAILED WITH 2 1; AT THE TOP CHORD OF THE TRUSS THE BOTTO CF THE TRUSS AND INTO THE STRINGEk. 2X4 STRINGER 48'0 C NAILED WITH (2) 12d COMMONS IN EACH TRUSS THE STRINGER IS TO BE CONTINUOUS THE ENTIRE LENGTH OF THE BUILDING- IN LIEU OF STRUCTURAL CEILING PANEL . 2X4 BLOCKING BETWEEN TRUSSES 48'0 C NAILED WITH (2) 12d NAILS EACH END GABLE BRACING DETAIL / FRAME WALLS FOUNDATION NOTES A CONCRETE ENCASED "LIFER" ELECTRODE IS REQUIRED PER ART 250 -50 1999 N.E.C. INSPECT PRIOR TO CONCRETE PLACEMENT THESE PLANS WERE DESIGNED BASED UPON AN ALLOWABLE SOIL BEARING CAPACITY OF 2000 PSI (MIN.) IT IS THE CONTRACTOR 1 HOMEOWNERS RESPONSIBILTY TO INSURE THAT THIS MIN IS PROPERLY PREPARED AND COMPACTED. GABLE TRUSS BRACING SEE CHART THIS PAGE 112" CDX OR OSB SHEATHING NAILED WITH 8d COMMON NAILS 6" OC N ALL EDGES AND IN THE FIELD EXCEPT AS NOTED RIDGE VENT PER SEC. 2309.7 2 DIAGONAL 48" 0 C NAILED WITH (2) 12d COMMONS >, TOP CHORD OF TRUSS, BOTTOM CHORD OF RUSS AND INTO THE SIDE OF THE STRINGER 2X4 STRINGER 48" 0 C NAILED WITH (2) 12d COMMONS IN EACH TRUSS 112' CEILING DRYWALL 2X4 BLOCKING BETWEEN TRUSSES 48" O C NAILED WITH (2) 12d NAILS EACH END r NAIL THIS AREA 3" OC OOF Tf USSE GABLE TRUSS BRACING PER TRUSS COMPANY SEE CHART THIS PAGE " 12 12 USE 16d NAILS @ 8" OC TO ATTACH TH BOTTOM CHORD OF THE GABLE TRUSS TO THE TOP PLATE NAILER AND 8d NAILS TO ATTACH THE SHEATHING TO THE GALE TRUSS ATTACH 2 X 8 PT NAILER ❑ 8" EXT BLOCK WALL TO THE BLOCK WALL WITH I I 6" J -BOLTS 48" OC ALONG ENTIRE LENGTH OF THE WALL. GABLE BRACING DETAIL / BLOCK WALLS PAGE 5 GARAGE DOOR DETAIL / FRAME WALLS ALL BUILDINGS ARE REQUIRED TO HAVE A PRE CONSTRUCTION TERMITE TREATMENT PER FBC 1816.7 INITIAL SOIL POISONING TREATMENTS SHALL BE DONE AFTER ALL EXCAVATION, BACKFILLING AND COMPACTING ARE COMPLETED. ALL CRAWL SPACES WILL HAVE AT LEAST (1 SF OF OPENING FOR EVERY 150 SF) OF CRAWL SPACE. THE OPENINGS SHALL BE ARRANGED TO PROVIDE CROSS VENTILATION AND COVERED WITH CORROSION RESISTANT WIRE MESH. PLUMBING AND ELECTRIC IN ACCORDANCE WITH CHAPTER 471.003 (2) (1) OF THE FLORIDA ADMINISTRATIVE CODE, ELECTRICAL, PLUMBING AND MECHANICAL SYSTEMS SHALL BE DESIGNED BY THE RESPECTIVE CONTRACTORS TO MEET ALL APPLICABLE CODES. THE SYSTEMS DRAWN HERON ARE BASED UPON THE HOMEOWNERS REQUIREMENTS. ALL ELECTRICAL OUTLETS IN BATHROOMS, KITCHENS, AND EXTERIOR AREAS ABOVE COUNTER HEIGHTS AND WITHIN 6' -0" OF SINKS SHALL BE GFI ( GROUND FAULT INTERRUPTER) ALL ELECTRICAL OUTLETS IN BEDROOMS SHALL BE WIRED INTO AN ARC -FAULT INTERRUPTER "AFI" CIRCUIT SMOKE