<br />ELECTRICAL SYMBOLS LEGEND
<br />(SYMBOLS APPLY ONLY WHEN USED ON DRAWINGS)
<br />SYMBOL
<br />DESCRIPTION
<br />�o/
<br />LIGHT FIXTURE
<br />0
<br />(WALL MOUNTED/CEILING MOUNTED)
<br />(— o --�
<br />LIGHT FIXTURE
<br />r---,��
<br />LIGHT FIXTURE,
<br />A. NO CIRCUITRY SHALL BE ALLOWED TO BE ROUTED ACROSS THE
<br />EMERGENCY LIGHT
<br />r-•.�.,;, –�
<br />LIGHT FIXTURE
<br />B. ALL EQUIPMENT SHALL BE UL LISTED WHERE APPLICABLE.
<br />NIGHT LIGHT
<br />0
<br />ENCLOSED COOLER/FREEZER LIGHT
<br />Ll
<br />TRACK LIGHTING
<br />/
<br />EXIT FIXTURE
<br />CRITICAL SCHEDULING CONCERNS. PROVIDE
<br />(WALL MOUNTED/CEILING MOUNTED)
<br />D. CONTRACTOR SHALL VERIFY ALL WALL FINISH THICKNESS
<br />EMERGENCY FIXTURE
<br />BEFORE INSTALLING BOXES: FURNISH AND INSTALL EXTENDED
<br />SWITCH, SINGLE POLE
<br />f3
<br />SWITCH, 3 -WAY
<br />$M
<br />SWITCH, MANUAL MOTOR
<br />$OS
<br />SWITCH, OCCUPANCY SENSOR
<br />#OS
<br />SWITCH, BI -LEVEL OCCUPANCY SENSOR
<br />(OS/ Q
<br />.S
<br />CEILING OCCUPANCY SENSOR AND ASSOCIATED RELAY
<br />LIVE PARTS.
<br />RECEPTACLE,DUPLEX
<br />RECEPTACLE, DUPLEX,
<br />2. PROVIDE SEALS AT RACEWAY PENETRATIONS AS FOLLOWS:
<br />MOUNTED HORIZONTALLY
<br />RECEPTACLE, DOUBLE DUPLEX
<br />A. FIRE RATED WALLS: SEAL PER SPECIFICATIONS FOR FIRE STOPPING.
<br />RECEPTACLE, DUPLEX ISOLATED GROUND
<br />B. NEUTRALIZATION AREA: SEAL PER MECHANICAL DETAIL.
<br />RECEPTACLE, DOUBLE DUPLEX,
<br />C. FREEZER/COOLER BOXES: SEAL WITH EXPANDING FOAM SEALANT.
<br />ISOLATED GROUND
<br />D. EXTERIOR: REFER TO ARCHITECTURAL DOCUMENTS FOR SEALING
<br />RECEPTACLE, SIMPLEX TWIST
<br />REQUIREMENTS AT ALL EXTERIOR MOUNTED DEVICES, FIXTURES,
<br />LOCK, L5 -15R, UNO
<br />ENCLOSURES, AND RACEWAY PENETRATIONS.
<br />RECEPTACLE, SIMPLEX TWIST
<br />O
<br />LOCK, ISOLATED GROUND, L5 -15R, UNO
<br />3. PROVIDE A SEPARATE EQUIPMENT GROUNDING CONDUCTOR (SIZE
<br />RECEPTACLE, DUPLEX TWIST
<br />PER NEC) IN PVC TYPE CONDUIT, POWER CIRCUITS, ISOLATED GROUND
<br />LOCK, L5 -15R, LINO
<br />CIRCUITS, OR AS SHOWN ON PLANS. CONDUIT SHALL BE SIZED PER NEC
<br />RECEPTACLE, DUPLEX TWIST
<br />BASED ON THWN 600 VOLT COPPER SINGLE CONDUCTORS, PLUS THE
<br />LOCK, ISOLATED GROUND, L5 -15R, UNO
<br />EQUIPMENT GROUNDING CONDUCTOR.
