Work Desc: A/C CHANGE OUT 2.5 TON 15 SEER
, �
.�
�'n�
. �
� �
, _
DUCTS IN ULA ED
FINAL �- �-��
REINSPECTION FEES: Reinspection fees will comply with Florida Statute 553.80 (2)(c)when extra inspection
trips are necessary due to any one of the following reasons: a)wrong address b) condemned work resulang
from faulty construction c) repairs or corrections not made when inspections called d)work not ready for
inspection when called e) permit not posted on job site t� plans not at job site g) work not accessible.
NOTICE: In addition to the requirements of this permit, there may be additional restrictions applicable to this property that
may be found in the public records of this county, and there may be additional permits required from other governmental
entities such as water management, state agencies or federal agencies.
"Warning to owner: Your failure to record a notice of commencement may result in your paying twice for
improvements to your properly. If you intend to obtain financing,consult with your lender or an attorney
before recording your notice of commencement."
Complete Plans, Specifications Must Accompany Application.All work shall be pertormed in accordance with
Ci Codes and Ordinances. NO OCCUPANCY BEFO C.O.
_,
CON RACTO SIGNATU PERMIT OFFI R
PERMIT EXPIRES IN 6 MONTHS WITHOUT APPROVED INSPECTION
CALL FOR INSPECTION - 8 HOUR NOTICE REQUIRED
PROTECT CARD FROM WEATHER
813-��0°� City of Zephyfiills Permit Application Fax-e��-�eo�oos�
Bufldinp Departrnent
D�b R�plv�d a-(J �--Q��' , }� '� s Q �
�T7-1-T-f7 Phan�CorMaet for P�nnlltln a� _ C�C.t
Own�s N�m� e J Q Q--l.�(}�.J i�� Own�►Phon�NumMr �/J^7�S'�S�-�
Owmrs Addnss �Q,t�C.Q� ' C� (/�- Ownsr Phon�Numb�r ��
FN Eimpl�Titl�hWd�d N� I '— � � Own�►Phon�Nwnb�r
F«aima.r�wnold.f,�dae.,s N � �
�oe,�sa �o�/ 3 L c�.c,c e c � w��,� .� rL �oT r �
SUBDMSION ��-1 Q�..1 U��� PARCEL ID/ ��'�� — � �� O 1 S U -��Q�)O "�/
(OSTANlO rROY PROP6RY TAX N071Cl)
WORK PROP08ED B NEW CONSTR 8 ADDlALT � SIGN Q Q DEMOLISH
INSTALL REPAIR
PROP08ED UEE Q SFR Q COMM Q OTHER
TYPE OF CONSTRUCtiION O BLOCK Q FRAME Q STEEL Q �--,
DESCRIPTION OF WORK �\C C-�'`�"��� O�.>E p7 .,S %Ol�F /S S f P iZ
BUILDINO SIZE SQ FOOTApE�� �Q►� ��
QBUILDINCa S VALUATION OF TOTAL CONSTRUCTION
QELECTR�CqL S AMP SERVICE Q PROGRESS ENERC3Y Q W.R.E.C.
OPIUMBING S
�FAECHANICAL S /'_^n � VALUATION OF MECHANIC/1L INSTALLATION
ltI
QGAS Q ROOFING Q SPECIALTY Q OTHER
FINISHED PLOOR EI�VATIONS FLOOD ZONE AREA QYES NO
BULLDER COMPANY �
a��A�� REGISTERED Y/ N FEE Cl� Y I N
�d�� LICMIE!#
ELECTRICIAN � CONPANY
$���TV� REGISTERED Y/ N FEE CURNB� Y/N
Addr�ss License#
PLUNBER �p�y --�
$���TU� REGISTERED Y!N FEE cuRAEn Y/N
Addnss Llcsnae#��
MECHApICAL �p�y,�y ��D S e���.C t S —,
a���TV� REGISTERED Y/N FEE CUitREI. Y I N
�aar... loC3c� Jv.,�F- �a.�- �a t31� u�«,se# C�-l�I(.o a l
onieR coMP�wr
$����� REGISTEREO Y/N FEE cu�n Y/N
Add►�st License if
IIIIIIIIIMIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIItilllll
RESIDENTIAL Attech(2)plot Plarro;(2)ssta d Building Plana;(1)set of Enapy Fams;R-Q�W PermR for new ccnstrucnon,
MlMmum ten(10)wottdng deya eRer suhmitfnl date. Requlrod ornite,Constructlon p�ans,Stamwater Plans w/Sllt Fence Insfalled,
S�anitery FacWtles 8 1 dumpster;Site Work Permk for wbdMsionsAetge p�oJeus
COMMERCIAL A�fech(3)complste ssb of BuiWiny Plans plus a Lite Sefety Peps:(1)ast oi F.nsrgy Forms.R-O-W Permit for nsw corqtrucyon.
