Laserfiche WebLink
i � I I <br /> � <br /> I <br /> I I <br /> M�r. Todd �Reichard -3- August 30, 1994 <br /> �' I <br /> RESPONSE• <br /> ! Air quantities within the new construction and renovation <br /> � areas, both new and existing, are shown on M-16. <br /> Existing devices have a blank hexagon with air quantity. <br /> Existing devices not in the new construction and <br /> renovation area are shown on M-14 with air quantities. <br /> � Some additional air quantities are shown on replacement <br /> ' � Drawing M-14, Star 2, dated August 19, 1994.. <br /> CC�)MMENT• <br /> Ac:-10 IWomen's Toilet 167 and Men's Toilet 169 are excessively <br /> negative. Revise the air quantities in these rooms to <br /> provide a maximum differential pressure of 100 CFM. <br /> � The air quantities shown on Drawing M-16 have not been <br /> � revised, please comply with this comment. <br /> RESPONSE• <br /> i <br /> � Have complied. See replacement Drawing M-16, Star 2, <br /> �dated August 19, 1994. <br /> CGMMENT• <br /> � <br /> AC-11 Provide 90 percent filtration for AHU-16 and AHU-17 that <br /> I serve the patient corridor system. <br /> I <br /> i Please revise the fan motor horse power requirements for <br /> �, AHU-16 and 17 due to the increased static pressure drop <br /> , imposed by the addition of the 90 percent filter Section <br /> � <br /> F-10 and F-11. <br /> RESPONSE• <br /> � Have complied. 90� filters have been scheduled and added <br /> + lon Sheet M-19, Star 1, dated March 28, 1994. See <br /> replacement Drawing M-20, Star 2, dated August 19, 1994 <br /> for upgraded horse power on AHU-16 and AHU-17. , <br /> � � <br /> COMMENT• , <br /> AC'-13 �Relocated the duct smoke detector for the return air to � <br /> �� �AHU-14 as required to sample the total return air <br /> i quantity including the 6-inch by 6-inch duct branch at � <br /> j the main return drop to AHU-14. Indicate the air j <br /> quantity and what this 6-inch by 6-inch duct serves. I <br /> � <br /> � <br /> i <br /> I <br />