.- <br /> �! •1 ' �r 'J� e <br /> � a � • " ,� � � <br /> i�`\ - ., � . <br /> � I <br /> 101-86 , LIFE SAFETY CODE • , <br /> exists 5 ft (152 cmJ or more of space between the top of the 12-3.63.5 Fixed view panels of wired glass, in steel or other <br /> ceiling subsystem and the bottom of the floor or rooJ above, � approved metal frames, limited to 1,296 sq in. (.84 sq m) in <br /> provided: i area, may be installed in these doors. <br /> (aJ The ceiling shall have been tested as a part of a fire- Exception: There shall be no restrictions in area and fire <br /> rated assembly tn accordance with NFPA 251,Standard Meth- resiStance ojglass and frames in buildings protected through- <br /> ods of Fire Tests of Building Construction and Materials,for a � out by an approved supervised automatic sprinkler sys[em <br /> test period of II hour or more, and insralled in accordance with Section 7-7. <br />' (bJ Corridor'partitions form smoketight joints with the ceil- <br /> ings (joint filler, if used, shall be noncombustibleJ and, 12-3.6.3.6 Dutch doors may be used where they conform to <br /> I� (cJ Each corripartment of interstitial space that constitutes a 12-3.6.3,and in addition,both upper leaf and lower leaf shall be <br /> separate smoke;area is vented, in case of smoke emergency, to equipped with a latching device, and the meeting edges of the <br />' the outside by mechanical means having sufficient capacity to upper and lower leaves shall be equipped with an astragal,rab- <br /> provide at least'two air changes per hour, but in no case having bet, or bevel. <br /> a capacity less �han 5,000 cfm (2.36 cu m/sJ, and Dutch doors protecting openings in enclosures around haz- <br /> (dJ The interstitia! space shall not be used for storage, ardous areas shall comply with NFPA 80, Standard for Fire <br /> and i Doors and Windows. <br /> (eJ The space shall not be used as a plenum jor supply, <br /> exhaust or retu`rn air except as noted in (cJ. 12-3.6.4 Transfer Grilles. Transfer grilles, whether or not <br /> ; protected by fusible link operated dampers,shall not be used in <br /> 12-3.6.2.2 Corridor walls shall form a barrier to limit the these walls or doors. <br /> transfer of smoke. Exception. Doors to toilet rooms, bathrooms, shower rooms, <br /> � sink closets and similar auxiliary spaces that do not contain <br /> 12-3.6.2.3 Fixed wired glass vision panels shall be permitted <br /> in corridor walls; provided they do not exceed 1,296 sq in. (.84 ./fammable or combustible materials may have ventilating lou- <br /> sq m) in area and are mounted in steel or other approved metal vers or may be undercut <br /> frames. � <br /> Exception: There shall be no restrictions in area and fire 12-3.7* Subdivision of Building Spaces. <br /> resistance of glass and frames in buifdings protected through- 12-3.7.1 Smoke barriers shall be provided, regardless of <br /> Iout by an approved supervised automatic sprinkler system building construction type, as follows. <br /> installed in acco�l dance with Section 7-7 (a) To divide every story used by inpatients for sleeping br <br /> 12-3.6.3* Corridor poors. treatment,or any story having an occupant load of 50 or more <br /> persons, regardless of use, into at least two compartments, <br /> 12-3.6.3.1 Doors protecting corridor openings in other than and - <br /> required enclosu�res of vertical openings, exits, or hazardous <br /> areas shall be substantial doors, such as those constructed of �b) To limit on any story the length and width of each smoke <br /> � i compartment to no more than 150 ft (45 m). <br /> I/4-in. (4.4-cm) solid bonded core wood or of construction that <br /> will resist fire fo'r at least 20 minutes. Exception No. 1: Protection may be accomplished in con- <br /> � junction with the provision of horizonta! exits. <br /> Exception No. 1�: In buildings protected throughout by an <br /> � approved supervised automatic sprinkler system installed in Exception No. 2. One dimension may be extended provided <br />' accordance withl Section 7-7, the door construction require- that the total width plus length does not exceed 300 ft (91 mJ <br /> ments noted above are not required, but the doors shall be con- and provided that fravel distance from a room to a smoke bar- <br /> � rier door or horizontaf exit is no more than I50 t 45 m . <br /> structed to resist�the passage of smoke.. .f � � <br /> Exception No. 2: Doors to toflet rooms, bathrooms, shower <br /> rooms, sink clos'ets, and similar auxiliary spaces that do not 12-3.7.2 Smoke barriers shall be provided on stories that are <br /> i contain flammab�le or combustible materials. usable but unoccupied. <br /> 12-3.6.3.2 Doo Is shall be provided with latches suitable for <br /> keeping the door'�closed and acceptable to the authority having 12-3.7.3 Any required smoke barrier shall be constructed in <br /> jurisdiction. accordance with Section 6-3 and shall have a fire resistance <br /> rating of at least 1 hour. <br /> Excepiion: Doors to toilet rooms, bathrooms,shower rooms, Exception. Where an atrium is t�sed,smoke barriers may ter- <br /> sink closets, and`similar auxiliary spaces that do not contain <br /> flammable or combustible materials minate at an airium wall constructed in accordance with <br /> Exception No. 2 to 6-2.4.5(gJ A minimum of two separate <br /> 12-3.6.3.3 Doorl frames shall be labeled, or shall be of steel smoke compartments shall be provided on each floor. <br /> construction, or shall be of other materials complying with the <br /> requirements of NFPA 252,Standard Methods of Fire Tests oj 12-3.7.4 At least 30 net sq ft (2.8 sq m) per patient in a <br /> Door Assemblies� hospical or nursing home or 15 net sq ft(1.4 sq m) per resident <br /> Exception: Door frames in buildings protected throughout by � in a limited care facility shall be provided within the aggregate <br /> � an approved supervised automatic sprinkler system installed in area of corridors, patient rooms, treatment rooms, lounge or <br /> accordance with Section 7-7. dining areas, and other low hazard areas on each side of the <br /> I � smoke barrier. On stories not housing bed or litter patients, at <br /> 12-3.6.3.4 Doorl closing devices are not required on doors in least 6 net sq ft (.56 sq m) per occupant shall be provided on <br /> corridor wall operiings other than those serving required enclo- each side of the smoke barrier for the total number of occupants <br /> sures of vertical ipenings, exits, or hazardous areas. in ad�oimng compartments. <br /> �see eomoN � <br />