Xenan fiash#ube enclosed in a rugged Lexan�'Iens. The , shall be able to be synchronized on a 2-wire circuit with
<br /> strobes shall be available with two or four field select- the capability to silence the audible if required. ,If the
<br /> abie settings in one unit and shall be rated, per UL 1971, sync module ar pawer supply fails to aperate{i.e., con- '
<br /> for up to 185 cd for wa11 mounting and 177 cd for ceiling tacts remain closed}, the strobes shali revert to a non-
<br /> mounting. The strobes shall operate aver an extended synchronized flash rate. All notification appliances shall
<br /> temperature range of 32°F to'i 2�°F{0°C to 49°C}and be Iisted for"Special Applications".
<br /> be listed for maximum humidity of 95°/a RH. Strobe • Strobes are designed to flash at 1 flash per second
<br /> inputs shal! be polarized for campatibility with standard minimum over their"Reguiated lnput Vaftage Range".
<br /> reverse polarity supervision of circuit wiring by a Fire
<br /> Alarm Control Panel (FACP). • All candela ratings represent minimum effective strobe
<br /> Audibies and Audible/Strobe Combinations intensity based an U�Standard 197'1.
<br /> Horns and horn/strobes shall be listed for Indoor use un- ' Series ZM Strobe products are listed under UL Stan-
<br /> der UL Standard 464.The horns shall be abie ta produce dards 1971 and 464 for indoor use with a temperature
<br /> range of 32 F to 120 F(0 C to 49 C) and maximum
<br /> a continuous output or a#emporal code-3 output that can humidity of 93% (±2%).
<br /> be synchronized.The horns shall have at least 2 saund
<br /> Ievel settings of 90 and 95 dBA. � Series ZH horns are listed under UL.Standard 464 far
<br /> Synchronization Modules audible signal appliances (Indoor use only).
<br /> When synchronization of strobes or temporal Code-3 au- '�-eChtllCa� �tl'�OCIt11t10C1
<br /> dibles is reguired, the appliances shall be synchronized
<br /> using the Siemens DSC sync modules, FS-250 panels, For comp(ete technical information, please consuit the
<br /> XLS panels, or PAD-3 pawer suppies with built-in sync relevant installation sheets as well as the Siemens
<br /> protacoL The strobes shall not drift aut af synchraniza- Compatibility Guide.
<br /> tion at any time during operatian. Audibles and strobes
<br /> Ordering Information 1 Mounting Requirements 1 Approvals
<br /> Ntounting Agency Approvals
<br /> Model Flumber Order Code pptions#
<br /> UL ULC CSFM FM
<br /> ZH-MC-R 5dd-636'161 8,D,E,F X # # #
<br /> ZH-MC-W 5q0-63B162 B,D,E,F X # # #
<br /> ZN-HMC-R 500-636163 B,D,E,F X # # #
<br /> ZH-HMC-W 500-636164 B,D,E,F X # # #
<br /> ZH-R 500-636159 B,D,E,F X # # #
<br /> ZH-W 500-636160 B,D,E,F X # # #
<br /> ZH-MC-CR 500-636165 B,D,E,F X # # #
<br /> ZH-MC-CW 500-636166 B,D,E,F X # # #
<br /> ZH-FiNIG-GR 500-636'167 B,D,E,F X # # #
<br /> ZH-HMGCW 500-636168 B,D,E,F X # # #
<br /> ZR-ivIC-R 5QQ-636169 B,D,E,F X # # ##
<br /> ZR-MC-W 500-636170 B,D,E,F X # # #
<br /> ZR-HMG-R 5Q0-636171 B,D,E,F X # # #
<br /> ZR-HMC-W 500-636172 B,D,E,F X # # #
<br /> ZR-MGCW 500-636174 B,D,E,F X # # #
<br /> ZR-MGCR 500-636173 B,D,E,F X # # #
<br /> ZR-HMC-CR 500-636175 8,D,E,F X # # #
<br /> ZRS-HMC-CW 500-83&176 B,D,E,F' X # # #
<br /> ZBB-R 500-636193 Accessory-Includes base,dust cover,mounting screws and installation sheet
<br /> ZB8-W 5d0-636194 Accassory-(ncludes base,dust cover,mounting screws and insfaliatian sheet
<br /> X=listed/approved #=pending *= Refer to Data Sheet#2585 for mounting options.
<br /> WARNING: PLEASE READ THESE SPECIFICATIONS AND INSTALLATION 1NSTRUCTfONS CAREFULLY BEFORE
<br /> USWG, SPECIFYING OR APPLYING THIS PRODUCT. FAILURE TO COMPL.Y WITH ANY OF THESE WS7RUCTlONS,
<br /> CAUTIONS AND WARNINGS COU�D RESU�T IN IMPROPER APPL.ICAI'ION, INSTAC.LATIUN ANC}lOR ORERATION
<br /> OF THESE PRODUCTS IN AN EMERGENCY SITUATI�N, WHICH COUL.D RESULT IN PROPERTY DAMAGE, AND
<br /> SERIOUS INJURY QR DEATH TO YOU AND(OR(?THERS.
<br /> Fire Safety Fire Safety
<br /> 8 pernwood Road 2 Kenview Boulevard
<br /> Plorham Park,NJ 07932 7I07 8rampton,Qntaria
<br /> Siemens BuildingTechnalogies Tei:(973)593-2600 5M Canada L6T5E4
<br /> FqX.(973)593-6670 SFS-IG Tel:(905)799-9937 July 2007
<br /> Fire Safety Website:www.sbt.siemens.comlfis Printed in U.S.A. FAX:{9Q5)799-9858 Now tssve