HomeMy WebLinkAbout13-14281 CITY OF ZEPHYRHILLS
, � � 5335-8TH STREET
' (si3)�so-oozo 14281
BUILDING PERMIT
Permit Number: 14281 Address: 39704 MEADOWOOD LP
Permit Type: MECHANICAL ZEPHYRHILLS, FL.
Class of Work: A/C CHANGEOUT Township: Range: Book:
Proposed Use: NOT APPLICABLE Lot(s): Block: Section:
Square Feet: Subdivision: MEADOWOOD ESTATES
Est. Value: Parcel Number: 13-26-21-0140-00000-0210
Improv. Cost: 5,000.00 ° _ �
Date Issued: 6/13/2013 Name: CARVALHO, RICHARD & SANDRA
Total Fees: 60.00 Address: 39704 MEADOWOOD LP
Amount Paid: 60.00 ZEPHYRHILLS, FL. 33542
Date Paid: 6/13/2013 Phone: (813)469-2321
Work Desc: A/C CHANGE OUT 3TON 13 SEER
���
1
�
i
DUCTSINSULATED
FINAL (,i--Z�'"
REINSPECTlON FEES: Reinspection fees will comply with Florida Statute 553.80(2)(c)when extra inspection
trips are necessary due to any one of the following reasons: a)wrong address b)condemned work resulting
from faulty construction c) repairs or corrections not made when inspections called d) work not ready for
inspection when called e) permit not posted on job site� plans not at job site g)work not accessible.
NOTICE: In addition to the requirements of this permit, there may be additional restrictions applicable to this property that
may be found in the public records of this county, and there may be additional permits required from other governmental
entities such as water management, state agencies or federal agencies.
"Warning to owner: Your failure to record a notice of commencement may result in your paying twice for
improvements to your property. If you intend to obtain financing,consult with your lender or an attorney
before recording your notice of commencement."
Complete Plans, Specifications Must Accompany Application.All work shall be pertormed in accordance with
City Codes and Ordinances. NO OCCUPANCY BEFO C.O.
n _
�l�
CONTRACTOR SIGN E PERMIT OFFI R
PERMIT E�IRES IN 6 MONTHS WITHOUT APPROVED INSPECTION
CALL FOR INSPECTION - 8 HOUR NOTICE REQUIRED
PROTECT CARD FROM WEATHER
e��-�e°'°°2o City of Zephyrhills Permit Application F,�-e��-�so.00s�
� Bullding Department
9�h R�alwd t� �`-3 Phon�Conqet for Pamlltln
-rr-r'r-rrrr —
Ownds Nrn� A V Q�I �l7 Own�►Phon�NumMr ' 0 c1� ` ��
OwnrrsAddr«s 3 ��4 m��a� WCGJ�' Own�rPhon�NwnMr ��
—�
FN Simpl�TlWhold�d Nam� N! _ Ownw PboM N�wnMr ��
FN Simph TMMhold�{Addnss �
JOB ADDRESE /��–I 17OU C�du C LOT/ �
susomsioN M t�,��,v i,,�a c�G� PARCEL 10/ l �Cr�ot/�G/ , 6�-aix,—�/o
�osr�a�m�eor v�em r�z�on�
WORK PROPOEED B NEw CoNSTR� ADDlALT O SIGN � Q DEMpL�SH
INSTALL REPAIR
PROPp8ED USE Q SFR � COMM Q OTHER ��
TYPE OF CONSTRUC710N O BLOCK � FRAME O STEEL a �—�,
DESCRIPTION OF WQRK C �'A�� U�— 3`�►�-� I� SE'2.-�
BUILDINO SIZE 8Q FOOTAOE C� NEIOHT �
�BUILDING S VALUATION OF TOTAL CONSTRUCTION
�E����- S AMP SERVICE Q PROGRESS ENERGY Q W.R.E.C.
