� <br />' r : <br /> ' I� <br /> EAST`' PASCO MEDICAL CENTER <br /> O.B. ADDITION/CON: EXEMPT <br /> CATH LAB- ADDITION/NON-REVIEWABLE <br /> LOGjNO. H-425-G <br /> NOVEMBER 7, 1989 <br /> B. Indicate the conduit and conductor size. <br /> E-10� Indicate the type of wire utilized for the 2/O feeders <br /> for Panel CRO. <br /> Specifications : <br /> I <br />� E-11� Section 16110: PVC conduit shall not be allowed for <br /> branch circuit use in, or to, patient cate areas . <br /> E-12 Section 16200: <br /> ! <br /> A. Remove the following items listed under life <br /> � safety system: <br />'I l. Nurse call ; <br /> 2 . Switchgear room electrical; and <br /> 3 . Fite pump <br /> B. Remove the atient corridor rece tacles listed <br /> P P <br /> under equipment system. <br /> E-13 Section 16720: <br /> A. Air duct smoke detector trouble shall be <br />� indicated visually or audibly in the fire alarm <br /> , annunciator and shall be identified as air duct <br /> � detector trouble. Air duct detectors in each <br /> � zone may be individually annunciat_ed ot may be <br /> combined to indicate a single annunciated trouble <br /> � signal . <br /> B. To assure that each smoke detector is operative, <br /> all ceiling and air duct smoke detectors shall be <br /> tested in place in accordanc� with the <br /> manufacturet ' s instructions . Sensitivity shall <br /> also be 'detetmined for each smoke detector in <br /> accordance with NFPA-72E. A certification <br /> report, signed by the installing contractor, <br /> shall be submitted at the final inspection <br /> listinq each smoke detector and the test method <br /> I y <br /> � Page 5 of 6 <br />