Minimum ten(10)rwrldnp days alter submiltal date. Requked msile,Cons6ud3on Plens,Stamvwtx Plens wl SiR Fence installed,
Sankary Fadlitlst 51 dumpste►.Site Wa1c Permk for all new projecb.All aommert�sl requiremerrts must mest compliance
SION PgtMR Abhch(2)ssb ot Enpineerad plans.
"�"PROPERTY 3URVEY reqWnrd for aN NEYV cpnsbudfon.
' Ili • 11 1 � 1 lii 11 � 14..........�111 Ill.ii
DIP�CtlOflt.•
FlII out applipti�n carnplstely.
Ownsr�C.ontrBetar eign badc of applicedon,tiotuizsd
M owr{2500,�Notia oi ComrMnamait Is nqulnd. rMC uppnda mn►i7500)
" Agent(tor 1he cb�fVSCtor)a Power oi Attaney(for the owner)waild ba someone with nofarized lettx irom owner wtlwribng seme
OVER THE WUtIT'ER PERMITTINO (Front af Appllcatlon pn�y)
Rerooh K shkiglss Sewera Serviee Upgrades A!C Fences(Pbt/Survey/footage)
Drhr�s-Wo�over CouMer N on publie roadways..needs ROW
NOTICE OF DEED RESTRICTIONS: The undersigned understands that this pertnit may be subjed to'deed"restrictions"
which may be moro reatrictive than County rogulations. The undersigned assumes responsibility for compliance w�h any
applicable daed restrfdfons.
UNUCENSED CONTRACTORS AND CONTRACTOR RESPON8IBIUTIE3: If the owner has hired a contrac�or or
contractas to undertake woric,they may be required to be Ifcansed in accar�dance with state and local regulatlons. If the
conhactor is nat licensed as required by law, both the owner and c�ntrador may ba dtad for a misdemeanor violaUon
under state law. If the owner or intended contractor are uncatain as to what licensi�g requfremerrts may appiy for the
intended work,they are advised to contact the Pasco County Building Inspectlon Divlsion--Lic�nsing Section at 727-847-
8009. Furthertnore, if the owner has hired a contrador or oontrsdors, he is advised to have the contrec�or(s) sign
portions of the"contractor Block'of this application for which they will be responsible. If you,as the owner sign as the
oontractor,that may be an indication that he is not proparly licensed and Is not antltled to pertniKing privileges in Pasco
CouMy.
TRANSPORTATION IMPACTNTILITIES IMPACT AND RESOURCE RECOVERY FEES: The undersigned understands
that Transportatlon Imped Fees and Reoourse Reoovery Fees may apply to the oonstrudion of naw buildings,change of
use in epstlng buildings,or expansion of existlng buildings,as specified in Pasco County Ordinance number 89-07 and
90-07,as ame�ded. The undersigned also understands,Uiat such fees,as may be due,witl be identlfled at the Bme of
partnitting. It is further understood that Transportatlon Impad Faes and Resource Reoovery Fees must be paid prior to
receNing a'certificate of occupancy or 8nal power releasa. If the project does not invdve a certlficate of occupancy or
final power release,the feas muat be paid prior to parmft issuance. Furthertnoro, H Pasco County WateNSewer Impact
fees aro due,they must be paid prior to pertnit issuance in accordance wiTh applicabb Pasco County ordinances.
