Laserfiche WebLink
y <br /> , � <br /> � <br /> � � � <br /> Rhvac-Residential&Light Commercial HVAC Loads I Elite Software Development,Inc. <br /> HVAC Designs �I Stonewood Office-Retail 1493 e <br /> Tam a, FL 33635 �i/ Pa e 1 <br /> Total Building Summary Loads I ' � <br /> Component � Area Sen Lat Sen r Total <br /> Description j Quan Loss Gain Gain � Gain <br /> 1A-cm-o: Glazing-Single pane, operable window, clear, 183.1 6,276 0 10,892 i10,892 <br /> metal frame no break, outdoor insect screen with „ <br /> 50%coverage, u-value 1.27 ' �, <br /> 1 B-cm: Glazing-Single pane window,fixed sash, clear, i 27.4 835 0 1,748 j! 1,748 <br /> metal frame no break, u-value 1.13 � <br /> 13A-4ocs:Wall-Block, board insulation only, R-4 board � 1095.7 4,231 0 2,555 � 2,555 <br /> insulation, open core, siding finish <br /> 16B-19-ad: Roof/Ceiling-Under attic or knee wall,vented 1493 1,975 0 3,731 ,� 3,731 <br /> attic, no radiant barrier, R-19 insulation, dark asphalt �, <br /> 22A-pm-t: Floor-Slab on grade, No edge insulation, no I 140 4,460 0 0 �� 0 <br /> insulation below floor,tile covering, passive, heavy � �� <br /> dry or light wet soil i ; <br /> Subtotals for structure: 17,777 0 ! ' 18,926 �18,926 <br /> People: 8 1,840 , 2,400 i 4,240 <br /> Equipment: 160 i 1,860 �i 2,020 <br /> Lighting: I 1560 � ' 5,320 5,320 <br /> Ductwork: 4,149 1,067 3,927 4,994 <br /> Infiltration: Winter CFM: 0, Summer CFM: 0 � 0 0 0 0 <br /> Ventilation: Winter CFM: 345,Summer CFM: 345 i 10,210 9,406 � 6,050 ,�15,456 <br /> Total Building Load Totals: i 32,135 12,473 I 38,483 50,955 <br /> Check Figures � ' <br /> � <br /> Total Building Supply CFM: 2,000 CFM Per Square ft.: � 1.34� <br /> Square ft. of Room Area: 1,493 Square ft. Per Ton: ! 34J <br /> Volume(ft')of Cond. Space: 13,930 Air Turnover Rate (per hour): ' 8.G <br /> � <br /> Building Loads '� ;; <br /> Total Heating Required With Outside Air: 32,135 Btuh 32.135 MBH ' <br /> Total Sensible Gain: 38,483 Btuh 76 % I, <br /> Total Latent Gain: 12,473 Btuh 24 % � � ' <br /> Total Cooling Required With Outside Air: 50,955 Btuh 4.28 Tons (Based On 75%Sensible �� <br /> � Capacity) � i <br /> Notes ' j <br /> Calculations are based on 8th edition of ACCA Manual J. i '' <br /> All computed results are estimates as building use and weather may vary. <br /> Be sure to select a unit that meets both sensible and latent 1�'oads. i <br /> � <br /> �i <br /> � i� <br /> i ;� <br /> , � <br /> I <br /> � <br /> �� <br /> , , <br /> I " <br /> I � <br /> i I <br /> I Ii <br /> i� <br /> � I) <br /> i d <br /> ii <br /> �i <br /> ; , I <br /> I I' <br /> i <br /> i , � <br /> � <br /> � 6 <br /> Wednesday,August 08,2007, 5:01 PM <br /> , , ' . i, <br />