Laserfiche WebLink
i � <br /> � <br /> i <br /> 1 ; SUPPORTS AND ANCHORS <br /> � � SECTION 15140 <br /> i � � <br /> � 3.6 ADJUSTMEfVT OF HANGERS AND SUPPORTS: Adjust hangers and supports and place <br /> � grout as required under supparts to bring piping to proper levels and elevations. <br /> I � I <br /> DIAMETER ; MAXIMUM HORlZONTAt SPAC//VG(Ft.)per M.S.s. SP-69 <br /> � OF <br /> � PtPE � <br /> i STEEL STD.WT. COPPER TUBE PVC.SCH. <br /> � i � 80 TYPE 1 <br /> � WATER VAP�R WATER VAPQR (*�� <br /> i � <br /> 1J4" ' � 7 $ 5 5 4-1/2 <br /> 3!8"and 1/2" � ! 7 8 5 6 4-1/2 <br /> �14" i � 7 9 5 7 5 <br /> 'I" i 7 9 6 8 5-1/2 <br /> 1-1/4" ; � 7 9 7 9 5-1/2 <br /> 1-1/2" � � 9 12 8 10 6 <br /> 2" � j 10 9 3 8 11 6 <br /> 2-1/2" i � 11 14 9 13 7 <br /> 3" !1 92 15 10 'E4 7 <br /> 3-1/2" ; j 13 16 11 15 --- <br /> ,4" � i 14 17 12 16 7-112 <br /> 5" ; i 16 19 13 18 --- <br /> 6" � 17 21 44 20 8-1/2 <br /> 8" � i 19 24 16 23 9 <br /> �10" i ! 20 26 1$ 25 9 0 <br /> ;12" ; ; 23 30 19 2$ 11 <br /> � ; i <br /> I " <br /> � � � A. See Section 15400 and 8upport and Hanger Spacing Schedule on the drawings <br /> � i� far pltambing piping systems. <br /> i <br /> i ! , B. Suppart fire-protection piping independently of other piping per NFPA,Sectian <br /> '1 � i 13. <br /> � <br /> � � � C. tnstallation sha(I be in accordance with (atest issue of"Fire Resistance Directory" <br /> � � published by UL. <br /> I i <br /> I � <br /> '� II <br /> � � � <br /> 'I ! I <br /> � � I END OF SECTION <br /> ,� fi <br /> . I <br /> � <br /> i <br /> � <br /> �� � <br /> � . <br /> (97008-040497} 1 a140-5 <br /> i � <br /> � i <br /> ; I <br />