Laserfiche WebLink
1035 Pine Hollow Point Dr F I RETRO N I CS Altamonte Springs,FI.32714 <br /> phone(407)774-6900/fax 774-2074 <br /> HARBOR FREIGHT F.A.C.P./SIGNAL EXPANDER CALC'S. <br /> DATE 5939 GALL BLVD <br /> 09/06/17 � <br /> NEW FACP ADDITION <br /> # x = SUPERVISORY CURRENT STATUS. CHANGED <br /> DEVICES DRAW TOTAL <br /> 1> SD505-APS/SMOKE DETECTOR PANEL= 5700> 1X.2 = .2 <br /> 1 0.00055 0.00055 <br /> 4> SD505-DUCTR/DUCT DETECTOR 0.2 AMPS (PANEL ONLY) <br /> 4 0.02 0 08 0 AMPS (EXISTING SYSTEM) <br /> 4> RTS2-AOS/REMOTE TEST STATION + 0 0942 AMPS (NEW DEVICES) <br /> 4 0.003 0.012 0.2942 AMPS (ALL DEVICES) <br /> 1> SD500-PS/PULL STATION x 24 H�URS SUPERVISORY <br /> 1 0.00055 0 00055 7 0608 TOTAL AMP HOURS (SUPV) <br /> 2> SD500-MIN/INPUT MODULE <br />� 2 0.00055 0 0011 <br /> 0 0 0 <br /> 0 0 0 <br /> 0 0 0 <br /> 0 0 0 BACKUP GENERATOR: NO <br /> # x = ALARM CURRENT STATUS: CHANGED <br /> DEVICES DRAW TOTAL <br /> 1> SD505-APS/SMOKE DETECTOR PANEL= 5700> 1X.325 = 325 <br /> 1 0.00055 0.00055 <br /> 4> SD505-DUCTR/DUCT DETECTOR 0.325 AMPS (PANEL ONLY) <br /> 4 0.062 0.248 0 AMPS (EXISTING SYSTEM) <br /> 4> RTS2-AOS/REMOTE TEST STATION + 0.6182 AMPS (NEW DEVICES) <br /> 4 0.055 0.22 0 9432 AMPS (ALL DEVICES) <br /> 1> SD500-PS/PULL STATION x 0.0833 HOURS ALARM (5 MINUTES)" <br /> 1 0.00055 0.00055 0 078569 TOTAL AMP HOURS (ALARM) <br /> 2> SD500-MIN/INPUT MODULE *�5 MIN= 0833/15 MIN=.2499� <br /> 2 0.00055 0.0011 ENGINEERING <br /> 1> HS/HORN STROBE 75cd SUPERVISORY CURREN' 7.0608 <br /> 1 0.148 0 148 ALARM CURRENT 0 078569 <br /> TOTAL COMBINED AH REQUIRE 7 139369 <br /> O O O MULTIPLY BY THE DERATING FACTO 1.2 <br /> MINIMUM BATTERY AH REQUIRE 8 567242 <br /> O O O BATTERY CAPACITY PROVIDEC 14 <br /> 0 0 0 <br /> 0 0 0 I <br />