Laserfiche WebLink
. r . , � <br /> �a. IVlanu�l S Compliance Repor# Job: R0217051 <br /> V4/�19����16� Date: 02-10-17 <br /> Ent6re Unit By: TMN <br /> Bahr's Propane Gas &AC Inc <br /> 4441 Allen Rd,Zephyrhills,FL33541 Phone:813-782-5013 <br /> � <br /> � i ' � • <br /> For: "Typical"- Units 8-2 thru 8-5 <br /> 4408 Court St, Zephyrhills, FL 33542 <br /> • • o � • <br /> Design Cond6tions <br /> Outdoor design DB: 91.0°F Sensible gain: 16322 Btuh Entering coil DB: 81.7°F <br /> Outdoor design WB: 76.0°F Latent gain: 3634 Btuh Entering coil WB: 65.1°F <br /> Indoor design DB: 75 0°F Total gain: 19956 Btuh <br /> Indoor RH: 50% Estimated airflow: 747 cfm <br /> Manufacturer's Per�i rrraance Data atActual Design Conditions <br />� Equipment type: Split AC <br /> Manufacturer: Tempstar or Eqv. Model: N4A324A(G)KC"+EN(A,D)4X24L17**+*9MX'"0401712A'"` <br /> Actual airflow• I747 cfm <br /> Sensible capacity: 16800 Btuh 103% of load <br /> Latent capacity: 5600 Btuh 154% of load <br /> Total capacity: ?2400 Btuh 112% of load SHR: 75% , <br /> • � � <br /> Design Conditions <br /> Outdoor design DB• 41.0°F Heat loss. 11506 Btuh Entering coil DB: 67.3°F <br /> Indoor design DB: 70.0°F <br /> Manufacturer's Perfi.rmance Data atActual Desegn Conc9itions <br /> Equipment type: Elec strip <br /> Manufacturer I Model: <br /> Actual airflow: 261 cfm <br /> Output capacity� 5.0 kW 148% of load Temp. rise: 60 °F <br /> Meets are all requirements of ACCA Manual S. <br /> I 2017-Feb-'10 12:07•13 <br /> � � v�reghtsof�` Right-SuiteO Universal 2017 17.0.10 RSU07440 Page 1 <br /> � .Butterfield 6 PIex�R0217051 Unit 8-1 to 8-5.rup Calc=MJS Buitding Front faces: N <br />