<br />RECEPTACLE, SPECIAL
<br />RECEPTACLE, SIMPLEX
<br />®
<br />RECEPTACLE, PLUG -MOLD
<br />Q
<br />JUNCTION BOX
<br />PLANS. COORDINATE THE STANDARD MOUNTING HEIGHTS WITH
<br />(WALL MOUNTED/CEILING MOUNTED)
<br />Q
<br />JUNCTION BOX, ALARM SYSTEM
<br />A. SWITCHES +44"
<br />(WALL MOUNTED/CEILING
<br />B. RECEPTACLES +20"
<br />MOUNTED), ALARM JUNCTION BOX
<br />Q
<br />FOR REMOTE TEST/RESET
<br />(WALL MOUNTED/CEILING MOUNTED)
<br />5. WIRING SHALL INCLUDE FINAL CONNECTION TO ALL EQUIPMENT IN
<br />EQUIPMENT CONNECTION POINT
<br />CONFORMANCE WITH EQUIPMENT SUPPLIER WIRING DIAGRAMS.
<br />(PROVIDED WITH EQUIPMENT)
<br />❑-�
<br />NON-FUSED
<br />6. CONTRACTOR IS RESPONSIBLE FOR PROVIDING COMPLETE
<br />DISCONNECT
<br />ol
<br />FUSED DISCONNECT
<br />stir�
<br />CIRCUIT, CONCEALED IN WALLS
<br />OR CEILING, E INDICATES
<br />7: NEW OVERCURRENT PROTECTIVE DEVICES INSTALLED IN EXISTING
<br />EXISTING WIRING
<br />PANELBOARDS OR DISTRIBUTION BOARDS SHALL MATCH THE TYPE AND
<br />PANELBOARD FOR FUTURE USE, UNLESS NOTED OTHERWISE ON
<br />AIC RATING OF EXISTING OVERCURRENT PROTECTIVE DEVICES.
<br />DRAWINGS. PROVIDE HANDLE DEVICE TO LOCK "SPARE" CIRCUIT
<br />CIRCUIT, CONCEALED IN FLOOR
<br />BREAKER IN THE "OFF" POSITION.
<br />8. BRANCH CIRCUIT CONDUCTORS SHALL BE MINIMUM #12 AWG UNLESS
<br />SLAB, E INDICATES EXISTING WIRING
<br />--1�
<br />E. DEMOLISHED FLUORESCENT LIGHT FIXTURES: REFER TO SELECTIVE
<br />CIRCUIT, EXPOSED, E
<br />SITE DEMOLITION SPECIFICATION FOR DISPOSAL OF LIGHT FIXTURE.
<br />FOR THE FINAL CONNECTION (15 -FT MAXIMUM).
