<br /> Rhvac'�Residential&'�Light Commercial HVAC Loads li Elite Software Development,Inc.
<br /> HVAC Designs �, i �° Stonewood Office-Retail 1493 e ��
<br /> Tam a,�FL 33635 �I i � I Pa e 1
<br /> Total Building S,ummary Loads I,
<br /> Component i� ; Area Sen Lat Sen Total �
<br /> Descr�p�ion �� Quan Loss Gain Gain Gain
<br /> 1A-cm-o: Glazing-Single pane, operable window, clear, 183.1 6,276 0 10,892 10,892
<br /> me�al frame no�,break, outdoor insect screen with
<br /> 50%coverage, u-value 1.27
<br /> 1B-cm:IGlazing-Single pane window,fixed sash, clear, 27.4 835 0 1,748 1,748
<br /> metal frame no �break, u-value 1.13
<br /> 13A-4ocs: Wall-Block, board insulation only, R-4 board 1095.7 4,231 0 2,555 2,555
<br /> insulation, open,core,siding finish
<br /> 16B-19-�ad: Roof/Ceiling-Under attic or knee wall,vented 1493 1,975 0 3,731 3,731
<br /> attic, no radiant barrier, R-19 insulation, dark asphalt
<br /> 22A-pm�It: Floor-Slab �on grade, No edge insulation, no � 140 4,460 0 0 0
<br /> ins�ilation below�floor,tile covering, passive, heavy
<br /> dry or light wet s'oil
<br /> Subtotals for structll�e: 17,777 0 18,926 18,926
<br /> People: 8 1,840 2,400 4,240
<br /> Equipment: 160 1,860 2,020
<br /> Lighting: 1560 5,320 5,320
<br /> Ductwork: �, 4,149 1,067 3,927 4,994
<br /> Infiltrati�on:Winter CFM: 0,Summer CFM: 0 0 0 0 0
<br /> Ventilation: Winter CFM: 345,Summer CFM: 345 10,210 9,406 6,050 15,456
<br /> Total Building Load�Totals: � 32,135 12,473 38,483 50,955 �
<br /> �,�
<br /> Check Figures �li I �
<br /> Total B ilding SuppIyICFM: 2,000 CFM Per Square ft.: 1.340
<br /> Square ft. of Room Area: 1,493 Square ft. Per Ton: 349
<br /> Volume (ft3) of Cond��,Space: 13,930 Air Turnover Rate (per hour): 8.6
<br /> Building Loads ' �
<br /> Total Heating Requir,ed With Outside Air: 32,135 Btuh 32.135 MBH
<br /> Total Se�sible Gain:'� 38,483 Btuh 76 %
<br /> Total Latient Gain: !� 12,473 Btuh 24 %
<br /> Total Cooling Required With Outside Air: 50,955 Btuh 4.28 Tons (Based On 75%Sensible
<br /> I� I Capacity)
<br /> Notes � ;� , �
<br /> Calculati'ons are bas'ed on 8th edition of ACCA Manual J. I
<br /> All computed results'are estimates as building use and weather may vary.
<br /> Be sure ��o select a u I it that meets both sensible and latent loads.
<br /> ' ' I
<br /> I' I I
<br /> I
<br /> I
<br /> �
<br /> ;�, Wednesday,August 08,2007, 5:01 PM