Laserfiche WebLink
Rhvac-Residential&Light Commercial HVAC Loads � Elite Software Development,Inc. <br /> Calcs-Plus � Suzin Nails And Spa <br /> North Venice,FL 34275 Pa e 4 <br /> Total Building Summary Loads � <br /> Component I Area Sen Lat Sen Total <br /> Descri tion i Quan Loss Gain Gain Gain <br /> 1B-cm: Glazing-Single pane window,fixed sash, clear, 139.8 4,584 0 11,172 11,172 <br /> metal frame no break, u-value 1.13, SHGC 0.78 <br /> 1A-cm-o: Glazing-Single pane, operablewindow, clear, 30 1,105 0 2,409 2,409 <br /> metal frame no break, u-value 1.27, SHGC 0.75 <br /> 11J: Door-Metal-Fiberglass Core 21 365 0 378 378 <br /> 13A-5ocs:Wall-Block, board insulation only, R-5 board 1220.4 4,424 0 2,944 2,944 <br /> insulation, open core, siding finish <br /> R-19 BU: Roof/Ceiling-Roof Deck(roofing,wood, 1199.7 1,565 0 1,512 1,512 <br /> insulation)or SIP Panels Supported on Beams, <br /> Custom, Built Up Roof R-19 Roof Deck <br /> 22A-pm-t: Floor-Slab on grade, No edge insulation, no 102 3,491 0 0 0 <br /> insulation below floor,tile covering, passive, heavy <br /> dry or light wet soil <br /> Subtotals for structure: 15,534 0 18,415 18,415 <br /> People: 36 3,780 7,200 10,980 <br /> Equipment: 1,400 3,000 4,400 <br /> Lighting: 1696 5,783 5,783 <br /> Ductwork: 0 0 0 0 <br /> Infiltration:Winter CFM: 126, Summer CFM: 0 3,987 0 0 0 <br /> Ventilation:Winter CFM: 0, Summer CFM: 150 0 6,015 3,111 9,126 <br /> AED Excursion: 0 0 1,579 1,579 <br /> Total Building Load Totals: 19,521 11,195 39,088 50,283 <br /> Check Fi ures i <br /> Total Building Supply CFM: 1,750 CFM Per Square ft.: 1.459 <br /> Square ft. of Room Area: 1,200 Square ft. Per Ton: 276 <br /> Volume (it')of Cond. Space: 16,796 <br /> Buildin Loads I <br /> Total Heating Required Including Ventilation Air: 19,521 Btuh 19.521 MBH <br /> Total Sensible Gain: 39,088 Btuh 78 % <br /> Total Latent Gain: 11,195 Btuh 22 % <br /> Total Cooling Required Including Ventilation Air: 50,283 Btuh 4.19 Tons(Based On Sensible+Latent) <br /> 4.34 Tons(Based On 75%Sensible <br /> Capacity) <br /> Notes <br /> Rhvac is an ACCA approved Manual J and Manual D computer program. <br /> Calculations are performed per ACCA Manual J 8th Edition,Version 2, and ACCA Manual D. <br /> All computed results are estimates as building use and weather may vary. <br /> Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at <br /> your design conditions. <br /> i <br /> i <br /> i, <br /> i <br /> I <br /> U:\...\Suzin Nails ... ills, FI.rh9 � Tuesday, July 14,2015, 10:49 AM <br />