Laserfiche WebLink
.� <br /> w� � <br /> , � ; � , , <br /> � , ; � <br /> i <br /> � <br /> EASTIPASCO MEDICAL CENTER <br /> EMER�ENCY ROOM AND REGISTRATION EXPANSIONS AND RENOVATIONS <br /> LOG NUMBER: H-425-F <br /> MAY 15, 1989 <br /> � REC�! VED <br /> ARCHITECTURAL JUN p 6 1ggg <br /> I <br /> Shee!t SD-4: A�S'a.,.. <br /> , ........ <br /> I <br /> A-1 ' A. Provide a demolition plan fot the first floor <br /> I emergency room areas which will be affected when <br /> the roof drain leaders are rerouted. <br /> � � <br /> � B. There shall be an access door in at least 2 sides <br /> ; of the windowless area and the access doors shall <br /> be at least 3 feet wide by 6 feet 8 inches high <br /> � with distinctive identifying matkings on their <br /> exterior . (Standard Building Code, Section 718 <br /> and Standard Fire Ptevention Code, Section 3605) . <br />' C. The unfinished second floor space shall be <br />� provided with a complete functioning fire <br /> � sprinkler system. <br /> Sheet SD-6 : <br /> I ' <br /> . A-2 ', A. Detail a method of installing sprayed <br /> ifireproofing of the required thickness on the <br /> ' backside of the new steel beams abutting existing <br /> i construction, or_ provide another method of <br /> � protecting the steel . <br /> i <br /> iB. Provide a detail showing the method of <br /> i stabilizing the exterior wall structure when the <br /> ; metal stud braces shown at 32 inches on center <br /> I are removed for the use of the space in the <br /> I future. - <br />' ; � <br /> Sheet SD-8 : <br /> i i <br />' A-3i Revise Specifications Section 0831 to provide the I <br /> � required access panels . <br /> � <br /> , I <br /> � � <br /> I <br /> � <br /> � <br /> i <br /> � <br /> i Page 1 of 3 <br /> i <br /> ! <br /> I � <br />.. � <br />