<br />INDICATES EXISTING WIRING
<br />FLUSH MOUNTED PANELBOARD
<br />_
<br />SURFACE MOUNTED PANELBOARD
<br />Td/Tv
<br />VOICE/DATA,
<br />V
<br />d = DATA ONLY, v = VOICE ONLY
<br />T
<br />LOW VOLTAGE CABLE BOX FOR OTHER
<br />m
<br />VOICE/DATA, FLUSH FLOOR
<br />Xy
<br />MOTOR
<br />❑
<br />TELEPOWER POLE
<br />Q
<br />PUSH BUTTON
<br />6
<br />BUZZER
<br />S�
<br />SMOKE DETECTOR
<br />MOUNTED UNLESS NOTED OTHERWISE. REFER TO ARCHITECTURAL
<br />ENERGY MANAGEMENT
<br />S -X
<br />TEMPERATURE SENSOR
<br />O
<br />THERMOSTAT
<br />TC
<br />TIME CLOCK
<br />ABBREVIATIONS
<br />a, b, c LOWER CASE LETTERS IG ISOLATED GROUND
<br />INDICATE SWITCHING IRC INTER -REGISTER
<br />AFC ABOVE FINISH COUNTER COMMUNICATION
<br />AFF ABOVE FINISH FLOOR ISP IN-STORE PROCESSOR
<br />AFG ABOVE FINISH GRADE LCU LIGHTING CONTROL UNIT
<br />C CONDUIT K KEY OPERATED
<br />CCT CIRCUIT N NEUTRAL
<br />CF CEILING/CIRCULATION FAN NTS NOT TO SCALE
<br />D DATA P WITH PILOT LIGHT
<br />EC ELECTRICAL CONTRACTOR RH RADIANT HEATER
<br />EF EXHAUST FAN RC REFRIGERATION'
<br />EP EXPLOSION CONTRACTOR
<br />ETR EXISTING TO REMAIN SC SECURITY CAMERA
<br />EWC ELECTRIC WATER SF SUPPLY FAN
<br />FUT FUTURE, TYP TYPICAL
<br />GR GROUND WH WATER HEATER
<br />GFEP GROUND FAULT EQUIPMENT WP WEATHERPROOF
<br />PROTECTION WR WEATHER RESISTANT
<br />GFI GROUND FAULT CIRCUIT UH UNIT HEATER
<br />INTERRUPTER UNO UNLESS NOTED OTHERWII
<br />GF GABLE FAN ##W CONDUCTOR IN AWG SIZE
<br />HD HAND DRYER
<br />10.28.16
<br />EN08
<br />1. FURNISH AND INSTALL ALL MATERIALS, EQUIPMENT, AND LABOR, FOR A
<br />13. ONLY FEEDER CIRCUITS NOTED ON THE ONE LINE DIAGRAM AND BRANCH
<br />COMPLETE INSTALLATION IN ALL RESPECTS, READY FOR INTENDED USE
<br />CIRCUITS NOTED BY LEGEND SHALL BE INSTALLED UNDER SLAB. ALL
<br />AND IN STRICT ACCORDANCE WITH NEC, NESC, STATE, AND LOCAL
<br />OTHER FEEDER AND BRANCH CIRCUITS SHALL BE INSTALLED OVERHEAD.
<br />CODES, AND MANUFACTURER'S RECOMMENDATIONS. PAY ALL
<br />PROVIDE EXTERIOR COATED GRC BENDS ON ALL CONDUIT RUNS THAT
<br />NECESSARY FEES AND PERMITS.
<br />HAVE 45 DEGREE BENDS OR GREATER. REF SPECIFICATIONS.
<br />A. NO CIRCUITRY SHALL BE ALLOWED TO BE ROUTED ACROSS THE
<br />14. SEISMIC ZONE REQUIREMENTS: PROVIDE EXPANSION COUPLINGS AND
<br />ROOF OR THE EXTERIOR SIDE OF THE EXTERIOR WALLS.
<br />BRACING FOR ELECTRICAL EQUIPMENT AS REQUIRED BY LOCAL CODES.
<br />B. ALL EQUIPMENT SHALL BE UL LISTED WHERE APPLICABLE.
<br />15. EXISTING ELECTRICAL AND ALARM:
<br />C. ARRANGE ALL WORK TO MINIMIZE DISRUPTIONS TO STORE
<br />A. WHERE DEMOLITION OR NEW CONSTRUCTION INTERRUPTS EXISTING
<br />OPERATIONS. COORDINATE ALL DISRUPTIONS WITH WALMART
<br />ELECTRICAL CIRCUITS FEEDING EXISTING EQUIPMENT, DEVICES, OR
<br />CONSTRUCTION MANAGER AND STORE MANAGER.
<br />LIGHTING TO REMAIN, BUT NOT SHOWN ON DRAWINGS, PROVIDE
<br />CRITICAL SCHEDULING CONCERNS. PROVIDE
<br />LABOR AND MATERIALS TO REWORK CIRCUITRY, AS REQUIRED, TO
<br />D. CONTRACTOR SHALL VERIFY ALL WALL FINISH THICKNESS
<br />MAINTAIN EXISTING OPERATION.