CONSTRUCTION LIEN LAW(Chapbr 713,Florida Statutss,as amsnd�: If valuaUon oi work is 52,500.00�more,I
certHy that I, the appl�arrt, have been provided with a copy of the 'Florida Constructlon Lien Law—Homeowner's
Protection Guide"prepared by the Florida Department of/�riculture and Consumer Af(airs. If the applicant is someone
other than the"owner,I certify that 1 have obtained a copy ot the above described document and promise in good faith to
deliver it to the'owner ptior to«�mmmencement
CONTRACTOR'S/OWNER'S AFFIDAVIT. I certify that all the information in this application is accurate and that all work
will be done in compliance with ail applicable laws regulatlng construction,zoning and land development Application is
hereby made to obtaM e pertnit to do wa�k and installation as indicated. I c�ertify that no work or insta�lati�on has
oommenced prior to issuance of a partnit and that all worlc will be pertormed to meet standards of all laws regulatlng
construction, County and City oodes, zoning regulatlons, and land davelopment rogulaUona in the jurisdidio�. I also
cerdfy that I underatand that the regulatlons of other govemment agencies may apply to the iMended work,and that it is
my responsibility to identify what actions I must taka to be in compliance. Such agandes indude but are not IimRed to:
- Departrnent of EnvironmeMal Protection-Cypress Bayheads, WeUand Areas and Environmentally Sensitive
Lands,WaterJWastewater Treatment.
- Southwest Florida Water Management Distrid-Welis, Cypress Bayh�ds, WeUand Areas, Aftering
Watercourses.
- Army Gorps of Engineers-Seawalis,Docks,Navigable Waterways.
- Department of Health 8 Rehabilitative Services/Environmental Health Unit-Wells, Wastewater Treatment,
Septic Tanks.
- US Environmental Protectfon Agency-Asbestos abatement.
- Federai Aviatlon Authority-Runways.
I understand tt�at the following reatrictions apply to the use of fill:
- Use of flll is not allowad in Flood Zone'V'unless expressly pertnitted.
- If the flll material is to be used in Flood Zone 'A', R is understood tfiat a drainage plan addressing a
"cwmpensating volume'wfll be submitted at time of pertnkting which is prepared by a professfonal engineer
licensed by the State oi Florida.
- If the fill material is to be used in Fbod Zone "A' in connecdon with a permitted building using stem wall
oonstruction,I oertify that flll wiil be used anly to fill the area within the stem well.
- If fill material is to be used in any area, I certHy that use of such flll will not adversely affect adjacent
Properties. If use of flll is found to adversely affect adjac�ent properdes,the owner may be dted for violatlng
the conditions of the building permit issued under the atteched pertnit applicatlon,for lots bss than one(1)
acre which are elevated by flll,an engineered drainage plan is required.
If I am the A(iENT FOR THE OWNER,I promise in good faith to inform the owner of the permitting conditi�ons set forth in
this affidavit prior to commenang construction. I understand that a separate permit may be roqulred for electrk�l work,
plumbing, signs, welis, pools, air conditloning, gas, or other installations not specHically induded in the application. A
permit issued shall be consWed to be a license to proceed with the wak and not as authorily to violate,cancel,alter,or
set aside any provisions of the technical codas,nor shall iasuanoe of a pertnit prevent the Building Ofticial irom tl�ereafter
requiring a correction of erro►s in plans,construction or violatlons of any codes. Every permk issued shall become invalid
unless the work authoraed by such permit is commenced wffhin six months of pertnit issuance,or if work auttwraed by
the permit is suspended or abandoned for a periad of sbc(6)months after the time the work is commenc�d. M extension
may be requested, in writlng,irom fhe Building OAtaal for a period not to exceed ninety(90)days and will demonstrate
justifieble cause for the extension. If work oeases for ninety(90)consecutive days,the job is considered abandoned.
WARNING TO OWNER: YOUR FAILURE TO RECORD A NOTICE OF COMMENCEMENT MAY RESULT IN YOUR
PAYINIi 71MCE FOR IMPROVEMENTS TO YOUR PROPERTY. IF YOU INTEND TO OBT N FINANGNO,CON8ULT
FLORIDA JURAT(F.S.117.03)
ONMER OR AOENT Cp��T
Sub�albsd end swom to(or afirm�d)bsforo ma this snd fo ar alNrmed) ms
Who la/aro psiaondly known to me a ha�lhaw produced V�ifonallv known to ms or hWhaw produosd
as ideMlflcatlon. as IdentMcetlon.
N�Y�� Notary Pudic
Commission No. Commission No.__ � Z��P LP�J l7
tv��+cc,..��l Se�.�a,.X
Nema of Notary tYPed�P�ad a�P� Nams of Ndery tYP�d�Prinfsd e►
gti►�"� Notary PuWic SWfe of Florida
Mary V Stewart
� My Commission EE 216630
'4"�p� Expires 07/18/2016
,�,.__�. y ., . b .
