Laserfiche WebLink
1 <br /> ` Manual S Compliance Report , ��b: �sa�SfwHcs���e�do�... <br /> Date: 819/2016 <br /> Entire House By: Dave <br /> BAYONET PLUMBING COOLING HEATING <br /> ' � - • • <br /> For: Lennar Homes <br /> i <br /> • � • � � <br /> Desig Conditions <br /> Outd or design DB: 91.3°F Sensible gain: 6914 Btuh Entering coil DB: 75.6°F <br /> Outd or design WB: 77.3°F Latent gain: 1652 Btuh Entering coil WB: 62.8°F <br /> Indoo design DB: 75.0°F Total gain: 8567 Btuh <br /> Indoo RH: 50% Estimated airflow• 600 cfm <br /> Manuf cturer's Performance Data at Actual Design Conditions <br /> Equip ent type: SpIitASHP <br /> Manu acturer: Lennox Model: 14FiPX-018-230-22+CBX27UH-018-230'`++TDR <br /> Actu I airflow: 600 cfm <br /> Sensi le capacity: 15300 Btuh 221% of load <br /> Laten capacity: 2700 Btuh 163% of load � <br /> Total_ apacity: 18000 Btuh 210% of load SHR: 85% <br /> • • . <br /> Desig Conditions <br /> Outd or design DB: 30.8°F Heat loss: 7775 Btuh Entering coil DB: 69.7°F <br /> Indoo design DB• 70.0°F <br /> Manuf cturer's Performance Data at Actual Design Conditions <br /> Equi menttype: SpIitASHP <br /> Marnifacturer: Lennox Model: 14HPX-018-230-22+CBX27UH-018-230*++TDR <br /> �Actu�l airflow• 600 cfm <br /> Outp�t capacity: 17500 Btuh 225°/a of load Capacity balance. 18 °F <br /> Supp emental heat required: 0 Btuh Economic balance: -99 °F <br /> , <br /> - Back p equipment type: Elec strip <br /> Man acturer: n/a Model: n/a+Na <br /> Actu I airflow: 600 cfm <br /> Output capacity: 0 kW 0% of load Temp. rise: 0 °F <br /> , <br /> The above equipment was selected in accordance with ACCA Manual S. <br /> �. wri htsoft� � 2016-Aug-0914:25:48 <br /> i �� 9 Right-Sufte�Universal 2013 13.0.09 RSU05714 Page 1 <br /> ..les center 1941 sf silverado ranch 416sq ft.rup Calc=MJ8 House Front faces: S <br />