Laserfiche WebLink
Building Analysis Job: 2575 sf Ap5 A elevation <br /> date: 12/30/2�16 <br /> lowerfloor gY: oaV� <br /> BAYONET PLUMBING COOLING HEATING <br /> ' • � a s <br /> For: Lennar Homes <br /> � - o e • • <br /> Locatian; lndoor: Heating Coaling <br /> Tampa international AP, FL, US Indoor temperature(�F) 70 75 <br /> Elevatian: 10 f# Design TD (°F) 39 16 <br /> L.atitude: 28°N Relative humidity{°!o} 50 5� <br /> Outdoor: Heating Cooling Moisture difference(gr/ib} 34.7 54.7 <br /> Dry bulb(°F) 31 91 Infiltration: <br /> Daily range(°F} - 14 ( L } Method Simplified <br /> Wet bulb(°F) - 77 Constructian quality Semi-tight <br /> Wind speed(mph) 15.0 7.5 Fireplaces 0 <br /> e <br /> Component BtuhlftZ Btuh % of{oad <br /> Walis 5.5 5196 31.8 <br /> Glazing 30.2 2683 16.A - <br /> Daors 23.5 466 2.9 <br /> Ceilings 1.8 57 0.4 <br /> Flaors 4.1 4478 27.4 <br /> lnfiltratian 1.9 2036 12.5 <br /> Ducts 14Q0 8.6 <br /> Piping 0 0 ,� <br /> Flumidificatian 0 0 <br /> Ventiiation 0 0 , "" <br /> Adjustments 0 °-• '- <br /> Tatal 16347 100.0 <br /> • o • <br /> Component Btuh/ftZ Btuh % of load <br /> Vilalis 2.8 2644 23.2 � <br /> Glazing 56.6 5032 44.1 �' <br /> Daors 18.4 365 3.2 <br /> Ceilings 2.0 64 0.6 <br /> Floors 0 0 0 <br /> Infiltration 0.4 454 4.0 <br /> Ducts 1655 14.5 <br /> Ventilation 0 0 <br /> lnternal gains 1200 10.5 �" <br /> Blower Q 0 <br /> Adjustments 0 <br /> Total 11413 100A � <br /> Latent Cooling Load= 1235 Btuh <br /> Overall U-value= 0.151 B#uh/ft2-°F' <br /> Data entries checked. <br /> ,�, Wrl htSOft" 2016-Dec-30 07•49:08 <br /> ^.. � 9 Right-Sufte�Universal 2013 13.0.09 RSU�5714 p�ge� <br /> �H:ILENNAft LQAdS12575 sf ADS-A etv 1.5-2ton.rup Catc=M.18 Frarrt Roor faces; S <br />