��� ����� � ��4�� �r��������
A���i iy�s�+i!l�li��►���MMt�IM�i�:
{TO fE ATT�C�TQ Ai��L�} `�� R��`
� �. � �a�
��:.
�.. .. _ .. ; ,. �.���:.
::��_„
�� ��� a � it/ -c' ��,:;,.;,�
Y-`�
�, - ��.. � � � � l3 < .�y;
�� � _ �N
� .� r.■r�:+�.:
_ . r�.,
�� �'� ���cYj�� � -
x.i�l��M, ����� t� / � Dre T�r��. (.� Z�� �6 /3 "�
_.____--
�..��
Il�i� �iAt#ri■e�ai�rad�l�d�'�►�6e HYAdC�it�roM b!►is��it lrMi�lo�e i� ,:> ��;�
�a �i��i�a�+�i�■�w�t i s�O 1 Q�l a e i i e�r C r o i R S�o�i o a 2�1�4�.6�.I.��i s
� ���� =
� �i�s�r��•�ciMi■s a�d aa�r`3b�is aoos(�i.ii■rs a[3o i�s ol�.*.y�.�.
� x�i��ies r�i�6a�o�d s�ti�a a ood��#�pevwd�■i�aLec
� ���d b�t b�'��%�l CO�;r��Ot 71�t����d
��i��otsq�is�� (�'�o01,Se�sion 103.4.7.1.1�
� D�odcw�s i�i arti�s e[ir�il adi w i�t i�t3�i■�s ac ss�s
�1��►s�d�Y t��dl�ejc�■d sr�ic �Si�ptio�2.S�4io� I0111.7.I.1�
� ZI�s iet s�a w�t�w�dad w�ies we�e a�s�s a�o�. �3�S�eliol�(t41�4�.7.1.1
1l�pt�llr i�d b�{eoa��q►a�ot'mr��d�.i)
�)_.
�a�aMAK
���Y?�d�
�
.�C� 2� 13
������ k§".��'?r'"f�' :c;.T: �� i
��'�� r.� .i �'�i�sw�����
� . . - �'� �rrr�►�si►#�laiii�tl�rli■�a���
� ,�:;"_ ;,.. ,.
r�� -���� .
. .ti�...:.•.��. ��tx� �
�:�__.�..-�. .
1��•::;,'
�^ � .�,.,,�3 .
� _ :�>-_,e .
� ,���#�.' �
Orlando Residence
HVAC Load Calculations
for
Kenneth Orlando
6413 Lauren Wood Drive
Zephyrhiils, FI 33542
����� HVAG O�
Prepared By:
Blake Lanier
And Services
6008 JETPORT INDUSTRIAL BLVD
TAMPA, FL, 33634
813-445-4818
Wednesday,June 26, 2013
Rhvac is an ACCA approved Manual J and Manual D computer program.
Calculations are pertormed per ACCA Manual J 8th Edition,Version 2, and ACCA Manual D.
.. . _.. �S H� �IM�n Drv�bp�a��+a:
Orlenda!�
Pro'ect Re ort
Project Title: Orlando Residence
Designed By: Blake Lanier
Project Date: June 26th 2013
Client Name: Kenneth Oriando
Client Address: 6413 Lauren Wood Drive
Client City: Zephyrhills, FI 33542
Client Phone: 813-715-1521
Company Name: And Services
Company Representative: Blake Lanier
Company Address: 6008 JETPORT INDUSTRIAL BLVD
Company City: TAMPA, FL,33634
Company Phone: 813-445-4818
Company E-Mail Address: OFFICE�,DCOMFORTISCOOL.COM
Company Website: WWW.COMFORTISCOOL.COM
Reference Ciry: Tampa, Florida
Building Orientation: Front door faces Southeast
Daily Temperature Range: Medium
Latitude: 28 Degrees
Elevation: 19 ft.
