Laserfiche WebLink
� Manual S Compliance Report Job: 1791Asf ADS <br /> Date: 911312017 <br /> Entire House By: Dave <br /> Bayonet Plumbing Heating and Air <br /> ' � - • • <br /> For: Lennar Homes <br /> • • • • • <br /> Design Conditions <br /> Outdoor design DB: 91.3°F Sensible gain: 22922 Btuh Entering coil DB� 75.7°F , <br /> Outdoor design WB: 77.3°F Latent gain: 3775 Btuh Entering coil WB. 62.8°F <br /> Indoor design DB: 75.0°F Total gain: 26698 Btuh ' <br /> Indoor RH: 50% Estimated airflow: 1000 cfm <br /> Manufacturer's Performance Data at Actual Desi n Conditions <br /> 9 <br /> Equipment type: SpIitASHP <br /> Manufacturer: Lennox Model: 14HPX-030-230-21+CBA27UHE-030-230'`++TDR <br /> Actual airflow: 1000 cfm <br /> Sensible capacity: 25500 Btuh 111% of load <br /> Latent capacity: 4500 Btuh 119% of load <br /> Total capacity: 30000 Btuh 112% of load SHR. 85% <br /> • • • <br /> Design Conditions <br />' Outdoor design DB: 30.8°F Heat loss 25706 Btuh Entering coil DB: 69.6°F <br /> Indoor design DB� 70.0°F <br /> Manufacturer's Performance Data at Actual Design Conditions <br /> Equipment type: Split ASHP <br /> Manufacturer: Lennox Model: 14HPX-030-230-21+CBA27UHE-030-230*++TDR <br />� Actual airflow: 1000 cfm <br /> Output capacity: 26000 Btuh 101% of load Capacity balance: 31 °F <br /> Supplemental heat required: 0 Btuh Economic balance: -99 °F <br /> Backup equipment type: Elec strip <br /> Manufacturer: n/a Model: n/a+n/a <br /> Actual airflow: 1000 cfm <br /> Output capacity: 0 kW 0% of load Temp. rise: 0 °F <br /> Meets are all requirements of ACCA Manual S <br /> ..: wri htsoft� 2017-Sep-1310:11:14 I <br /> �, 9 Right-Suite�Universal 2017 17.0.23 RSU05714 Pa9e� I <br /> �� CBA27UHE AH's\1791A sf ADS template 2.5ton.rup Calc=MJ8 Front Door faces: W <br />