<br />BEFORE INSTALLING BOXES: FURNISH AND INSTALL EXTENDED
<br />I
<br />BOXES OR BOX EXTENDERS WHERE REQUIRED.
<br />B. IF DEMOLITION OR NEW CONSTRUCTION WILL DISRUPT EXISTING
<br />START OF BUSINESS THE FOLLOWING MORNING NO
<br />UNDERGROUND SERVICES (ELECTRICAL, TELEPHONE, PARKING LOT
<br />E. CONTRACTOR SHALL VERIFY THAT ALL AFFECTED PANELBOARDS
<br />LIGHTING CIRCUITRY, ETC.) PROVIDE ALL MATERIALS AND LABOR AS
<br />HAVE CIRCUIT BREAKER KNOCKOUTS PROPERLY COVERED AND
<br />REQUIRED TO REROUTE, SLEEVE, OR OTHERWISE REWORK THESE
<br />THAT ALL TRIM IS IN GOOD CONDITION, ALLOWING NO ACCESS TO
<br />SERVICES TO MAINTAIN THEIR EXISTING OPERATION.
<br />LIVE PARTS.
<br />4. UPON COMPLETION OF ELECTRICAL INSTALLATION
<br />C. EXERCISE CAUTION AROUND ALARM AND SECURITY CABLES DURING
<br />2. PROVIDE SEALS AT RACEWAY PENETRATIONS AS FOLLOWS:
<br />DEMOLITION AND CONSTRUCTION. PROTECT ALARM AND SECURITY
<br />CABLES FROM ACCIDENTAL DAMAGE SO THAT SYSTEMS REMAIN
<br />A. FIRE RATED WALLS: SEAL PER SPECIFICATIONS FOR FIRE STOPPING.
<br />OPERATIONAL AT ALL TIMES.
<br />B. NEUTRALIZATION AREA: SEAL PER MECHANICAL DETAIL.
<br />D. DISPOSE OF ALL REMOVED MATERIALS, UNLESS OTHERWISE NOTED.
<br />C. FREEZER/COOLER BOXES: SEAL WITH EXPANDING FOAM SEALANT.
<br />16. EXISTING ELECTRICAL DEMOLITION:
<br />D. EXTERIOR: REFER TO ARCHITECTURAL DOCUMENTS FOR SEALING
<br />A. GENERAL: REMOVE OR RELOCATE EXISTING ELECTRICAL EQUIPMENT
<br />REQUIREMENTS AT ALL EXTERIOR MOUNTED DEVICES, FIXTURES,
<br />CONDUIT, AND CONDUCTORS AS INDICATED ON THE DRAWINGS, OR
<br />ENCLOSURES, AND RACEWAY PENETRATIONS.
<br />ONLY AS REQUIRED BY DEMOLITION, REMOVE ALL PANELBOARDS,
<br />O
<br />DISCONNECT SWITCHES, BOXES, RELAYS, TIME SWITCHES, LIGHTS,
<br />3. PROVIDE A SEPARATE EQUIPMENT GROUNDING CONDUCTOR (SIZE
<br />DEVICES, ETC., WHICH WILL NOT BE REUSED.
<br />PER NEC) IN PVC TYPE CONDUIT, POWER CIRCUITS, ISOLATED GROUND
<br />CIRCUITS, OR AS SHOWN ON PLANS. CONDUIT SHALL BE SIZED PER NEC
<br />B. SALES FLOOR: REMOVE UNUSED POWER DROP CONDUIT,
<br />BASED ON THWN 600 VOLT COPPER SINGLE CONDUCTORS, PLUS THE
<br />CONDUCTORS AND RELATED DEVICES SERVING SALES AREA
<br />EQUIPMENT GROUNDING CONDUCTOR.
