, � page 2 <br /> INSTALLATION USING CONCRETE RUNNER/FOOTER revision 6/07 <br /> 16. A concrete runner,footer or slab may be used in place of the steel ground pan. <br /> a) The concrete shall be minimum 2500 psi mix <br /> b) A concrete runner may be either longitudinal or transverse,and must be a minimum of 8°deep with a minimum width of 16 inches <br /> longitudinally or 18 inches transverse to allow proper distance between the concrete bolt and the edge of the concrete(see below). <br /> c) Footers must have minimum surface area of 441 sq.in.(i.e.21"square),and must be a minimum of 8"deep. <br /> d) If a full slab is used,the depth must be a 4"minimum. <br /> Special inspection of the system bracket installation is not required.. Footers must allow for at least 4°from the concrete bolt to the edge <br /> of the concrete. <br /> NOTE:The bottom of all footings,pads,slabs and runners must be per local jurisdiction. <br /> LONGITUDINAL: (Model 1101 LC"V") <br /> 17. Wh�n�!sing Part#1101-W-CPCA(wetset�,,simply install the bracket in runnerlfooter OR When installing in cured concrete use Part# <br /> 101-D-CPCA(drvsetl.The 1101 (dryset)CA bracket is attached to the concrete using(2)5/8"x3°concrete wedge bolts(Simpson part# <br /> S162300H 5/8"X 3"or Powers equivalent).Place the CA bracket in desired location. Mark boft hole locations,then using a 5/8°diameter <br /> masonry bit,drill a hole to a minimum depth of 3". Make sure all dust and concrete is blown out of the holes.Place wedge bolts into drilled <br /> holes,then place 1101 (dry set)CA bracket onto wedge bolts and start wedge bolt nuts. Take a hammer and IighUy drive the wedge bolts <br /> down by hitting the nut(making sure not to hit the top of threads on bolt).The sleeve of concrete wedge bolt needs to be at or below the to� <br /> of concrete.Complete by tightening nuts_ <br /> LATERAL:(Model 1101 TC"V") <br /> 18. For wet set(part#1101-W-TACA)installation simply install the anchor bolt into runnerffooter. For dry set installation(part#1101-D-TACA) <br /> mark bolt hole locations,then using a 5/8°diam. masonry bit,drill a hole to a minimum depth of 3°. Make sure all dust and concrete is <br /> _!•=�:•^�`:::"�`='�.^!�M:��^�';��^!±s;S�mpson part�tS162300H 5/8°X 3°or Powers equivalent)into(D)concrete dry transverse <br /> __ _____ .____,::_�,::.:;,��;.,r�� «_..�_� �:�3 yammer and IighUy drive the wedge bolts down by hitting the nut(making sure not to hit <br /> -_•••-_---. _...:..-- -..:._ :._. . � ..___= <br /> the top of threads on bolt),then remove the nut.The sleeve of concrete wedqe bolt needs to be at or below the tou of concrete. <br /> 19.When using part#1101 CVW(wetset)or 1101 CVD(dryset),install per steps 17&18. <br /> Notes: <br /> 1. LENGTH OF HOUSE IS THE ACTUAL BOX SIZE <br /> 2. � _�r"-!?n �PIATEAND FRAI1/�T�LOC',ATION (needstr� <br /> 1��1�_-1_!'_-J�' �T1� :u���ICa1{�VI���VI�) <br /> 3. � LOCATION�LONGffUDWALBRACENG ONLY <br />� 4. �=���.!r"-._`'__��-�__-�-.-�.-._ <br /> REQUIRED NUMBER AND LOCATION OF MODEL 1101 "V" OR 1101 C "V" <br /> �RO�CES FOR UP TO 4/12 ROOF PITCI-9 <br /> « <br /> ALL WIDTHS;AND LENGTHS UP TO 52' <br /> � � • • • • <br /> • • � • • � <br /> ALL WIDTHS;AND LENGTHS OVER 52'TO 80' <br /> • � <br /> � • � • <br /> • • <br /> • • • • � � <br /> � • • • � • <br /> HOMES WITH 5%12 ROOF PITCH REQUIRE: PER FLORIDA REGULATIONS _ ' <br /> 6 systems for home lengths.up to 52' and 8 systems for homes over 52' and up 80': One stabilizer <br /> plate and frame tie required.at each lateral bracing system. � � - ". <br />