Laserfiche WebLink
. Job: C0117003 � <br /> .- �" wrightsoft° RightSuiteO Universal 2017 Load Summary i <br /> AHU5 Byte� JND .�� <br /> Randy Watson Designs, Inc <br /> � <br /> 73821 US Highway 98 By Pass,Dade City,FL 33525 Phone:352-523-2077 i <br /> � • ' • • <br /> For: Sunrise Manufacturing � <br /> Zephyrhills, FL <br /> Zone: AHU5 COOLING LOAD , <br /> 1. DESIGN CONDITIONS at Jul 1800 LDT Peak load at Jul 1800 LDT <br /> Inside: 78 °F Outside: 90 °F TD: 12 °F � <br /> RH: 56 % MoistDiff: 46.9 gr/Ib Mult: 1.0 Ins.wb 65 °F , <br /> Sensible Latent <br /> . 2. SOLAR RADIATION THROUGH GLASS 0 - ' <br /> 3. TRANSMISSION GAINS Sensible 23379 - � <br /> Walls: 17506 - - ' <br /> Glass: 0 - - � <br /> Doors: 1542 - - <br /> Partitions: 0 - - � <br /> Floors: 0 - - <br /> Ceilings: 4331 � <br /> 4. INTERNAL HEAT GAIN Sensible � Latent 13381 6250 - <br /> Occupants: 2138 3750 - - � <br /> Lights: 3140 - - - i <br /> Motors: 0 - - - ' ; <br /> Appliances: 8103 2500 - - i <br /> 5. INFILTRATION: Outside air cfm: 0 0 0 <br /> 6. SUBTOTAL: Space load Sensible Latent 36760 6250 � <br /> Envelope 36760 6250 - - <br /> Less external 0 - - - ' <br /> Redistribution 0 0 - - , <br /> 7. SUPPLY DUCT 0 - <br /> _ 8. SUBTOTAL: Space load+ supply duct 36760 - , <br /> Actual cfm: 1900 at supply TD: 23 - - <br /> 9. VENTILATION: Mak�up air cfm: 162 2139 5168 ! <br /> 10. RETURNAIR LOAD: Lighting+ plenum (net) 0 - <br /> 11. RETURN DUCT 0 - ' <br /> 12. TOTAL LOADS ON EQUIPMENT 38900 11418 � <br /> HEATING LOAD ; <br /> 13. DESIGN CONDITIONS MUIt: 1.0 � <br /> Inside: � 70 °F Outside: 43 °F TD: 27 °F <br /> 14. TRANSMISSION LOSSES 29178 � <br /> Walls: 19822 - i <br /> Glass: 0 - <br /> Doors: 1604 - <br /> Partitions: 0 - i <br /> Floors. 4020 - i <br /> Ceilings: 3732 - <br /> 15. INFILTRATION: Outside air cfm: 0 0 � <br /> 16. SUBTOTAL: Space load 29178 <br /> Envelope 29178 - <br /> Less external 0 - j <br /> Less transfer 0 - i <br /> Redistribution 0 I <br /> 17. SUPPLY DUCT: 0 � <br /> 18. VENTILATION: Make-up air cfm: 162 4827 ! <br /> 19. HUMIDIFICATION 1960 <br /> Piping 0 <br /> 20. RETURN DUCT 0 <br /> 21. TOTAL HEATING LOAD ON EQUIPMENT 35965 � <br /> � WI'1 htsoft° 2017-.1an-11 �5:47:ss � <br /> 9 Right-Suite�Universal 2017 17.0.10 RSU07440 Page 5 <br /> \C0717003-Sunrise Manufacturing\C0117003b.rup Calc=MNS House Front faces:SE <br />