Laserfiche WebLink
° � Manual S Compliance Report Job: 2600sf <br /> Date: 1l3/2017 <br /> En tire Ho use By: Dave <br /> BAYONET PLUMBING COOLING HEATING ' <br /> ' • - s • <br /> For: Lennar Homes <br /> • e . • . <br /> Design Conditions <br /> Outdoor design DB: 91.3°F Sensible gain: 34401 Btuh Entering coil DB: 75.6°F <br /> Outdoor design WB• 77.3°F Latent gain: 4401 Btuh Entering coil WB. 62.8°F <br /> Indoor design DB. 75.0°F Total gain: 38802 Btuh <br /> Indoor RH: 50% Estimated airflow: 1400 cfm <br /> Manufacturer's Performance Data at Actual Design Conditions <br /> Equipment type: SpIitASHP <br />, Manufacturer: Lennox Model: 14HPX-042-230-18+CBX27UH-042-230'`++TDR <br /> Actual airtlow: 1400 cfm <br /> Sensible capacity: 36975 Btuh 107% of load <br /> Latent capacity: 6525 Btuh 148% of load <br /> Total capacity� 43500 Btuh 112% of load SHR. 85% <br /> i <br /> • e • <br /> Design Conditions ' <br /> Outdoor design DB. 30.8°F Heat loss: 39282 Btuh Entering coil DB. 69.7°F <br /> Indoor design DB: 70.0°F <br /> Manufacturer's Performance Data at Actual Design Conditions <br /> Equipment type: SpIitASHP <br /> Manufacturer: Lennox Model: 14HPX-042-230-18+CBX27UH-042-230*++TDR ' <br /> Actual airflow� 1400 cfm <br /> Output capacity: 43500 Btuh 111% of load Capacity balance: 36 °F <br /> Supplemental heat required: 0 Btuh Economic balance: -99 °F <br /> Backup equipment type: Elec strip , <br /> Manufacturer n/a Model: n/a+n/a <br /> Actual airflow: 1400 cfm <br /> Output capacity: 0 kW 0% of load Temp. rise: 0 °F <br /> The above equipment was selected in accordance with ACCA Manual S <br /> .� wri htsoft 2o17-Jan-03 09:09:12 <br /> �,�„� 9 Right-Suite�Universal 2013 13.0.09 RSU05714 Page 1 <br /> �'� H:\LENNAR LOADS12fi00 sf ADS drewn 3.5 ton.rup Calc=MJ8 Front Door faces: E <br /> I <br />