Altitude Factor: 0.999
Elevation Sensible Adj. Factor: 1.000
Elevation Total Adj. Factor: 1.000
Elevation Heating Adj. Factor: 1.000
Elevation Heating Adj. Factor: 1.000
Outdoor Outdoor Outdoor Indoor Indoor Grains
Dry Bulb Wet Bulb Rel.Hum Rel.Hum �Bulb i f
Winter: 40 37.52 80°/a n/a 70 n/a
Summer: 95 77 45% 50% 75 46
Total Building Supply CFM: 1,122 CFM Per Square ft.: 0.895 "
Square ft.of Room Area: 1,254 Square ft. Per Ton: 509
Volume(ft3)of Cond. Space:(clg.) 10,035
* Based on area of rooms being heated or cooled(whichever governs system) rather than entire floor area.
Total Sensible Gain: 26,210 Btuh 89 %
Total Latent Gain: 3,339 Btuh 11 %
Total Cooling Required Including Ventilation Air: 29,550 Btuh 2.46 Tons(Based On Sensible+Latent)
�
Rhvac is an ACCA approved Manual J and Manual D computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2,and ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
your design conditions.
C:\UsersWaosn\Desktop\ELITEWCEVEDO.rhv Wednesday,June 26,2013,8:34 AM
�.. . , . . . E�s 8oilwr��v�Nop��.lnc.
, , ,.. . ;� ��
Miscellaneous Re ort
" "� €�1c�or � Ic�Oar � �
� 1i�;'� F�:i�t Rei.#� 8�b D�
Winter: 40 37.52 80% n/a 70 n/a
Summer: 95 77 45°/a 50% 75 46.41
D�t'
Main Trunk Runouts
Calculate: Yes Yes
Use Schedule: Yes Yes
Roughness Factor: 0.00300 0.01000
Pressure Drop: 0.1000 in.wg./100 ft. 0.1000 in.wg./100 ft.
Minimum Velocity: 650 ft./min 450 ft./min
Ma�dmum Velocity: 900 ft./min 750 ft./min
Minimum Height: 8 in. 8 in.
Ma�dmum Height: 8 in, g in,
,�x.
Win r Summer
Infiltration Specified: 0.000 AC/hr 0.230 AC/hr
0 CFM 38 CFM
Infiltration Actual: 0.000 AC/hr 0.000 AC/hr
Above Grade Volume: X� Cu.ft. X 10.035 Cu.ft.
0 Cu.ft./hr 0 Cu.ft./hr
X . 1 7 X 0•0167
Total Building Infiltration: 0 CFM 0 CFM
Total Building Ventilation: 0 CFM 70 CFM
---System 1---
Infiltration&Ventilation Sensible Gain Multiplier: 21.98 = (1.10 X 0.999 X 20.00 Summer Temp. Difference)
Infiltration&Ventilation Latent Gain Multiplier: 31.54 = (0.68 X 0.999 X 46.41 Grains Difference)
Infiltration &Ventilation Sensible Loss Multiplier: 32.98 = (1.10 X 0.999 X 30.00 Winter Temp. Difference)
Winter Infiltration Specified: 0.000 AC/hr(0 CFM),Construction:Average
Summer Infiltration Spec'rfied: 0.230 AC/hr(38 CFM), Construction:Average
�' �7�r 1
l� twd D�td Stt�fsE�a F�m
A1�r: '� ' �:�n k�ut�ic�t Area (�i
1 Supply Main Attic 16B 0.12 6 112 No
1 Return Main Attic 16B 0.24 6 112 No
C:\Users�.laosn\Desktop\ELITE�ACEVEDO.rhv Wednesday,June 26,2013,8:34 AM
�.,. ' 'f�4�NYC�:',t.ords �9�o�Na+e qwNop�_M�c.
�, . ,;::;.. �; �� O�lendo R�
a
Load Preview Re ort
Net Rec ft2 Sen Lat Net Sen H=s S�ys A� �
Scope Ton Ton /Tor► Area Gain Gain Gain �oss CFM CFM CFM Size
Building 2.46 291 431 1,254 26,210 3,3� 29,560 0 0 1,122 1,122
System 1 2.46 2.91 431 1,254 26,210 3,339 29,550 0 0 1,122 1,122 26
Verdilation 1,539 2,208 3,747 0
Duct LateM 732 732
Zo�� 1,254 24,671 400 25,071 0 0 1,122 1,122 26
1-Ist Floor 1,254 24,671 400 25,071 0 0 1,122 1,172 11—
C:\Users�,laosn\Desktop\ELITEWCEVEDO.rhv Wednesday,June 26,2013,8:34 AM
�'wf . , , . . '#.ww�s ����wr��A�,y� alw�.
