<br /> DF-52416:D•A3-20
<br /> � MS-5UD(E)/MS-10UD(E) Series �� FII'E�•LITe°ALarf"Y1S
<br /> � -
<br /> F�ve Zone F�re Alarm Control Panel ,
<br /> Ten Zone Fire Alarm Control Panel by Honeywell �
<br /> �-f:x 3� �,na,.. T-�� :.�-�����'' ' �*i�- ,� * :t..,.,,..,'d 7 -.:: -�.x.;,�
<br /> _ -'t -4(:__��;'A"�'"� , � ... � .
<br /> ... ��',_,,:�R::�_�:..ii=:_°:.�,�-?*-.S:7L:....
<br /> General �
<br /> The MS-5UD-3(E) is a five-zone FACP (Fire Alarm Control
<br /> Panel)and the MS-10UD-7(E)is a ten-zone FACP.These con-
<br /> trol panels provide reliable fire signaling protection for small to
<br /> medium-sized commercial, industrial, and institutional build- �
<br /> ings. Both panels include built-in communicators for Central
<br /> Station Service and remote upload/download. :.;,-,;, ,;,- -<,;
<br /> �� 4 _;,�?,..: ;�..:,;;, ��,•:�:5;=:.,; ,. . .
<br /> Each of these FACPs is compatible with System Sensor's `� ��i���` � �••'� "'i t"� .�����'�' `:Y�`
<br /> � �,�':�`�`� �';�;::;y,,;.__�:;;:-�
<br /> �-'�.�.,, .
<br /> microprocessor-based i3 series detectors.These conventional �• -� �°°��-•=�';���=':��
<br /> - �_r,�:; �.Y.,
<br /> smoke detectors can transmit a maintenance trouble signal to x � �;:�t
<br /> ��•.:
<br /> the FACP indiqating the need for cleaning and a supervisory � ^ ����� " �:��
<br /> "freeze°si nal when ihe ambient tem erature falls below the �'�:`���",
<br /> 9 P ► ;;:��-�:�
<br /> detector rating. Additionally, both the MS-5UD-3 and MS- _;;r�'�+�{
<br /> 10UD-7 are compatible with conventional input devices such �, �;���'�=
<br /> r�{
<br /> as two-and four-wire smoke detectors,puil stations,watertlow n�+ -;t�:�
<br /> devices, tamper switches, and other normaliy-open contact s`u;`��::� a
<br /> devices. Refer to the Fire•Lite Device Compatibility Document `� ���� �
<br /> for a complete listing of compatible devices.
<br /> Outputs include four NACs (Notification Appliance Circuits), "
<br /> i three programmable Form-C relays (factory programmed for
<br /> Alarm,Trouble;and Supervisory)and 24 VDC special applica- '
<br /> tion resettable and nonresettable power outputs. The FACPs ,
<br /> supervise all v�iring, AC voltage, battery level and telephone _Strobe Synchronization for System Sensor, Wheelock,
<br /> line integriry.
<br /> Gentex,Faraday,or Amseco devices.
<br /> Activation of a compatible smoke detector or any normally- _Selective Silence(horn-strobe mute).
<br /> open fire alarm initiating device will activate audible and visual
<br /> signaling deviGes, iliuminate an indicating LED, sound the —Temporal or Steady Signal.
<br /> piezo sounder'at the FACP, activate the communicator and —Silenceable or Nonsilenceable.
<br /> FACP alarm relay, and operate an optional module used to . Optional CAC-5X Style Z (Class A) Converter Module for
<br /> notify a remote station or initiate an auxiliary control function. NACs and IDCs(2 required for MS-10UD-7).
<br /> New options include a UL listed printer,PRN-6F and FireLite's • Form-C Relays for Alarm, Trouble and Supervisory- Con-
<br /> IPDACT Internet Monitoring module. The FireWatch Series tact Ratings 2.0 A@ 30 VDC or 0.5 A Q 30 VAC(resistive).
<br /> internet monitoring modules IPDACT-2 and IPDACT2UD per- . 3.0 A total system current for MS-5UD-3.
<br /> mit monitoring;of alarm signals over the Intemet saving the � �.0 A total system current for MS-10UD-7.
<br /> monthly cost o�two telephone lines.Although not required,the
<br /> secondary telephone line may be retained providing backup • Optional Dress Panel DP-51050
<br /> communication over the public switched telephone line. • Optional Trim Ring TR-CE for semi-flush mounting.
<br /> NOTE:The MS-5UD-3E and MS-10UD-7E offers ihe same fea- • 24 volt operation.
<br />� tures as the M$-5UD-3 and MS-f0UD-7 but allow connection to . Low AC voltage sense.
<br /> 240 UAC. Unless othenvise specified, the information in this data Alarm Verification.
<br /> sheet applies to both the i20 UAC and the 240 1/AC versions of � �
<br /> these panels. ?� • PAS(Positive Alarm Sequence).
<br /> NOTE:For ULC-listed models,see DF-60440. • Automatic battery trickle charger.
<br /> , • Up to eight ANN-BUS annunciators:
<br /> F@atUl'eS —Optional 8 zone Relay Module ANN-RLY.
<br /> • Listed to UL Standard 864,9th edition. —Optional LED Annunciator Module ANIV-LED,
<br /> • Built-in DACT(Digital Alarm Communicator/Transmitter). —Optional Remote Annunciator ANN-8Q.
<br /> • Style B(Cla;ss B)IDC(Initiating Device Circuit) —Optional Remote Printer Gateway ANN-S/PG.
<br /> —MS-5UD-3-five IDCs. —Optional LED Annunciator Driver ANN-1/O.
<br /> —MS-10UD=7-ten IDCs. • Optional 4XTMF module (conventional'reverse polarity/city
<br /> • Style Y(Cla�s B)NAC(Notification Appliance Circuit)-spe- box transmitter).
<br /> cial application power PROGRAMMING AND SOPTWARE: :
<br /> —MS-5UD-3-four NACs. • Can be programmed at the panel with no special software
<br /> —MS-10UD?7-four NACs. or additional equipment. -
<br /> • Notification Appliances may be programmed as • Programmable Make/Break Ratio.
<br /> —Silence Inhibit. Uplo d/Download(local or remote)of program and data via
<br /> —Auto-Silence. r inte DA¢�
<br /> ,�.,�����; ,��,�e,�
<br /> I �
<br /> i,�'�"'����'+ ����E��'��.������f� � DF-52416:D•07/26/2010—Page1 of4
<br /> �.��ati ��T`�1�;'+�n��6�'G,�-.E._l.�l.�-- --�--
<br />