, . . . �'�i <br /> ,�� . . . , <br /> �� <br /> � . , <br /> EAST� PASCO MEDICAL CENTER <br /> EMERlGENCY ROOM AND REGISTRATION EXPANSIONS AND RENOVATIONS <br /> LOG ,��NO. H-425-F / CON NO. NON-REVIEWABLE <br /> NOVEMBER 14, 1989 <br /> ,� <br /> ARCH,ITECTURAL <br /> The ;li Levised consttuction document review lettet was dated ' <br /> Sept�,embet 5, 1989 . Th� response dated October 2, 1989, <br /> sati,�fsfies the requitements of this office with the following <br /> exce;ption(s) . <br /> Chan�qe Order 6: <br /> A-l � Door 102 shall be futnished with emergency release � <br /> hatdware. <br /> A-2 Revise Section B/A4.4 to comply with the plan. <br /> A-3 I� Revise the existing 2-hour wall above the horizontal � <br /> II shaft wall so that the stair enclosure has continuity <br /> ,� independent of the nonrated construction. <br /> � <br /> MFC: If E/mc <br /> �� <br /> �� <br /> MECHANICAL <br /> The I�� Levised construction document review letter was dated <br /> September 5, 1989. The response dated October 2, 1989, <br /> sati�sfies the tequirements of this office with the following <br />' exce�ption(s) . , <br /> �!�� <br /> AC-12 Your response is not in compliance with the <br /> ��I requitements of this office. You must either revise � <br /> the drawinqs ot ptovide documentation to indicate the <br /> Feq�ireai changes ar� part of the conttact documents . <br /> The content of your response to Lhis comment is <br /> acceptable; however, the sketch is zequited to have a <br /> � engineer ' s seal in lieu of the atchitect ' s seal shown. <br /> V <br /> New comments : _ <br /> AC-13I Comply with this comment. Provide a =evised duct� <br /> layout fot Toilet 104A pet Ch�nge Otdet 6 . ' , <br /> AC-1 Pr.ovide 90 percent aiL filttation for the fan coil ' � <br /> units serving the exam/tteatment aieas, Specialty Fan � I <br /> Coil Units 4, 6 and 7 . ' <br />� Page 1 of 2 <br />