��r,� �, �� �.w�waV�
Total Buildin Summar Loads
A�ea sen l�t 3en Tt#�
I � f,�t�ut l� C,e�r+ C3�'t �n
1 C-cm:Glazing-Single pane window with storm, clear, 133 0 0 10,272 10,272
metal frame no break,u-value 0.87,SHGC 0.67
11 F: Door-Wood -Solid Core With Metal Storm 21 0 0 182 182
13AB-Ofcs:Wall-Block, no blanket or board insulation, 998 0 0 4,090 4,090
filled core,siding finish
16A-19: Roof/Ceiling-Under Attic with Insulation on Attic 1254.4 0 0 4,610 4,610
Floor(also use for Knee Walls and Partition Ceilings),
Unvented Attic, No Radiant Barrier,Any Roofing
Material,Any Roof Color, R-19 insulation
FLOOR ON SLAB: Floor-Over open crawl space or 1254.4 0 0 621 621
garage,Custom, FLOOR ON THE SLAB
Subtotals for structure: 0 0 19,775 19,775
People: 2 400 460 860
Equipment: 0 1,200 1,200
Lighting: 70 239 239
Ductwork: 0 732 2,998 3,729
Infiltration:Winter CFM:0,Summer CFM:0 0 0 0 0
Ventilation:Winter CFM:0, Summer CFM:70 0 2,208 1,539 3,747
Total Building Load Totals: 0 3,339 26,210 29,550
f�+`I8� .
Total Building Supply CFM: 1,122 CFM Per Square ft.: 0.895 *
Square ft. of Room Area: 1,254 Square ft. Per Ton: 509
Volume(ft3)of Cond. Space:(clg.) 10,035
* Based on area of rooms being heated or coofed(whichever governs system) rather than entire floor area.
Total Sensible Gain: 26,210 Btuh 89 °/a
Total Latent Gain: 3,339 Btuh 11 %
Total Cooling Required Including Ventilation Air: 29,550 Btuh 2.46 Tons(Based On Sensible+ Latent)
NO�
Rhvac is an ACCA approved Manual J and Manual D computer program.
Calculations are performed per ACCA Manual J 8th Edition,Version 2, and ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
your design conditions.
C:\UsersWaosn\Desktop\ELITEWCEVEDO.rhv Wednesday,June 26,2013,8:34 AM
� _ _ . . �.i:iil�Yl� ��w1��i�N�ie�
- �
, , , -�
S stem 1 S stem i Summa Loads
l�, S�en L� S� T�eF
� t�+ F�eiln �n C�in
1 C-cm:Glazing-Single pane window with storm, clear, 133 0 0 10,272 10,272
metal frame no break,u-value 0.87,SHGC 0.67
11 F: Door-Wood-Solid Core With Metal Storm 21 0 0 182 182
13AB-Ofcs:Wall-Block, no blanket or board insulation, 998 0 0 4,090 4,090
filled core, siding finish
16A-19: Roof/Ceiling-Under Attic with Insulation on Attic 1254.4 0 0 4,610 4,610
Floor(also use for Knee Walls and Partition Ceilings),
Unvented Attic, No Radiant Barrier,Any Roofing
Material,Any Roof Color, R-19 insulation
FLOOR ON SLAB: Floor-Over open crawl space or 1254.4 0 0 621 621
garage,Custom, FLOOR ON THE SLAB
Subtotals for structure: 0 0 19,775 19,775
People: 2 400 460 860
Equipment: 0 1,200 1,200
Lighting: 70 239 239
Ductwork: 0 732 2,998 3,729
Infiltration:Winter CFM:0, Summer CFM:0 0 0 0 0
Ventilation:Winter CFM:0,Summer CFM:70 0 2,208 1,539 3,747
System 1 System 1 Load Totals: 0 3,339 26,210 29,550
CM��tC
Supply CFM: 1,122 CFM Per Square ft.: 0.895 '
Square ft. of Room Area: 1,254 Square ft. Per Ton: 509
Volume(ft3)of Cond. Space: (clg.) 10,035
` Based on area of rooms being heated or cooled (whichever governs system) rather than entire floor area.