<br />GONDOLAS BEING RELOCATED OR REMOVED. EXISTING CONDUIT
<br />AND CONDUCTORS MAY BE REUSED FOR NEW POWER DROPS
<br />4. WIRING DEVICES: DEVICE MOUNTING HEIGHTS ARE FROM FINISHED
<br />WHERE SIZE, RATING, AND CONDITION MEET REQUIREMENTS
<br />FLOOR TO CENTER OF OUTLET BOX UNLESS NOTED OTHERWISE ON
<br />INDICATED ON PLANS AND ALL U.L. RATINGS. REMOVE ALL UNUSED
<br />PLANS. COORDINATE THE STANDARD MOUNTING HEIGHTS WITH
<br />CONDUIT AND CONDUCTORS BACK TO POINT OF ORIGIN WHENEVER
<br />MASONRY:
<br />FEASIBLE AND RELABEL DEMOLISHED CIRCUITS AS "SPARE".
<br />A. SWITCHES +44"
<br />PROVIDE HANDLE DEVICE TO LOCK "SPARE" CIRCUIT BREAKER IN
<br />B. RECEPTACLES +20"
<br />THE "OFF" POSITION.
<br />C. VOICE/DATA +20"
<br />C. CONDUIT AND WIRING TO BE ABANDONED IN CEILING SPACES AND
<br />5. WIRING SHALL INCLUDE FINAL CONNECTION TO ALL EQUIPMENT IN
<br />OTHER NON-PUBLIC AREAS (I.E., THROUGH STOCKROOM AREA):
<br />CONFORMANCE WITH EQUIPMENT SUPPLIER WIRING DIAGRAMS.
<br />CUT WIRING LOOSE AND REMOVE FROM RACEWAY(S), LEAVING
<br />RACEWAY(S) IN PLACE. CONDUIT TO BE ABANDONED IN WALLS OR
<br />6. CONTRACTOR IS RESPONSIBLE FOR PROVIDING COMPLETE
<br />FLOORS SHALL BE REMOVED BACK TO FINISHED SURFACE AND
<br />PANELBOARD IDENTIFICATION SCHEDULES FOR PANELBOARDS
<br />CAPPED INSIDE. REPAIR SURFACE(S) TO MATCH ADJACENT.
<br />AFFECTED BY REMODEL.
<br />D. ALL CIRCUIT BREAKERS SERVING BRANCH CIRCUITS TO BE
<br />7: NEW OVERCURRENT PROTECTIVE DEVICES INSTALLED IN EXISTING
<br />ABANDONED OR REMOVED SHALL REMAIN IN RESPECTIVE
<br />PANELBOARDS OR DISTRIBUTION BOARDS SHALL MATCH THE TYPE AND
<br />PANELBOARD FOR FUTURE USE, UNLESS NOTED OTHERWISE ON
<br />AIC RATING OF EXISTING OVERCURRENT PROTECTIVE DEVICES.
<br />DRAWINGS. PROVIDE HANDLE DEVICE TO LOCK "SPARE" CIRCUIT
<br />BREAKER IN THE "OFF" POSITION.
<br />8. BRANCH CIRCUIT CONDUCTORS SHALL BE MINIMUM #12 AWG UNLESS
<br />NOTED OTHERWISE IN SCHEDULES. WHERE 20A BRANCH CIRCUITS
<br />E. DEMOLISHED FLUORESCENT LIGHT FIXTURES: REFER TO SELECTIVE
<br />HAVE #8 AND LARGER WIRE SPECIFIED, #10 AWG WIRE SHALL BE USED
<br />SITE DEMOLITION SPECIFICATION FOR DISPOSAL OF LIGHT FIXTURE.
<br />FOR THE FINAL CONNECTION (15 -FT MAXIMUM).
<br />F. BUILDING COMPONENTS ABANDONED BY THE SCOPE OF WORK SHALL
<br />9. WHERE BRANCH CIRCUITS ARE GROUPED, SIZE CONDUIT AND DERATE
<br />BE SECURED TO PREVENT FALLING, LOOSENING, OR CREATING
<br />CURRENT CARRYING CONDUCTORS PER NEC.