DETECTORS SHALL BE PLACED IN EACH BEDROOM AND IN HALLWAY AREAS ADJACENT TO BEDROOM AND OTHER LIVING AREAS SMOKE DETECTOR PER SEC.905.2.5 ---------------- _SPLICE BLOCK 1 0-011 EXT WALL 10d NAILS BOTTOM EDGE 3" OC DBL ROWS -- --- L- --- --- 1 - - - - - -- - _-_ -- - _-_- _ -_ -_ -- - - - -- - -- - - - --- - -- - - -- - - -_ Od NAILS BOTTOM EDGE 10d NAILS BOTTOM EDGE 3" O C DBL ROWS 3" OC DBL ROWS UPLIFT CAPACITY OF 15132" WOOD STRUCTURAL PANEL SHEATHING FOR BOTH SHEARWALLS AND UPLIFTS SIMULTANEOUSLY ( 855 PLF) DRAWN BY R S HANLEY ALL THE INFORMATION ON THIS PAGE IS INTENDED TO BE CORRECT BUT MISTAKES CAN BE MADE AND IT IS THE RESPONSIBILITY OF THE 7114102 CONTRACTOR TO VERIFY ALL INFORMATION PRIOR TO CONSTRUCTION. WE WILL BE AVAILABLE TO HELP RESOLVE ANY PROBLEMS. ALL WORK SHALL COMPLY WITH PREVAILING CODES STANDARD BUILDING, PLUMBING, MECHANICAL, NEC. AND ALUMINUM. SCALE: 1/4" = V -0" D.W. SMITH ENGINEERING - FLORIDA # 53608 MECHANICAL & ARCHITECTURAL ENGINEERING I HEREBY CERTIFY THAT THESE PLANS AND SPECS ARE IN COMPLIANCE WITH THE 9909 WALLASTON DRIVE DADE CITY ,FLA. 33525 FLORIDA BUILDING CODE 2001 FOR 110 MPH (3 SECOND GUST) WIND ZONE. 352 - 521 -0865 OFFICE 352- 521 -0867 FAX. 8 0 . 011 �NAiLift�`�� RD F OOF T USSE j 10d NAILS TOP V 3" 6C DBL RbWS I I V -------F-------I-------- I ( ------1--------I-------- O 10d NAILS BOTI) EDGES ROW 3" C DBL I I � III V i I V o I I o I o I v � I N I cn 0 I I 0 co J i w w I o I F I o 0 l z I � rn R I R l R z I z 1 z 0 0 0 I I I I 1 0-011 EXT WALL 10d NAILS BOTTOM EDGE 3" OC DBL ROWS -- --- L- --- --- 1 - - - - - -- - _-_ -- - _-_- _ -_ -_ -- - - - -- - -- - - - --- - -- - - -- - - -_ Od NAILS BOTTOM EDGE 10d NAILS BOTTOM EDGE 3" O C DBL ROWS 3" OC DBL ROWS UPLIFT CAPACITY OF 15132" WOOD STRUCTURAL PANEL SHEATHING FOR BOTH SHEARWALLS AND UPLIFTS SIMULTANEOUSLY ( 855 PLF) DRAWN BY R S HANLEY ALL THE INFORMATION ON THIS PAGE IS INTENDED TO BE CORRECT BUT MISTAKES CAN BE MADE AND IT IS THE RESPONSIBILITY OF THE 7114102 CONTRACTOR TO VERIFY ALL INFORMATION PRIOR TO CONSTRUCTION. WE WILL BE AVAILABLE TO HELP RESOLVE ANY PROBLEMS. ALL WORK SHALL COMPLY WITH PREVAILING CODES STANDARD BUILDING, PLUMBING, MECHANICAL, NEC. AND ALUMINUM. SCALE: 1/4" = V -0" D.W. SMITH ENGINEERING - FLORIDA # 53608 MECHANICAL & ARCHITECTURAL ENGINEERING I HEREBY CERTIFY THAT THESE PLANS AND SPECS ARE IN COMPLIANCE WITH THE 9909 WALLASTON DRIVE DADE CITY ,FLA. 33525 FLORIDA BUILDING CODE 2001 FOR 110 MPH (3 SECOND GUST) WIND ZONE. 352 - 521 -0865 OFFICE 352- 521 -0867 FAX. 8 0 . 