QPLUMBING j
�MECHANICpL s ��� VALUATION OF MECHANICAL INSTALLATION
Q� � ROOFING O SPECIALTY Q OTHER
FINISHED FLOOR ELEl�AT10NS FLOOD 20NE AREA QYES NO
BUILDER COMPANY _—�
s��NATU(� REGISTERED Y/N FEE CUI�T Y/N
Add1Nt Lkeflse# ��
ELECTiiC1AN CONPANY —�
810NA7URE REGISTERED Y/N �cupR6� Y/N
�wdrps ucenee#��
PLUMBER �pNP�y �
s�ONATURE REGISTEREA V/ N FEE CURRB. Y/N
AddfMt �_ LICMtse p��
MECHAIi1CAL CpMPANY /7/�� J�«[ !CG� S
a���� RE6ISTERED Y/ N r'�ctxute� Y/N
� Uoenae# L L•l?(_��/�!/CJ! 'S I
OTHER C�P�,
$���T�� REGISTERED Y/N FEe CuRRe, Y/N
Addras Licenee#��
IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIi111111111I111111I111t1Ii1 / 11tI
RESIDENTiAL Aqach(2)Plot Plans:(2)asfs cf guNdiny pla�y�(�)a�a{Enagy Forma;R-0-W PermR for new canstructlan,
I�Inlmum ten(10)wwpng deya aRsr submiltal data. RepuYed qqke.Co�ahuctlon Plans.Stamnveter Plam w/SIIt Fence Instdisd,
Slanitary FadlPoes d,t dumpatx,Site Work Permk far subdivisionyler�p projscts
COMMERCIAL qUad�(3)compbte asb d B�ding Plam plus a Llfs Safety Pape:(1)set d Enarpy Forms.R-O-W Pertnk fa nsw mr�struc:yon.
Minimum ten(t o)worldn0 dM alte►submktal dets. Requked amke.Construetlon Plara�StormMater PlerM w/SiR FMOe irutalled,
S�itary Fadlltlss 6 1 dumpster.Ske Wak Parmft ta all new projeaffi.All commerdal requiremaMa must meet oompliancs
aION PERMIT Aqtadi(2)teb of Enpineersd Plens.
""'PROPERTY 3URVEY rsqtdred for aN NEW construdion.
DI►�etlons:
FlII out appliptipn completely.
Ownsr d ConhMsOor sign bsdc d application,rwtarizwd
If owr t2500�!Netle�of Comm�nart�nt b nqulnd. (AfC upprada owr t7500)
" npenc(ror me cbnvaaa>ar Powx of ntt«ney(tor ti,e owne.>,NOUId be someone wim nocarizea�ener from owne�wn,oribn9 same
OVFR THE COUNT�R PERMITTING (Front of Appllcetlon Ony)
Rsroots if ahqigbs Sewrers Savice Upgrades MC Fences(PIoUSurvey/FOMa9e)
DrMw�s-NoC over Countx H m pudle roadways..needs ROW
' NOTI�E�OF DEED RESTRICTIONS: The undersigned understsnds that this pertnit may be subjed to'deed'restrictions'
� which may be mae reatrktive than CouMy rogulations. The undersigned assumes responsibility for compliance with any
applicable dsed restrictlons.
UNLICENSED CONTRACTORS AND CONTRACTOR RESPONSIBILITIES: If the owner has hired a c�ntractor or
contractors to undertake work,thay may be required to be licensed in accordance with state and local regulations. If the
oontrac�or is not licbnsed es roquired by law, both the owner and contractor mey be dted for a misdemeanor violatlon
under state law. If the owner or intended contractor are unc�rtain as to what Ucensing requirements may apply for the
intended work,they are advised W c�ontact the Pasco County Building Inspecdon DNision�..icensing Section at 727-847-
8008. Furthertnore, it the ownor has hired a coMrac�ar contractors, he is edvised to have the contradw(s) sign
portions of the'oontractor Block'of this applicatlon fa�which they will be responsible. H you,as the owner sign as the
contractor,that may be an indicatlon thffi he is not properly iicensad and is not entltled to pertnitting privileges in Pasco
County.
TRANSPORTATION IMPACTN71L117E3 IMPACT AND RESOURCE RECOVERY FEES: The undersigned understands
that TrensportaUon Impad Fees and Recourse Recovery Fees may apply to the c�nnstruction of new buildings,change of
usa in e�dstlng buildings,or expansion of epsting buildings,as specHiad in Pasoo County Ordinance number 88-07 end
90-07,as amendad. Tha undersigned also understands,that such fees,as may be due,will be identlfled at the tlme of
permitting. It is further understood that Trenaportatlon Impect Fees and Resource Reoovery Fees must be paid prior to
recsiving a'certlflcate oi occupancy'or flnal power release. If the project does not invdve a cartlflcate of oa;upancy or
final power release,the feas must be paid prior to parmft issuance. Furthertnore,if Pasco County WatedSewer Impact
fees aro due,they must be paid prior to permit issuance in axordance wtth appticable Pasco County ordinanc�s.
