Laserfiche WebLink
Final Calculations - Hazen-Williams • � , • <br /> Beneficial Fire Protection ' • Page 6 <br /> HARBOR FREIGHT TOOLS Date 062317 <br /> Hyd. Qa Dia. Fitting Pipe Pt Pt <br /> Ref. "C" or Ftng's Pe Pv **""'*'`* Notes "'`*'`** <br /> Point Qt Pf/Ft Eqv. Ln. Total Pf Pn <br /> 0.0 <br /> 92.60 26.406 K Factor= 18.02 <br /> "P-6 <br /> 22 14.21 1.728 T 11.29 57.540 19.327 <br /> to 120.0 0.0 11.290 0.0 <br /> 1 M 14.21 0.0061 0.0 68.830 0.418 Vel = 1.94 <br /> 1 M 34.12 1.728 T 11.29 104.330 19.745 K Factor @ node EQ01 <br /> to 120.0 0.0 11.290 0.0 <br /> 32 48.33 0.0586 0.0 115.620 6.770 Vel = 6.61 <br /> 0.0 <br /> 48.33 26.515 K Factor= 9.39 <br /> 'P-7 i <br /> 23 38.76 1.728 2T 22.58 162.000 19.497 <br /> to 120.0 0.0 22.580 0.0 <br />' 33 38.76 0.0389 0.0 184.580 7.186 Vel = 5.30 <br /> 0.0 <br /> 38.76 26.683 K Factor= 7.50 <br /> *P-8 <br /> 24 39.17 1.728 2T 22.58 162.000 19.578 <br /> to 120.0 0.0 22.580 0.0 <br /> 34 39.17 0.0397 0.0 184.580 7.328 Vel = 5.36 <br /> 0.0 <br /> 39.17 26.906 K Factor= 7.55 <br /> I * - <br /> P9 <br /> 25 39.92 1.728 2T 22.58 162.000 19.601 <br /> to 120.0 0.0 22.580 0.0 <br /> I 35 39.92 0.0411 0.0 184.580 7.591 Vel = 5.46 <br /> 0.0 <br /> 39.92 27.192 K Factor= 7.66 <br /> *P-10 <br /> 20 65.96 3.314 0.0 13.330 19.058 <br /> to 120.0 0.0 0.0 0.0 <br /> 21 65.96 0.0044 0.0 13.330 0.058 Vel = 2.45 <br /> 21 66.10 3.314 0.0 13.330 19.116 <br /> to 120.0 0.0 0.0 0.0 <br /> 22 132.06 0.0158 0.0 13.330 0.211 Vel = 4.91 <br /> 22 -14.20 3.314 0.0 13.330 19.327 <br /> to 120.0 0.0 0.0 0.0 <br /> 23 117.86 0.0128 0.0 13.330 0.170 Vel = 4.38 <br /> 23 -38.77 3.314 0 0 13.330 19.497 <br /> to 120.0 0.0 0.0 0.0 <br /> 24 79.09 0.0061 0.0 13.330 0.081 Vel = 2.94 <br /> 24 -39.17 3.314 0.0 13.330 19.578 <br /> to 120.0 0.0 0.0 0.0 <br /> 25 39.92 0.0017 0.0 13.330 0.023 Vel = 1.48 <br /> 0.0 <br /> 39.92 19.601 K Factor= 9.02 <br /> Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 <br /> I <br />