> -- `�•- <br /> , _ � '� _ � <br /> � ._ :. ^� -.:: <br /> . _. �_; t q <br /> PENINSULA FIRE SYSTEMS, INC. � b� <br /> P . 0. B OX 114 4 6 �G>i'�``�` <br /> � TAMPA, FL 33610 � � �/..�. <br /> � 6��� ��� <br /> i <br /> I HYDRAULIC CALCULATIONS <br /> FOR <br /> WAL-MART GARD�N AREA i <br /> I ZEPHYRHILLS, FLORIDA <br /> FILE NUMBER: WAL-GAR <br /> DATE: MAY 14 , 1992 <br /> � -DESIGN DATA- <br /> OCCUPAN'CY CLASSIFICATION: PER SPEC, S <br /> DENSITY:� . 19 gpm/sq . ft . <br /> AREA OF ;P�PPLICATION: 2000 sq . ft . <br /> I COVERAG!E PER SPRINKLER: 121 . 00sq . ft . <br /> NUMBER OF SPRINKLERS CALCULATED: 17 sprinklers <br /> TOTAL SPRINKLER WATER FLOW REQUIRED: 432 . ]. gpm <br /> TOTAL W;ATER REQUIRED (including hose) : 682 . 1 gpm <br /> FLOW ANID PRESSURE (@ BOR) : 682 . 1 gpm @ 30 . 9 psi <br /> SPRINKLER ORIFICE SIZE: 17/32 inch <br /> NAME OF , CONTRACTOR: PENINSULA FIRE SYSTEM, INC. <br />' DESIGN/LAYOUT BY: S.R.H. /D. P .G. <br /> � <br /> AUTHORITY HAVING JURISDICTIOIV : CITY �F ZEPHYRHILLS <br /> � <br />' CONTRACTOR CERTIFICATION NUMBER: 392603000188 <br /> I <br /> C LCULATIONS BY HASS COMPUTER PROGRAM (LICENSE # 812A40.5 ., ) -:� � <br /> HRS SYSTEMS, INC. - -- -- <br /> ATLANTA, GA =- - ,> - � I <br /> � ` � <br /> , � <br /> , ���`��- i' <br /> " � I <br />