CONSTRUCTION LIEN LAW(Chapter 713,FMrida Stabit�s.as amsnd�d): If valuatlon of work is 52,500.00 or more.I
certlty tl►at I, tl�a applicant, have been provided wlth a copy of the 'Florida ConsVuctlon Lien Law--Fiomeowner's
Protedion Guide'prepered by the Fbrida Department of Agriculture and Consumer Alfairs. If the applicant is someone
other than the"owner",i certify that I have obtained a copy of the above described document and promise in good faith to
deliver it to the`ovmer prior to commencement.
CONTRACTOR'S/OWNER'S AFFIDAVIT• I certity that all the information in this application is accurate and that all woric
will be done in compliance with ail applicable laws regulating�nsWctfon,zoning and land development Application is
hereby made to obtain a pertnit to do wak and installation as indicated. I certlty that no work or dnstallstfon has
commenced prior to issuance of a pertnit and that all worlc will be pertormed to meet atandards ot all laws regulatlng
constructlon, County and City codes, zoning regulatlons, and land davelopment regulaUons in the juriadicNon. I also
oertliy that I understand that the regulations af other govemmeM agencies mey apply to the intended work,and that it is
my responsibility to idantHy what acUons I must take to be in compliance. Such agencies indude but are not limited to:
- Department of EnvironmaMel Protedion-Cypress Bayheads, WeUand Aroas and Environmentally Sensitive
Lands,WateNWastewater Treatment.
- Southwest Florida Water Management District-Wells, Cypress Bayheads, Wetland Areas, Altering
wacarcourses.
- Artny Corps of Engineers-Seawalis,Docks,Navigable Waterways.
- DepaRme�t of Heatth 8 Rehabilitative ServiceslEnvironmantal Heaith Unk-Wells, Wastewater Treatment,
Septic Tanks.
- US Environmental Protectlon Agency-Asbestos abatement.
- Federal Aviation Authority-RumNays.
I understand that the following reatridions apply to the use of fill:
- Use of fill is not allowed in Flood Zone"V'unless e�cpressly permitted.
- Ii the fill matarial is to be used in Flood Zone 'A', ft is understood that a drainage plan addressing a
'compensatlng volume'will be submitted at tlme of permitting which is prepared by a professional engineer
licensed by tha Stata of Florida.
- If the flll material is to be used in Flood 2one "A' in connec�lon with a permitted building using stem wall
construction,I certify that fl1►witl be used onry to flll the area within the stem wa11.
- If ftll material is to be used in any area, I ceRify that use of such fill will not adversely affect adjacent
properties. If use of fill is found to adversely a�adjacent propertles,the owner may be dted for vidatlng
the conditlons of the building pertnit iasued under d�e attsched pertnit app8catlan,for lots less than one(1)
acxe which are elevated by fill,an engineered drainage plan is required.
If I am the AGENT FOR THE OWNER,I promiae in good faifh to inform the owner of the pertnilting conditions set forth in
this atfidavit prior to commenang c:onstruction. I understand that a separate permit may be roquirad for electricai work,
plumbing, signs, wells, pools, air conditloning, gaa, or other installatlons not speciflcally Induded in the appHcation. A
perm(t issued shall be construed to be a license to proceed wlth fhe work and not as autl�to violate,cencel,alter,or
set asida any provisions of the technical codes,nor shall issuance of a pertnit preverH the Building Oflidal from y�ereafter
requiring a cortgction of errors in plana,construdion or violatfons of any codes. Every permR issued shall become invalid
unless the work authorized by such permit is commenoed within six months ot pertnit issuance,or if work authorized by
the permit is suspended or abandoned for a pe►iod of six(6)moMhs after the time the wa�k is commenc�d. M extension
may be requested, in writing,Trom the Buflding Oflicial for a period not to exceed ninety(90)days and will demonstrate
justifiable cauae for the extension. If work ceases for ninety(90)consecutive days,the job is considered abandoned.
