Laserfiche WebLink
� i � <br /> . . , � <br /> � � <br /> , <br /> � ; <br /> � <br /> � <br /> M���. Todd Reichard -9- August 30, 1994 <br /> COMMENT• <br /> Sheet E-24 : <br /> E-�25 Indicate the panel and branch circuit information for the <br /> ; life safety lighting homerun shown at Corridor 174. <br /> RF:SPONSE• � <br /> I � <br /> � ;Have complied. See replacement Sheet E-24, Star 2, dated <br /> ;August 19, 1994 . <br /> � I <br /> CC)MMENT• � <br /> �� <br /> SYieet E-25• <br /> EI26 Relocate the sprinkler pipe (Sheet FP-7) � that passes <br /> through the dedicated space of Panel 1LN6. <br /> � � <br /> RESPONSE: i <br /> 'Sprinkler pipe re-routed. <br /> ; <br /> CC�MMENT• ' <br /> —�� <br /> E�'27 ��Provide selected receptacles connected to the critical <br /> � <br /> �branch in the Telephone Equipment Room 168. <br /> RESPONSE• � <br /> iHave complied. See replacement Sheet E-25, Star 2, dated <br /> August 19, 1994. <br /> COMMENT: i <br /> I <br /> Sh'eet E-25 and E-28: <br /> E�28 Provide overcurrent protection for the power transformer <br /> for the smoke damper motors in accordance with Section <br /> i 450-3 (b) (2) . Provide a wiring detail showing compliance. � <br /> � <br /> RESPONSE• <br /> , , <br /> iProvided OCP and means of disconnect per diagram on Sheet � <br /> �E-33. <br /> i <br /> i <br /> '�� <br /> ,� <br /> � I <br /> � , <br />