011 �NAiLift�`�� RD F OOF T USSE j GARAGE DOOR DETAIL / BLOCK CONSTRUCTION ® 0 V ® ® ® 0 0 0 V O I ( A MINIMUM OF 2X6 PINE GRADE LUMBER AROUND DOOR OPENING ATTACHED WITH (4) 112" X6" LAG BOLTS SPACED EQUALLY EACH SIDE AND 24 ACROSS THE TOP. O GARAGE DOOR DETAIL / BLOCK CONSTRUCTION 12" MAX. OVERHANG WITHOUT THE USE OF DROP GABLES NAIL GABLE TRUSS BOTTOM CHORD TO LEDGER WITH 12d COMMONS 8" OC NAIL LEDGER TO TOP PLATE OF EXT WALL WITH 12d COMMON NAILS 8" OC ALL DOOR HARDWARE TO BE INSTALLED PER MANUFACTURES SPECIFICATION WITH THE SAME ALLOWANCE FOR 110 MPH WIND. GARAGE DOOR TO BE REINFORCED TO WITHSTAND UP TO '110 MPH WIND LOAD ALL DOOR HARDWARE TO BE INSTALLED PER MANUFACTURES SPECIFICATION WITH THE SAME ALLOWANCE FOR 110 MPH WIND. 'JARAGE DOOR TO BE REINFORCED TO WITHSTAND UP TO 110 MPH WIND LOAD ALL OF THE PRODUCTS SPECIFIED ON THIS DRAWING OR ANY OTHER PAGE IN THIS PLAN MAY BE REPLACE WITH THOSE OF GREATER OR EQUAL VALUES. 0 ® 0 0 V ® ® ® 0 0 0 V O I ( A MINIMUM OF 2X6 PINE GRADE LUMBER AROUND DOOR OPENING ATTACHED WITH (4) 112" X6" J -BOLTS SPACED EQUALLY EACH SIDE AND 24110C ACROSS THE TOP. O 12" MAX. OVERHANG WITHOUT THE USE OF DROP GABLES NAIL GABLE TRUSS BOTTOM CHORD TO LEDGER WITH 12d COMMONS 8" OC NAIL LEDGER TO TOP PLATE OF EXT WALL WITH 12d COMMON NAILS 8" OC ALL DOOR HARDWARE TO BE INSTALLED PER MANUFACTURES SPECIFICATION WITH THE SAME ALLOWANCE FOR 110 MPH WIND. GARAGE DOOR TO BE REINFORCED TO WITHSTAND UP TO '110 MPH WIND LOAD ALL DOOR HARDWARE TO BE INSTALLED PER MANUFACTURES SPECIFICATION WITH THE SAME ALLOWANCE FOR 110 MPH WIND. 'JARAGE DOOR TO BE REINFORCED TO WITHSTAND UP TO 110 MPH WIND LOAD ALL OF THE PRODUCTS SPECIFIED ON THIS DRAWING OR ANY OTHER PAGE IN THIS PLAN MAY BE REPLACE WITH THOSE OF GREATER OR EQUAL VALUES. I I V I I I I V O I ( O O � III I I I rn tti I w I w I v I a I o z I ( vi v co J i J R z z I l 0 0 l 0 V_ I I I L J 12" MAX. OVERHANG WITHOUT THE USE OF DROP GABLES NAIL GABLE TRUSS BOTTOM CHORD TO LEDGER WITH 12d COMMONS 8" OC NAIL LEDGER TO TOP PLATE OF EXT WALL WITH 12d COMMON NAILS 8" OC ALL DOOR HARDWARE TO BE INSTALLED PER MANUFACTURES SPECIFICATION WITH THE SAME ALLOWANCE FOR 110 MPH WIND. GARAGE DOOR TO BE REINFORCED TO WITHSTAND UP TO '110 MPH WIND LOAD ALL DOOR HARDWARE TO BE INSTALLED PER MANUFACTURES SPECIFICATION WITH THE SAME ALLOWANCE FOR 110 MPH WIND. 'JARAGE DOOR TO BE REINFORCED TO WITHSTAND UP TO 110 MPH WIND LOAD ALL OF THE PRODUCTS SPECIFIED ON THIS DRAWING OR ANY OTHER PAGE IN THIS PLAN MAY BE REPLACE WITH THOSE OF GREATER OR EQUAL VALUES.