<br />DAMAGE OF ANY KIND IN THE FUTURE.
<br />10. PROVIDE UL LISTED HANDLE TIES ON ALL MULTIWIRE BRANCH
<br />17. ETHERNET CABLE:
<br />CIRCUITS PER NEC REQUIREMENTS.
<br />A. FURNISH AND INSTALL JUNCTION BOXES AS SHOWN ON PLANS.
<br />11. SUPPORTS FROM STRUCTURE: NO ATTACHMENT OF ANY TYPE SHALL
<br />PROVIDE CONDUIT AS REQUIRED BY LOCAL CODES AND/OR
<br />BE MADE TO BRIDGING OR JOIST WEB MEMBERS. UTILIZE ONLY THE
<br />ORDINANCES.
<br />TOP AND BOTTOM CHORDS FOR SUPPORTING THE ELECTRICAL
<br />SYSTEM INSTALLATIONS.
<br />B. ETHERNET CABLE IS FURNISHED BY OTHERS.
<br />12. DEVICES SHOWN ON COOLER/FREEZER PANELS SHALL BE SURFACE
<br />C. ELECTRICAL CONTRACTOR SHALL INSTALL CABLE IN POWER POLES.
<br />MOUNTED UNLESS NOTED OTHERWISE. REFER TO ARCHITECTURAL
<br />DOCUMENTS FOR CONDUIT INSTALLATION AND SEALING
<br />D. ELECTRICAL CONTRACTOR SHALL INSTALL OTHER CABLE AS
<br />REQUIREMENTS.
<br />DIRECTED BY WALMART CONSTRUCTION MANAGER.
<br />T
<br />16.470
<br />L4D4-30
<br />11 a mill :1 WA k gi
<br />92219=4
<br />1/8" = 1'-0"
<br />7
<br />t■1
<br />2
<br />NOTE
<br />GENERAL POWER NOTES
<br />11.19.10 EN09
<br />EN02
<br />ARRANGE ALL WORK THAT REQUIRES POWER
<br />1. TELEPOWER POLE(S): MOUNT JUNCTION BOX(ES) TO
<br />INTERRUPTIONS TO THE STORE TO BE ACCOMPLISHED
<br />TOP SIDE OF BOTTOM CHORD OF BAR JOIST. INSTALL
<br />AFTER NORMAL STORE BUSINESS HOURS. NOTIFY THE
<br />FURNISHED PRE -WIRED POWER POLE AND TERMINATE
<br />STORE MANAGER AND THE WALMART CONSTRUCTION
<br />PROVIDED FLEXIBLE CONDUIT AND WIRING TO
<br />MANAGER A MINIMUM OF 48 HOURS IN ADVANCE OF ALL
<br />JUNCTION BOX. PROVIDE UNISTRUT SUPPORTS AND
<br />STORE POWER INTERRUPTIONS. STORE MANAGER MUST
<br />HARDWARE TO SECURE TELEPOWER POLE PLUMB TO
<br />ALLOW FOR POWERING DOWN OF COMPUTER SYSTEMS,
<br />BUILDING STRUCTURE.
<br />MOVING AFFECTED PRODUCT, MODIFICATION OF
<br />255 FT.
<br />WALMART AFTER-HOURS WORK SCHEDULES,
<br />2. PROVIDE LIQUID -TIGHT FLEXIBLE METAL CONDUIT AND
<br />COORDINATION WITH OTHER TRADES, AND OTHER
<br />WIRING FROM DISCONNECT SWITCH OR JUNCTION
<br />CRITICAL SCHEDULING CONCERNS. PROVIDE
<br />BOX TO EQUIPMENT KNOCKOUT OR ELECTRICAL
<br />TEMPORARY POWER AS REQUIRED. INSTALLATION OF
<br />CONNECTION POINT.
