Laserfiche WebLink
: , . <br /> Manual S Compliance Report Job: 2386BsfADS <br /> Date: 6/73/2017 <br /> En tire Ho us e By: Dave <br /> Bayonet-Plumbing Heating and Air - <br /> " s - s s <br /> For: Lennar Homes <br /> • • Y 0 6 <br /> Design Conditions , <br /> Outdoor design DB 91.3°F Sensible gain: 31270 Btuh Entering coil DB 75.6°F <br /> Outdoor design WB: 77.3°F Latent gain: 5526 Btuh Entering coil WB 62.8°F <br /> Indoor design DB: 75.0°F Total gain: 36796 Btuh <br /> Indoor RH. 50% Estimated airflow: 1400 cfm <br /> Manufacturer's Performance Data atActual Design Conditions <br /> Equipment type: SpIitASHP <br /> Manufacturer� Lennox Model: 14HPX-042-230-21+CBA27UHE-042-230*++TDR <br /> Actual airtlow: 1400 cfm <br /> Sensible capacity� 35700 Btuh 114% of load <br /> Latent capacity: 6300 Btuh 114% of load <br /> Total capacity� 42000 Btuh 114% of load SHR. 85% <br /> e • . <br /> Design Conditions <br /> Outdoor design DB� 30.8°F Heat loss. 32596 Btuh Entering coil DB 69.7°F <br /> Indoor design DB� 70.0°F <br /> Manufacturer's Performance Data at Actual Design Conditions <br /> Equipmenttype: SpIitASHP <br /> Manufacturer Lennox Model: 14HPX-042-230-21+CBA27UHE-042-230*++TDR <br /> Actual airflow: 1400 cfm <br /> Output capacity: 42000 Btuh 129% of load Capacity balance: 24 °F <br /> _ Supplemental heat required: 0 Btuh Economic balance: -99 °F <br /> i Backup equipment type: Elec strip <br /> Manufacturer n/a Model: n/a+n/a <br /> Actual airflow: 1400 cfm <br /> Output capacity: 0 kW 0% of load Temp. rise: 0 °F <br /> Meets are all requirements of ACCA Manual S. <br /> ,�. wri htsoft` 2017-Jun-13 08:27:32 <br /> ��� 9 Right-Suite�Universal 2017 17.023 RSU05714 page 1 <br /> ...with CBA27UHE AH's12386B sf ADS-ABO 3.5 ton.rup Calc=MJ8 Front Door faces: S <br />