LA� ;
Total Sensible Gain: 26,210 Btuh 89 %
Total Latent Gain: 3,339 Btuh 11 %
Total Cooling Required Including Ventilation Air: 29,550 Btuh 2.46 Tons(Based On Sensible+ Latent)
WOt+�
Rhvac is an ACCA approved Manual J and Manual D computer program.
Calculations are pertormed per ACCA Manual J 8th Edition, Version 2,and ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's pertormance data at
your design conditions.
C:\Users�.laosn\Desktop\ELITEWCEVEDO.rhv Wednesday,June 26,2013, 8:34 AM
�=�_:. , . � EAM�Safiw�n��#no.
'�'` ,:� �. _ � �
S stem 1, Zone 1 Summar Loads Avera e Load Procedure for Rooms
� �ea S�i l� sen '�o�
.,:,_ .. Qf�au� l.�s �h E�in t�n
1 C-cm:Glazing-Single pane window with storm, clear, 133 0 0 10,272 10,272
metal frame no break,u-value 0.87, SHGC 0.67
11 F: Door-Wood- Solid Core With Metal Storm 21 0 0 182 182
13AB-Ofcs:Wall-Block, no blanket or board insulation, 998 0 0 4,090 4,090
filled core,siding finish
16A-19: Roof/Ceiling-Under Attic with Insulation on Attic 1254.4 0 0 4,610 4,610
Floor(also use for Knee Walls and Partition Ceilings),
Unvented Attic, No Radiant Barrier,Any Roofing
Material,Any Roof Color, R-19 insulation
FLOOR ON SLAB: Floor-Over open crawl space or 1254.4 0 0 621 621
garage, Custom, FLOOR ON THE SLAB
Subtotals for structure: 0 0 19,775 19,775
People: 2 400 460 860
Equipment: 0 1,200 1,200
Lighting: 70 239 239
Ductwork: 0 0 2,998 2,998
Infiltration:Winter CFM:0, Summer CFM:0 0 0 0 0
System 1,Zone 1 Load Totals: 0 400 24,671 25,071
Che�t
Supply CFM: 1,122 CFM Per Square ft.: 0.895 `
Square ft. of Room Area: 1,254 Square ft. Per Ton: 600
Volume(ft3) of Cond. Space:(clg.) 10,035
* Based on area of rooms being heated or cooled (whichever governs system) rather than entire floor area.
zc��� �
Total Sensible Gain: 24,671 Btuh 98 %
Total Latent Gain: 400 Btuh 2 %
Total Cooling Required: 25,071 Btuh 2.09 Tons(Based On Sensible+ Latent)
N�tas
Rhvac is an ACCA approved Manual J and Manual D computer program.
Calculations are performed per ACCA Manual J 8th Edition,Version 2,and ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
your design conditions.
C:\UsersUaosn\Desktop\ELITEWCEVEDO.rhv Wednesday,June 26,2013, 8:34 AM
�c+� #�,#�'�: s� �M�otlwr�n�h�.
�aC. Ofindo R�o�l
� .: ::-, , ; _ P, 8
Detailed Room Loads - Room 1 - !st F/oor Avera e Load Procedure
Calculation Mode: Clg.only Occurrences: 1
Room Length: 39.2 ft. System Number: 1
Room Width: 32.0 ft. Zone Number: 1
Area: 1,254.0 sq.ft. SupplyAir: 1,122 CFM
Ceiling Height: 8.0 ft. Supply Air Changes: 6.7 AC/hr
Volume: 10,035.0 cu.ft. Req. Vent. Clg: 70 CFM
Number of Registers: 11 Actual Winter Vent.: 0 CFM
Runout Air: 102 CFM Percent of Supply.: 0 %
Runout Duct Size: 8 in. Actual Summer Vent.: 70 CFM
Runout Air Velocity: 292 ft./min. Percent of Supply: 6 %
Runout Air Velocity: 292 ft./min. Actual Winter Infil.: 0 CFM
Actual Loss: 0.038 in.wg./100 ft. Actual Summer Infil.: 0 CFM
�m ; �ea -U-
�" Vs� HT11rl Lass � Gaint C,�tn
N -Wall-13AB-Ofcs 40 X 8 287 0.183 0.0 0 4.1 0 1,176
E-Wall-13AB-Ofcs 32 X 8 195 0.183 0.0 0 4.1 0 799
S-Wall-13AB-Ofcs 40 X 8 320 0.183 0.0 0 4.1 0 1,312
W-Wall-13AB-Ofcs 32 X 8 196 0.183 0.0 0 4.1 0 803
