Laserfiche WebLink
Chapter 2—Components <br /> Page 2- 1 <br /> = Revision 5 <br /> � Chapter 2 <br /> : , <br /> System Components <br /> Cvlinder Sizes <br /> The Buckeye Fire Equipment Kitchen Mister Fire Suppression System has available four (4) cylinder sizes; the Model <br /> BFR-5 (5 flow points), Model BFR-10 (10 flow points), Model BFR-15 (15 flow points), and Model BFR-20 (20 flow <br /> points). Cylinder sizes are based on the flow point capacity of the cylinder, for example, the BFR-5 is capable of <br /> supporting a maximum of five(5)Flow points. All cylinders are manufactured, marked, and tested in accordance with DOT <br /> 4BW240. Each cylinder is shipped pre-filled with extinguishing agent, and charged with dry nitrogen to a pressure of 195 <br /> psig(1344 KPa)@ 70°F(21°C) Cylinder and valve assembly dimensions are shown in Figure 2-1. <br />� Note� Cylinders shall always be stored in an upright position. � <br /> — a _.��_� g <br /> ( I <br /> B��EYE <br /> SRlII <br /> m,.� � <br /> � -_� � <br /> i� <br /> I <br /> I <br /> I <br /> „A„ � <br /> „B„ „p„ <br /> i <br /> � <br /> � � � <br /> >>C„ - <br /> Figure 2-1. <br /> Cylinder and Valve Assembly Dimensions. <br /> A B C D Mau. Weight <br /> Model inches inches inches inches Flow Ibs. Mounting <br /> Number (cm) (cm) (cm) (cm) Points (kg) ` Bracket <br /> � BFR-5 24.8 (63) 16.2 (41) 10 (25} 13.4 (34) 5 42 Ibs.(19) MB-1 <br /> , BFR-10 34.4 (87) 25.8 (66) 10 (25) 23 (58) 10 74 Ibs.(33) MB-2 <br /> BFR-15 44.8 (114) 36.2 (92) 10 (25) 33.4 (85) 15 107 Ibs.(48) MB-2 <br /> " � BFR-20 42.4 (108) 33.8 (86) 12 (31) 31 (79) 20 130 Ibs.(60) MB-2 <br /> BPN: BFR-TM ULEX 6885 ULC-EX 6885 <br /> - January 1, 2013 <br />