WARNIN(i TO OWNER: YOUR FAILURE TO RECORD A NOTICE OF COMMENCEMENT MAY RESULT IN YOUR
PAYING T1MCE FOR IMPROVEMENTS TO YOUR PROPERTY. IF YOU INTEND TO OBT N FINANGNO,CONSULT
FLORIDA JURAT(F.S.117.03)
OWNER OR AOEMT CONTRACT
Subwibsd�swom to(or alllm�d)bsfors ms this Su�sd and to or alMrmsd) msy�y,.,
/a— by _ �1.�Je G 1 5
Wlw Wero psrsonsly knov�m to ms«haNhaw produced who wars ps�onel�r Ivwrrn ro me a hr�meve praeucsd —
es identlfleafiai. es Idantllitxtlon.
Notsry Public / �/�-G.✓j � �1 iotsry Pudic
Commiaaion No. Commission No.
Name oi Nokary tYPed�PAMed or tlamP� N�Nofary`sd,prtntsd a dartpsd �
�v�� Notary Public State of Florida
Mary V Stewart
My Commission EE 216630
�q�.� Expiros 07/18/2016
CITY OF / / / / BUILDINO
ZEPHYRHaLL3 DEPARTMENT
OF ADDITION OR CORRECTION
� • • - •
ADDRE55 DATE PERMIT�,
�� �� r�`�. L ��Z� /�`� �
THIS JOB HAS NOT BEEN COMPLETED. The following additions or corrections shall be mcde before the job
will be accepted.
� � ''^ � �' �'` `y �1 L S
/ �' � `' ' ' 1�' k' � � ��i �O�P�c• ��`C�4e.,.
_ '
C��tIY �b Ar�� �Z c�ne.�t hu,u�� cl�ca�.8c �,T �y�,,,,, b aiz•�,�
�t is un�awFul tor any Carpenter,Contractor,euilder,or other persons,to AFTER CORRECTIONS ARE MADE CALL
cover or cause to be covered,any part of the work with flooring,�ath,earth 780-0020 FOR RE-INSPECTION
or other material,until the proper inspector has had ample time to approve
the installation.
OFFICE HOURS 7:30 AM-5 PM MON.-FRI INSPECTOR
Ca valho Residence
HVAC Load Calculations
for
Richard Cavalho
39704 Meadow Wood Loop
Zephryhil Is,fl 33542
����� H1lA� L�
Prepared By:
Blake Lanier
Cool Now
6008 JETPORT INDUSTRIAL BLVD
TAMPA, Fl_, 33634
813-445-4818
Monday,June 03, 2013
Rhvac is an ACCA approved Manual J and Manual D computer program.
Calculations are pertormed per ACCA Manual J 8th Edition, Version 2,and ACCA Manual D.
-� ,,:'- -r-- ,.
',-4�- �� . � ':.� j� -��'
. '� ° � .•.��°•
- ,-ti��rt''-
Project Report
Project Title: Cavalho Residence
Designed By: Blake Lanier
Project Date: May 24th 2013
Client Name: Richard Cavalho
Client Address: 39704 Meadow Wood Loop
Client City: Zephryhills,fl 33542
Client Phone: 813-788-0044
Company Name: Cool Now
Company Representative: Blake Lanier
Company Address: 6008 JETPORT INDUSTRIAL BLVD
Company City: TAMPA, FL, 33634
Company Phone: 813-445-4818
Company E-Mail Address: OFFICE@COMFORTISCOOL.COM
Company Website: WWW.COMFORTISCOOL.COM
Reference City: Tampa, Florida
Building Orientation: Front door faces West
Daily Temperature Range: Medium
Latitude: 28 Degrees
Elevation: 19 ft.
Altitude Factor: 0.999
Elevation Sensible Adj. Factor: 1.000
Elevation Total Adj. Factor: 1.000
Elevation Heating Adj. Factor: 1.000
Elevation Heating Adj. Factor: 1.000
Outdoor Outdoor Outdoor Indoor Indoor Grains
Dry Bulb Wet Bulb Rel.Hum Rel.Hum Drv Bulb Difference
Winter: 40 37.52 80% n/a 70 n/a
Summer: 95 77 45% 50% 75 46
Total Building Supply CFM: 1,480 CFM Per Square ft.: 1.063 *
Square ft.of Room Area: 1,392 Square ft. Per Ton: 469
Volume (ft3) of Cond. Space: (clg.) 16,703
" Based on area of rooms being heated or cooled (whichever governs system) rather than entire floor area.
