Laserfiche WebLink
� � • � • <br /> HEATING&AIR CONDITIONIIVG <br /> 1512 E.GARY RD <br /> LAKEI.AND FL 33801 <br /> OR�AhiDo 407-COOLING-TAMPA/LAKEI.AND 863-940-9800 <br /> 03/22/2017 <br /> State Pronerty Management <br /> 38100 Townview Ave#205 HVAC <br /> Zephyrhills,FL 33542 <br /> WO#1687-1 <br /> • Split electric system 2 ton(R-22) <br /> • The air handler is 15 years old in poor condition; Interior evaporator coil is heavily rusted showing signs <br /> formicaria corrosion,Blower wheel is caked with dirt and debris effecting the system from running at its maximum <br /> efficiency <br /> • Support box will need to be installed to fit the new unit and support system properly <br /> • The AC is 16 years old in poor condition; System was found void of refrigerant leaving volatile acids in the <br /> system causing an extensive amount of damage among the condenser coils; Unit is R-22 and recommended <br /> ' replacing due to the fact that R-22 units are becoming obsolete rendering the issue of costly repairs if needed <br /> • Ductwork is in fair condition <br /> • Some sheetrock may need to be trimmed or cut to install the new equipment and it will be the responsibility of ' <br /> the GC for repairs , <br /> • 150 Amp panel '� <br /> Service comnleted: <br /> Diagnostic$59.00(waived if system is replaced) � <br /> Option#1 Service . <br /> Service needed: <br /> Leak search$149.00 , <br /> Recover refrigerant$99.00 <br /> Replace condenser coil$1,352.00 <br /> Pull and clean evaporator coil$199.00 <br /> Filter drier and evacuation$149.00 <br /> Repair suction line$99.00 <br /> Replace dual value capacitor$149.00 <br /> Repair low voltage wire at outdoor unit$90.00 <br /> Pull and clean blower assembly$89.00 <br /> Incurred cost$59.00 <br /> Total: $2,434.00 <br /> *System may need further repairs* <br />