<br />NEW EQUIPMENT SHALL BE COMPLETED AND THE
<br />I
<br />POWER SYSTEM TESTED AND RE -ENERGIZED PRIOR TO
<br />3. WHERE EQUIPMENT NAMEPLATE PROTECTIVE DEVICE
<br />START OF BUSINESS THE FOLLOWING MORNING NO
<br />RATING DIFFERS FROM SIZE PROVIDED, CHANGE OUT
<br />LATER THAN A TIME ESTABLISHED BY THE STORE
<br />BRANCH CIRCUIT WIRING AND OVERCURRENT DEVICE
<br />MANAGER AND THE WALMART CONSTRUCTION
<br />TO APPROPRIATE RATING PER NEC.
<br />MANAGER.
<br />~ Z
<br />4. UPON COMPLETION OF ELECTRICAL INSTALLATION
<br />AND PRIOR TO ENERGIZING CIRCUIT:
<br />BAKERY LIGHTING PLAN
<br />1/8" = 1'-0"
<br />1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
<br />{ f
<br />A. INSPECT WIRE AND CABLE FOR PHYSICAL DAMAGE.
<br />B. PERFORM, CONTINUITY TEST.
<br />C. VERIFY PROPER PHASING CONNECTION TO ALL
<br />THREE PHASE MOTOR LOADS.
<br />20A WIRE SIZING SCHEDULE
<br />ALL WIRE SIZES SHOWN ON PANEL SCHEDULES
<br />ARE INTENDED TO BE MINIMUM ACCEPTABLE WIRE
<br />SIZE,
<br />THE FOLLOWING SCHEDULE IS TO BE USED TO SIZE
<br />WIRE FOR 20 AMP CIRCUITS (120 AND 277 VOLT).
<br />LENGHTS (IN FEET) ARE INTENDED TO BE MAXIMUM.
<br />120 VOLT
<br />#12
<br />#10
<br />#8
<br />#6
<br />1-5 AMPS
<br />200 FT.
<br />325 FT.
<br />490 FT.
<br />770 FT.
<br />6-10 AMPS
<br />100 FT.
<br />160 FT.
<br />245 FT.
<br />385 FT,
<br />11-15 AMPS
<br />70 FT.
<br />110 FT.
<br />165 FT.
<br />255 FT.
<br />277 VOLT
<br />#12
<br />#10
<br />#8
<br />#6
<br />1-5 AMPS
<br />480 FT.
<br />760 FT.
<br />1170 FT
<br />1865 FT.
<br />6-10 AMPS
<br />240 FT.
<br />380 FT.
<br />585 FT.
<br />930 FT,
<br />11-15 AMPS
<br />160 FT.,
<br />250 FT.
<br />390 FT.
<br />1 620 FT.
<br />ELECTRICAL KEYNOTES
<br />16.133 EXISTING LIGHT FIXTURES TO BE
<br />RELOCATED TO NEW LOCATION AS
<br />SHOWN.
<br />16.470 FURNISH AND INSTALL NEW 20 AMP,
<br />120 VOLT CIRCUIT(S). FEED FROM
<br />PANELBOARD AS INDICATED. PROVIDE
<br />20A-1 P CIRCUIT BREAKER IF NEEDED.
<br />E.C. SHALL MATCH MANUFACTURER,
<br />TYPE AND AIC RATINGS OF EXISTING
<br />CIRCUIT BREAKERS. E.C. SHALL
<br />VERIFY PRIOR TO ROUGH -IN THAT
<br />EXISTING PANELBOARD HAS SPARE
<br />CAPACITY TO ACCOMMODATE
<br />ADDITIONAL LOAD.
<br />i
<br />. ........... _
<br />nix
<br />4 5 6 7 8 9 10 11 12 13 14 15
<br />1 if = 60'-0"
<br />EXISTING CONDITIONS WERE TAKEN FROM
<br />ORIGINAL DRAWINGS AND MAY NOT REFLECT
<br />EXACT "AS -BUILT" CONDITIONS. CONTRACTOR
<br />SHALL FIELD VERIFY ALL EXISTING CONDITIONS
<br />PRIOR TO SUBMITTINGFINAL BIDS. CONTRACTOR
<br />SHALL CAREFULLY COORDINATE NEW WORK AND
<br />DEMOLITION WITH ALL OTHER DISCIPLINES AND
<br />EXISTING CONDITIONS.