Total Sensible Gain: 32,542 Btuh g1 %
Total Latent Gain: 3,076 Btuh g ��,
Total Cooling Required Including Ventilation Air: 35,618 Btuh 2.97 Tons (Based On Sensible+ Latent)
Rhvac is an ACCA approved Manual J and Manual D computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2,and ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
your design conditions.
C:\UsersWaosn\Desktop\ELITE\BETTS.rhv Monday,June 03,2013, 2:01 PM
� f -4,��.::� :%:� 7�$"�y r -3'�' a -,t�. ��-,
, � ��.. �„� � � ��,..
� �
�a:. w� °��`: s&x s.�� ��?- .� �� '.�.°�s
� �. �', .�.,.
Miscellaneous Report
Winter: 40 37.52 80°/a n/a 70 n/a
Summer: 95 77 45% 50% 75 46.41
Main Trunk Runouts
Calculate: Yes Yes
Use Schedule: Yes Yes
Roughness Factor: 0.00300 0.01000
Pressure Drop: 0.1000 in.wg./100 ft. 0.1000 in.wg./100 ft.
Minimum Velocity: 650 ft./min 450 ft./min
Ma�mum Velocity: 900 ft./min 750 ft./min
Minimum Height: 8 in. 8 in.
Mabmum Height: 8 in. 8 in.
Winter Summer
Infiltration Specified: 0.000 AC/hr 0.230 AC/hr
0 CFM 64 CFM
Infiltration Actual: 0.000 AC/hr 0.230 AC/hr
Above Grade Volume: X 0 Cu.ft. X 16.703 Cu.ft.
0 Cu.ft./hr 3,842 Cu.ft./hr
X 0. 167 X 0.0167
Total Building Infiltration: 0 CFM 64 CFM
Total Building Ventilation: 0 CFM 0 CFM
---System 1---
Infiltration &Ventilation Sensible Gain Multiplier: 21.98 = (1.10 X 0.999 X 20.00 Summer Temp. Difference)
Infiltration &Ventilation Latent Gain Multiplier: 31.54 = (0.68 X 0.999 X 46.41 Grains Difference)
Infiltration &Ventilation Sensible Loss Multiplier: 32.98 = (1.10 X 0.999 X 30.00 Winter Temp. Difference)
Winter Infiltration Specified: 0.000 AC/hr(0 CFM), Construction:Average
Summer Infiltration Specified: 0.230 AC/hr(64 CFM), Construction:Average
1 Supply Main Attic 16B 0.12 6 112 No
1 Return Main Attic 16B 0.24 6 112 No
C:\UsersWaosn\Desktop\ELITE\BETTS.rhv Monday,June 03, 2013,2:01 PM
,.'i#�.' � .,4� '��;�r,;`•�- � � "
�;? '•,'A j�.`-'�:�. i':9'..x�. "�?"i ..,.'.,—.,..a:i' a�;i
_',1'4� - Si�f '�i;-
�r, '!W/4'�;'+`��- e�.'
