Laserfiche WebLink
, � <br /> .. � , <br /> A . � � Zone Design Load Surnmary for HEAR USA <br /> Froject Nanie:ZEPHYRHILL 07/O6/2015 <br /> �, Prepared by:MDS�ngineering Corp 07:OOPM <br /> � <br /> - � Zone 1 DESIGN COOLING DESIGN HEATING <br /> COOLING DATA AT Sep 1400 HEATING DATA AT DES HTG <br /> COOLING OA DB/WB 84.4°F/70.8°F HEATING OA DB/WB -6.0°F/-7.2°F <br /> OCCUPIED T-STAT 75.0°F OCCUPIED TSTAT 70.0°F <br /> Sensible Latent Sensible Latent <br /> ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr) <br /> Window&Skylight Solar Loads 292 ftz 12917 - 292 ftZ - - <br /> Wall Transmission 658 ft2 2283 - 658 ft2 11279 - <br /> Roof Transmission 0 ftZ 0 - 0 ft2 0 - <br /> Window Transmission 292 ftZ 1004 - 292 ftz 13031 - <br /> Skylight Transmission 0 ftZ 0 - 0 ft2 0 - <br /> Door Loads 0 ft2 0 0 ftZ 0 - <br /> Floor Transmission 1184 ftz 0 - 1184 ft2 0 - <br /> Partitions 2560 ftz 0 - 2560 ftZ 0 - <br /> Ceiling 0 ft2 0 - 0 ftz 0 - <br /> Overhead Lighting 0 W 0 - 0 0 - <br /> Task Lighting 0 W 0 - 0 0 - <br /> Electric Equipment 0 W 0 - 0 0 - <br /> People 12 2940 2460 0 0 0 <br /> Infiltration - 0 0 - 0 0 <br /> Miscellaneous - 0 0 - 0 0 <br /> Safety Factor 0%!0% 0 0 0% 0 0 <br /> il <br /> »Total Zone Loads 19144 2460 24310 0 <br /> Hourly Analysis Program v.4.3 Page 1 of 1 <br />