<br />EACH SUBCONTRACTOR IS RESPONSIBLE FOR HAVING
<br />A THOROUGH KNOWLEDGE OF ALL DRAWINGS AND
<br />SPECIFICATIONS IN THEIR RELATED FIELD. THE FAILURE
<br />TO ACQUAINT THEMSELF WITH THIS KNOWLEDGE DOES
<br />NOT RELIEVE THE RESPONSIBILITY OF PERFORMING
<br />THE WORK PROPERLY. NO ADDITIONAL
<br />COMPENSATION SHALL BE ALLOWED BECAUSE OF
<br />CONDITIONS THAT OCCUR DUE TO FAILURE TO
<br />FAMILIARIZE WORKERS WITH THIS KNOWLEDGE.
<br />cwta o Ww�o,
<br />LL ��-�- Fzw Zu
<br />� w
<br />ww roQgao-wacn�m
<br />0 a~ �zza�WU�=ar
<br />U- wm ?ao¢OLL=�Vu~w�
<br />0 �LLwWNDo?z�=z~z
<br />W LLZM �¢WUUOa
<br />~ ?n.. ow QZTXF-QO
<br />0JOQLLtAXO QU w
<br />0 �¢ mZ�Uu)JWWOOE�i
<br />v. �Z WWaW=(Luzo no
<br />U)waZhf=O~aaOwaOF-w
<br />r=-nnw0 u)iaowx_jxv¢t=-
<br />08
<br />QN
<br />�
<br />? Y
<br />�
<br />zs
<br />o
<br />=w
<br />�
<br />v
<br />ao
<br />� �
<br />m
<br />Esuz
<br />W
<br />-
<br />o
<br />I
<br />W
<br />LL
<br />Oa
<br />L
<br />F U
<br />O
<br />tD
<br />~ Z
<br />xa
<br />J
<br />�C>
<br />aC,
<br />m
<br />cwta o Ww�o,
<br />LL ��-�- Fzw Zu
<br />� w
<br />ww roQgao-wacn�m
<br />0 a~ �zza�WU�=ar
<br />U- wm ?ao¢OLL=�Vu~w�
<br />0 �LLwWNDo?z�=z~z
<br />W LLZM �¢WUUOa
<br />~ ?n.. ow QZTXF-QO
<br />0JOQLLtAXO QU w
<br />0 �¢ mZ�Uu)JWWOOE�i
<br />v. �Z WWaW=(Luzo no
<br />U)waZhf=O~aaOwaOF-w
<br />r=-nnw0 u)iaowx_jxv¢t=-
<br />ISSUE BLOCK
<br />CHECKED BY: BW
<br />DRAWN BY: MAP
<br />PROTO: NEW LOOK BAKERY
<br />DOCUMENT DATE: 05/23/17
<br />V -- �5 1 � 10
<br />VINCENT G. MASILIONIS
<br />LICENSE # 68913
<br />BAKERY
<br />POWER
<br />•R s A
<br />SHEET:
<br />E1
<br />QN
<br />�
<br />zs
<br />o
<br />�
<br />cam
<br />� �
<br />m
<br />Esuz
<br />W
<br />zow
<br />�Y
<br />-F:
<br />z
<br />J
<br />CD_
<br />JL
<br />z
<br />z
<br />O
<br />v
<br />ISSUE BLOCK
<br />CHECKED BY: BW
<br />DRAWN BY: MAP
<br />PROTO: NEW LOOK BAKERY
<br />DOCUMENT DATE: 05/23/17
<br />V -- �5 1 � 10
<br />VINCENT G. MASILIONIS
<br />LICENSE # 68913
<br />BAKERY
<br />POWER
<br />•R s A
<br />SHEET:
<br />E1