� <br /> I <br /> � <br /> � SECTION 15862 - CENTRIFUGAL ROOF MOUNTED EXHAUST FANS <br /> s � <br /> � <br /> � PART 1� - GENERAL <br /> � <br /> 1.1 WORK INCLUDED <br /> A. Centrifugal Roof Mounted Exhaust Fans. <br /> � 1.2 SUBMITTALS <br /> � A. Submit for Review: <br /> � <br /> � l. Product Data including rated capacities of selected models, <br /> j weights (shipping, installed, and operating), furnished <br /> ' � specialties, and accessories. Indicate dimensions, finishes <br /> � and coatings, required clearances, methods of assembly of <br /> components, and piping and wiring connections. <br /> 2. Shop Drawings showing layout of each unit, including <br /> � controls and related accessories. <br /> , ' B. Submit at Project Completion: <br /> • ' <br /> 1. Maintenance data for fans and accessories; include in <br /> operation and maintenance manuals. Include wiring <br /> diagrams detailing electrical power supply and ladder-type <br /> i wiring diab ams for interlock and control wiring. <br /> 1.3 QUALITY ASSURANCE <br /> iA. Certify fan performance in accordance with AMCA Certified Air <br /> � and Sound Rating Criteria, Standard 210. <br /> B. Provide components that: <br /> � 1. Comply with NFPA 70 and that are listed and labeled by <br /> i <br /> UL where available. <br /> 2. Meet AMCA performance requirements and are licensed to <br /> use the AMCA Seal. <br /> 3. Comply with applicable NEMA standards. <br /> • 4. Comply with UL 705. <br /> i <br /> � <br /> ICT 991�84 <br /> I 15862 - 1 <br />