_ i
Load Preview Report —
� Net Rec ftz I gen Lat) Net Sen Sys Sys Sys Duct
Scope � Ton Ton, !T'on' Area� Gain Gain; Gan Loss Htg Clg Act Size
i I , CFM CFM CFM
I i —� -- --
Buildng 2.97 3.62 385 1,392 32,542 3,076 35,618 0 - 0 1,480 1,480 -
System 1 2.97 3.62 385 1,392 32,542 3,076 35,618 0 0 1,480 1,480 34
Duct Laterrt �� ��
Zone 1 1,392 32,542 2,419 34,961 0 0 1,480 1,480 34x
t-Ist Floor 1,392 32,542 2,419 34,961 0 0 1,480 1,480 14–
C:1UsersWaosn\Desktop\ELITE\BETTS.rhv Monday,June 03, 2013,2:01 PM
��,.�'� '�� ".,°�nN .,�`�^sa..'d�,"t�"y��.-��°a� ,,L '�,,�, 'g�� -
��' z��. � ��� � 4
��_ ,�
= d�i����� �� -^ , � �
Tota/Building Summary Loads -�
1 D-hv-o:Glazing-Double pane,operable window, heat- 380 0 0 14,664 14,664
absorbing,vinyl frame, u-value 0.57, SHGC 0.44
11 F: Door-Wood -Solid Core With Metal Storm 21 p � 182 182
13A6-Ofcs:Wall-Block, no blanket or board insulation, 1039 0 0 4,260 4,260
filled core, siding finish
16A-15: Roof/Ceiling-Under Attic with Insulation on Attic 1391.9 0 0 6,368 6,368
Floor(also use for Knee Walls and Partition Ceilings),
Unvented Attic, No Radiant Barrier, Any Roofing
Material,Any Roof Color, R-15 insulation
22C-5rl-t: Floor-Slab on grade, Horizontal board 144 0 i� 0 0
insulation e�ends 4'under slab,tile covering, R-5
insulation, radiant, light dry soil
Subtotals for structure: 0 0 25,474 25,474
People: 2 400 460 860
Equipment: (l 1,200 1,200
Lighting: 0 0 0
Ductwork: 0 657 2,951 3,608
Infiltration:Winter CFM:0, Summer CFM:64 0 2,019 1,408 3,427
Ventilation:Winter CFM:0, Summer CFM:0 0 0 0 0
AED Excursion: 0 0 1,048 1,048
Total Building Load Totals: 0 3,076 32,542 35,618
Total Building Supply CFM: 1,480 CFM Per Square ft.: 1.063 '
Square ft. of Room Area: 1,392 Square ft. Per Ton: 469
Volume (ft3) of Cond. Space:(clg.) 16,703
' Based on area of rooms being heated or cooled (whichever governs system) rather than entire floor area.
Total Sensible Gain: 32,542 Btuh g1 %
Total Latent Gain: 3,076 Btuh g %
Total Cooling Required Including Ventilation Air: 35,618 Btuh 2.97 Tons (Based On Sensible+ Latent)
Rhvac is an ACCA approved Manual J and Manual D computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2,and ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
your design conditions.
C:\UsersWaosn\Desktop\ELITE\BETTS.rhv Monday,June 03, 2013,2:01 PM
,9 s ,�T_' ., , -a' ;�__. - - ' � ' "�`�- ��
,� ^i
° i�¢, ,�#��`c .X4.i � '� �� ',d"h,{^ �
� ar,� s ,.���t- .,��«- :�"�3r�`��a-a��r�.-a��1'�'�M�M
.��'*�, "�a „��r M az-,,r"„�' '�°''�, sri`a. I u�
. _ �� �' � ' #°� �.r�., m��"'�' _,�a�dul��l,�';'�9R:a�r�r���p�m��;�''�.ldii .�I I
System 1 System 1 Summary Loads
1 D-hv-o:Glazing-Double pane, operable window, heat- 380 0 0 14,664 14,664
absorbing,vinyl frame, u-value 0.57, SHGC 0.44
11 F: Door-Wood- Solid Core With Metal Storm 21 0 0 182 1 g2
13AB-Ofcs:Wall-Block, no blanket or board insulation, 1039 0 0 4,260 4,260
filled core,siding finish
16A-15: Roof/Ceiling-Under Attic with Insulation on Attic 1391.9 0 0 6,368 6,368
Floor(also use for Knee Walls and Partition Ceilings),
Unvented Attic, No Radiant Barrier,Any Roofing
Material,Any Roof Color, R-15 insulation
22G5r1-t: Floor-Slab on grade, Horizontal board 144 0 �D 0 0
insulation extends 4'under slab,tile covering, R-5
insulation, radiant, light dry soil
Subtotals for structure: 0 i� 25,474 25,474
People: 2 400 460 860
Equipment: � 1,200 1,200
Lighting: 0 0 0
Ductwork: 0 657 2,951 3,608
Infiltration:Winter CFM:0, Summer CFM:64 0 2,019 1,408 3,427
Ventilation:Winter CFM:0, Summer CFM:0 0 0 0 0
AED Excursion: 0 0 1,048 1,048
System 1 System 1 Load Totals: 0 3,076 32,542 35,618
Supply CFM: 1,480 CFM Per Square ft.: 1.063 "
Square ft. of Room Area: 1,392 Square ft. Per Ton: 469
Volume (ft3) of Cond. Space: (clg.) 16,703
" Based on area of rooms being heated or cooled (whichever governs system) rather than entire floor area.
