Laserfiche WebLink
�ingle Family Dwelling <br /> Plan Review Comments <br /> 1. F.F.E. shall be a minimum of$" above the road elevation and an engineered site plan. <br /> 2. Lots shall be graded to comply with R401.3 of the F.B.C. <br /> 3. Compaction test required if 24" or more of fill dirt is brought in at any one place. <br /> 4. Tie in survey required before pouring cancrete. <br /> 5. Driveways require a R.O.W. use permit. All 4 sides af driveway thru the sidewalk shall have <br /> expansian material. <br /> 6. All setbacks shall be met. <br /> 7. All property markers shall be uncavered and marked at time af first inspec�ion. <br /> 8. All A.D.A. requirements shall be met. <br /> 9. No electric, plumbing, mechanical, or framing shall be covered without an inspection and <br /> approval first. <br /> 10. AIl Garages shall camply with section R302.6 of the F.B.C. {Fire Separation}. <br /> 11. Appliances shall not be installed in a location where subject to:mechanical damage unless <br /> protected by approved barriers. IV1303.4 af the F.B.0 <br /> 12. Water heaters shall comply with section P607.3 of the F.B.C. <br /> 13. Faundation supports for A1C units sha11 be raised at Ieast 3"abave finished grade. M1308.1 <br /> 14. Return air in all bedrooms. F.B.C. M1620.4 <br /> 15. Smoke detectars are to be installed in accardance wzth R313.1 of the F.B.C. <br /> 16. All glazing requirements are to be in accardance wit11 R308.4 af the F.B.C. <br /> 17. AII means of egress are to be in accordance with R31 I of the F.B.C. <br /> 18. "Green gypsum board" shall not be used as a backer in shawers or tubs. R702.4.2 F.B.C. <br /> 19. Combination-type AFCI breakers are required at all locatzons requiring an AFCI type breaker. <br /> 20. Carbon monoxide alarms will be required in new canstruction that uses fossil-burning heating <br /> or appliances or an attached garage. They shali be znstalled in accordance with�he F.B.C. <br /> 21. All plurnbing, mechanical, and electrical shall be separate from unit ta unit. This includes all <br /> underground plumbing and electric. <br /> 22. All 2008 N.E.C. Codes will be enfarced. <br /> 23. Tamper-Resistan�Receptacles in accordance with 40b.11 of the 200$N.E.0 <br /> 22. In accordance with the Land Development Code, lots shall be sodded before final at least 10 <br /> feet around the structure. <br /> F.F.E.-Finished Floor Elevatipn <br /> F.B.C- Florida Building Code 5�'Edition <br /> R.O.W.-Right af Way <br /> A.D.A.-Americans with Disabilities Act N.E.C.-National Electric Code(2008) <br /> \ <br />