Laserfiche WebLink
Single Family T)welling , <br /> Plan Review Camments <br /> 1. F.F.E. shall be a minimum of 8" above the road elevation and an engineered site plan. <br /> 2. Lats shall be graded to comply with R401.3 of the F.B.C. <br /> 3. Compactian test required if 24" or more of fill dirt is brought in at any one place. <br /> 4. Tie in survey required before pouring concrete. <br /> 5. Driveways require a R.O.W. use permit. A114 sides of driveway thru the sidewalk shall have <br /> expansion materiai. <br /> 6. All setbacks shall be met. <br /> 7. A11 praperty markers shall be uncovered and marked at time of first inspection. <br /> 8. All A.D.A. requirements shall be met. <br /> 9. No electric,pluznbing,mechanical, ar framing sha11 be covered without an inspectifln and <br /> approval fixst. <br /> 10. All Garages shall camply with sectian R309.2 of the F.B.C. (Fire Separation). <br /> 11. Appliances shall not be installed in a location where subject to mechanical damage unless <br /> protected by approved barriers. M343.4 af the F.B.0 <br /> 12. Water heaters shall comply with section P607.3 of the .F.B.0 <br /> 13. Foundation supports forAJC units shall be raised at least 3"abave finished grade. MI308.1 <br /> 14. Return air in all bedroorns. F.B.C. M1620.4 <br /> I 5. Smoke detectors are to be installed in accordance with R313.1 of the F.B.C. <br /> 16. All glazing requirements are to be in accardance with R308.4 ofthe F.B.C. <br /> 17. AIl means of egress are to be in accordance with R311 of the F.B.C. <br /> 18. "Green gypsum board" shall not be used as a backer in showers or tubs. R'702.4.2 F.B.C. <br /> 19. Combinatio�-type AFCI breakers are required at a11 locations requirzng an AFCI type breaker. <br /> 20. Carbon monoxide alarms will be required in new canstruction that uses fossil-burning heating <br /> ar appliances ar an attached garage. They sha1l be installed in accardance with the F.B.C. <br /> 21. All plumbing,mechanical, and electrical shall be separate from unit to unit. This includes a11 <br /> underground plumbing and electric. <br /> 22. A112008 N.E.C. Codes will be enforced. <br /> 23. Tamper Resistant Receptacles in accordance with 40b.11 of the 2008 N.E.0 <br /> 22. In accordance with the Land Llevelapment Code, lats shall be sadded before final at least 1Q <br /> feet araund the structure. <br /> F.F.E.-Finished Floor Elevation <br /> F.B.C-Florida Building Code 5�'Edition <br /> R.O.W.-Right Of Way <br /> A.D.A.-Americans with Disabilities Act N.E.C.-Natianal Electric Code (2008) <br />