Total Sensible Gain: 32,542 Btuh g1 %
Total Latent Gain: 3,076 Btuh 9 %
Total Cooling Required Including Ventilation Air: 35,618 Btuh 2.97 Tons(Based On Sensible+ Latent)
Rhvac is an ACCA approved Manual J and Manual D computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
your design conditions.
C:\UsersWaosn\Desktop\ELITE\BETTS.rhv Monday,June 03,2013, 2:01 PM
-�'` ':: -�`� x�� r, ° b`
aY -�� �� �y ���n ss� *� c
� .w` m ��.
System 1, Zone 1 Summary Loads (Average Load Procedure for Rooms) �
1 D-hv-o:Glazing-Double pane, operable window, heat- 380 0 0 14,664 14,664
absorbing,vinyl frame, u-value 0.57, SHGC 0.44
11 F: Door-Wood -Solid Core With Metal Storm 21 0 0 182 182
13A6-Ofcs:Wall-Block, no blanket or board insulation, 1039 0 �D 4,260 4 260
filled core, siding finish �
16A-15: Roof/Ceiling-Under Attic with Insulation on Attic 1391.9 0 i� 6,368 6,368
Floor(also use for Knee Walls and Partition Ceilings),
Unvented Attic, No Radiant Barrier, Any Roofing
Material,Any Roof Color, R-15 insulation
22C-5rl-t: Floor-Slab on grade, Horizontal board 144 0 A 0 0
insulation extends 4'under slab,tile covering, R-5
insulation, radiant, light dry soil
Subtotals for structure: 0 0 25,474 25,474
People: 2 400 460 860
Equipment: 0 1,200 1,200
Lighting: 0 0 0
Ductwork: 0 0 2,951 2,951
Infiltration:Winter CFM:0, Summer CFM:64 0 2,019 1,408 3,427
System 1,Zone 1 Load Totals: 0 2,419 32,542 34,961
Supply CFM: 1,480 CFM Per Square ft.: 1.063 `
Square ft.of Room Area: 1,392 Square ft. Per Ton: 4�g
Volume (ft3) of Cond. Space: (clg.) 16,703
" Based on area of rooms being heated or cooled (whichever governs system) rather than entire floor area.
Total Sensible Gain: 32,542 Btuh g3 %
Total Latent Gain: 2,419 Btuh 7 %
Total Cooling Required: 34,961 Btuh 2.91 Tons(Based On Sensible+ Latent)
Rhvac is an ACCA approved Manual J and Manual D computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2,and ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
your design conditions.
C:\Users�.Jaosn\Desktop\ELITE\BETTS.rhv Monday,June 03,2013, 2:01 PM
, r e; , 3 �, y, ,. � - ��.
a
�'�� "li ,� _��a. �� �����'�� 4��'n ra'.x.,-'s„�.�.
