Laserfiche WebLink
' 2i�:ri <br /> � P � � ' West Engineering Setv�ces � <br /> r � <br /> � ' Ga�'Y 3414 Grestwood St. <br /> '',' �sT PE Lakeland, FI 33813 <br /> I <br /> I <br /> � <br /> j <br /> ; i HYDRAULIC CALCULATIONS <br /> ��I FOR <br /> � � <br /> � <br /> � EAST PASCO MEDICAL CTR. <br /> ER RENOVATION <br /> FILE NUMBER: EPMC <br /> DATE : Aug 24 , 1999 <br /> -DESIGN DATA- � <br /> OCCUPANCY CLASSIFICATION: - LIGHT HAZARD <br /> DENSITY: . 10 gpm/sq. ft . <br /> AREA OF APPLICATION: 1500 sq. ft . � <br /> COVERAGE PER SPRINKLER: 196 sq. ft . <br /> NUMBER OF SPRINKLERS CALCULATED: 13 sprinklers <br /> TOTP_T_ SPRT_NKLER F7ATER FLOW REQUIRED: 215 . 6 gDm <br /> TOTkL WATER REQUIRED ( including hose) : 315 . 6 gpm <br /> FLOW AND' P.RESSURE (@ BOR} : 215 . 6 gpm @ 27 . 8 psi <br /> SPRINKLER ORIFICE SIZE: 1/2 inch <br /> NAME OF ICONTRACTOR: �-TLANTIC COAST FIRE PROTECTION, INC . <br /> � <br /> DESIGN/LAYOUT BY: BRIAN CRAWFORD � <br /> I � <br /> AUTHORITY HAVING JURISDICTION : � PASCO COUNTY ' <br /> CONTRACTOR CERTIFICATION NUMBER: 731992000199 <br /> CtiL:i��1.ATI�NS BY HASS c;�MPrJTER PROGRAM ( LICENSE {� 1bU8�1490LU ) <br /> _ HRS SYST�:MS , 1NC . <br /> A`PLANTA, GA <br />