N -Door-11 F 3 X 7 21 0.280 0.0 0 8.7 0 182
N -Gls-1 C-cro shgc-0.67 100%S 12 0.870 0.0 0 31.4 0 377
E-Gls-1 C-cro shgc-0.67 0%S 25 0.870 0.0 0 81.8 0 2,045
E-Gls-1 C-cro shgc-0.67 0%S 36 0.870 0.0 0 81.8 0 2,944
W-Gls-1 C-cro shgc-0.67 0%S(2) 60 0.870 0.0 0 81.8 0 4,906
UP-Ceil-16A-19 39.2 X 32 1254.4 0.049 0.0 0 3.7 0 4,610
Floor-FLOOR ON SLAB 32 X 39.2 1254.4 0.033 0.0 0 0.5 0 621
Subtotals for Structure: 0 0 19,775
Infil.:Win.:0.0, Sum.:0.0 1,152 0.000 0 0.000 0 0
Ductwork: 0 2,998
People:200 IaUper,230 sen/per: 2 400 460
Equipment: 0 1,200
Lighting: 70 239
Room Totals: 0 400 24,671
C:\UsersWaosn\Desktop\ELITEWCEVEDO.rhv Wednesday,June 26,2013,8:34 AM
� This combination qualifies for a Federal Energy
' Efficiency Tax Credit when placed in service
between Feb 17,2009 and Dec 31,2013.
Certificate of Product Ratin s
AHRI Certified Reference Number: 5722633 Date: 6/26/2013
Product: Split System: Heat Pump with Remote Outdoor Unit-Air-Source
Outdoor Unit Model Number:ASZ140301A*
Indoor Unit Model Number: ASPT36C14A'
Manufacturer: AMANA HEATING AND AIR CONDITIONING
TradelBrand name: ASZ14 SERIES
Manufacturer responsible for the rating of this system combination is AMANA HEATING AND AIR
CONDITIONING
Rated as follows in accordance with AHRI Standard 210/240-2008 for Unitary Air-Conditioning and Air-Source
Heat Pump Equipment and subject to veri�cation of rating accuracy by AHRI-sponsored, independent,third
party testing:
Cooling Capacity(Btuh): 28000
EER Rating (Cooling): 12.50
SEER Rating(Cooling): 15.00
Heating Capacity(Btuh)@ 47 F: 27000
Region IV HSPF Rating (Heating): 8.50
Heating Capacity(Btuh)@ 17 F: 15600
'RaGngs followed by an asterisk(•)indicate a voluntary rerate of previously published dala,unless accompanied with a WAS,which indicates an involuntary rerate.
DISCLAIMER
AHRI does not endorse the product(s)Gsted on this Certifieate and makes no represeMaUons,wama�Mies or guararhees as to,and assumes no responsibility for,
the product(s)listed on thia CeAfNcate.AHRI expresaly dlsclalms all BabI1Hy for damages of any kind arising out of the uae or pertortnanee of the product(s�,or the
unauthorized akeration of data Ilated on this Certlflcate.CertHkd ratings are valld only for modela and co�lgurations listed in the directory at wNrW,ahridirectory.org.
TERMS AND CONDITIONS
This Certlflcate and ks coMeMs are proprietary products of AHRI.This Cerfificate shall only be used fpr indNidual,personal and confideMial reference purposes.
The coirterNs of this CerliRcate may not,in whole or In part,be reproduced;copied;disseminated;entered into s eomputer database;or Wherwise utl�ized,in any
fortn or manner or by any means,except fo►the user'a individual,peraonal and confldeMial referenee.
CERTIFICATE VERIFICATION � ��'
The information for the model cited on this certifieate can be verified at www.ahridirectory.org, Air-Conditioning,Heating,
cllck on'Nerify Certificate"link and errter the AHRI Certlfied Reference Number and the date on A. ■■-'
whieh the cerfificate was issued,whkh is listed above,and the Certlffeate No.,whieh is listed bebw. and R@}�IgA�qfiO�In5?ItUf@
�02013 Air-Conditioning,Heating,and Refrigeration Institute CERTIFICATE NO.: 130167206875454660