"� �.�+r
Detailed Room Loads - Room 1 - Ist F/oor (Average vLoad Procedure)
Calculation Mode: Clg.only Occurrences: �
Room Length: 42.0 ft. System Number: 1
Room Width: 33.1 ft. Zone Number: �
Area: 1,392.0 sq.ft. Supply Air: 1,480 CFM
Ceiling Height: 12.0 ft. Supply Air Changes: 5.3 AC/hr
Volume: 16,703.0 cu.ft. Req. Vent. Clg: 0 CFM
Number of Registers: 14 Actual Winter Vent.: 0 CFM
Runout Air: 106 CFM Percent of Supply.: p o�a
Runout Duct Size: 8 in. Actual Summer Vent.: 0 CFM
Runout Air Velocity: 303 ft./min. Percent of Supply: 0 %
Runout Air Velocity: 303 ft./min. Actual Winter Infil.: 0 CFM
Actual Loss: 0.040 in.wg./100 ft. Actual Summer Infil.: 64 CFM
N -Wall-13AB-Ofcs 40 X 10 319 0.183 0.0 0 4.1 0 1,308
E -Wall-13AB-Ofcs 32 X 10 270 0.183 0.0 0 4 1 0 1,107
S-Wall-13AB-Ofcs 40 X 10 280 0.183 0.0 0 4..1 0 1,148
W-Wall-13AB-Ofcs 32 X 10 170 0.183 0.0 0 4 1 0 697
N -Door-11 F 3 X 7 21 0.280 0.0 0 8.7 p �82
N -Gls-1 D-hv-o shgc-0.44 100%S 60 0.570 0.0 0 20 6 0 1,238
�2)
E -Gls-1 D-hv-o shgc-0.44 0%S(2) 50 0.570 0.0 0 53.7 0 2,684
S-Gls-1 D-hv-o shgc-0.44 0%S (4) 120 0.570 0.0 0 22.4 0 2,692
W-Gls-1 D-hv-o shgc-0.44 0%S (5) 150 0.570 0.0 0 53.7 0 8,050
UP-Ceil-16A-15 42 X 33.1 1391.9 0.061 0.0 0 4.6 0 6,368
Floor-22C-5rl 144 ft..Per. 144 0.980 0.0 0 0.0 0 0
Subtotals for Structure: 0 0 25,474
Infil.:Win.:0.0, Sum.:64.0 1,440 0.000 0 0.978 2,019 1,408
Ductwork: � 0 2,951
AED Excursion:
People:200 lat/per, 230 sen/per: 2 1,048
400 460
Equipment: 0 1,200
Room Totals: 0 2,419 32,542
C:\UsersWaosn\Desktop\ELITE\BETTS.rhv Monday,June 03, 2013,2:01 PM
DUC�" INSPECTION AND 3EALIl�G CERTIFICATION
��+.�.�.a�.�����.E..�,.co�s.�,. ��i.4.��.z
('f0 BE A'TTACSTD TO AIR HA..�DL�R)
w�eess o��att: ��7 �o �/ /'YI��I�a�L,1 C✓��� � — _ ,
�o.�t�aar���of�y�pmea�: /�-s' 3 / 3� � G'S'.�'f.3 v 3 c, �-
Pamit�Ta: ya-�'
�.,�: a.v� S-��v2 ��L I��J C�
�s: c�c _ ►�r � 92� ��. � � �3
I��►cect�r tb�t t�a�xxt�odc as�oc�ed with tbe HVAC u�i�t nfa+mced bv the pQmit lil�ed sbo��e h�s
b��a�tod aod se�ied is acca�+d�x.rith tbe?A I t}Fla�ida F.ae�y Code.Sectioa I OI r4.6.I.I b}the
Fo�stfo�wbk m�ethod(a): -
� �'hec�e�.all acistia�aud acc�.ssio�e ducts(miai��ut�uf 30 mches aktarxe)bave
bcr' saia�us�in��mastic oa�a code-appetrNed aqaivafmt,
❑ D�ocyc�s 8atad to be loca�ed��in aoaditicoe�sp�oe wrba=fi�tt6er�.iaipaQi,on wd
s�'aoar+e�+a1 {P�cc�iaa 1= Sectian 20�.4.?.I.I}
�j D��a�ic��as impewed at tima a�f i�1 aod w+a fr��d s�t joiots or sea�s�
ah+e�dy xaied s�t sn�pcoVed fabcic aod m�tic. (Facce�on 2,Se�6on lO�.�i.T.1.I}
� 1�e duct sy�uem Fas�es�ed aod�eirs�va�r m�de as n�ceuarv. (F.uept�p4 3,St�ian I014.7.1.I
DuQ syslem tes�ed by Ecompaep�lor isc�ichut)
(�?
�
Pr"��d 1Kaws afd�riio�frtd�Ca�pmry�e,pnrsoetati�r
Rtp�rsa�oait�s's?"rtls:
� �v/3
�� �
�aCA Ta�i�l��I—3JiS�f12
Zi�b.s ar+�ip FS.fOCa.,��as�s��.,��,sc�t.+t.7.u.Fs.1�CC�►1�.�c e.,��ii!r„d
��is e�wwean.Is ���'�K�re�t i�i�D�et����,