Laserfiche WebLink
Fittings Used Summary . <br /> COX FIRE PROTECTION Page 3 -� <br /> fp 1-2-1549-16-16 Zephyr Plaza 011ies Date <br /> Fitting Legend _" <br /> Abbrev. Name '/z '/a 1 1'/a 1'/z 2 2'/z 3 3'/z 4 5 6 8 10 12 14 16 18 20 24 <br /> A Alarm Rel E1 &E3 7.7 21.5 17 27 29 <br /> B NFPA 13 8utterfly Valve 0 0 0 0 0 6 7 10 0 12 9 10 12 19 21 0 0 0 0 0 <br /> E NFPA 13 90'Standard Elbow 1 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61 <br /> T NFPA 13 90'Flow thru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121 <br /> Units Summary <br /> Diameter Units Inches <br /> Length Units Feet <br /> Flow Units US Gallons per Minute <br /> Pressure Units Pounds per Square Inch <br /> Note� Fitting Legend provides equivalent pipe lengths for fittings types of various diameters. <br /> Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors <br /> of 120 except as noted with * The fittings marked with a*show equivalent lengths values <br /> I supplied by manufacturers based on specific pipe diameters and CFactors and they require no <br /> adjustment. All values for fittings not marked with a*will be adjusted in the calculation <br /> for CFactors of other than 120 and diameters other than Sched 40 per NFPA. <br /> Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 <br />