Laserfiche WebLink
I <br /> � <br /> ; i <br /> Right-SuiteO Universal 2017 Load Summary Job: C0117003 i <br /> _ � wrightsoft° Date: 01-03-17 <br /> Corridor2 By: JND � <br /> Randy Watson Designs, Inc I <br /> - i <br /> 13821 US Hlghway 98 By Pass,Dade City,FL 33525 Phone:352-523-2077 I <br /> � • ' • • � <br /> For: Sunrise Manufacturing � <br /> Zephyrhills, FL � <br /> � <br /> Zone: Corridor2 COOLING LOAD , <br /> 1. DESIGN CONDITIO1vS at Jul 1800 LDT Peak load at Jul 1600 LDT , <br /> Inside: 75 °F Outside: 90 °F TD: 15 °F <br /> RH: 56 % MoistDiff: 53.9 gr/Ib Mult: 1.0 Ins.wb 63 °F <br /> Sensible Latent <br /> 2. SOLAR RADIATION THROUGH GLASS 0 - � <br /> 3. TRANSMISSION GAINS Sensible 0 - i <br /> Walls: 0 - - ' <br /> Glass: 0 - - - <br /> Doors: 0 - - � <br /> Partitions: 0 - - <br /> Floors: 0 - - ! <br /> Ceilings: 0 - - � <br /> 4. INTERNAL HEAT GAIN Sensible Latent �2785 0 � , <br /> Occupants: 0 0 - - ; <br /> Lights: 564 - - - <br /> Motors: 0 - - <br /> Appliances: 2221 0 - - � <br /> 5. IIYFILTRATION: Outside air cfm: 0 0 0 , ; <br /> 6. SUBTOTAL: Space load Sensible Latent 2785 0 � � <br /> Envelope 2785 0 - - <br /> Less external 0 - - - <br /> Redistribution 0 0 - - <br /> 7. SUPPLY DUCT 0 - <br /> 8. SUBTOTAL: Space load+supply duct 2785 - <br /> Actual cfm: 153 at supply TD: 20 , <br /> 9. VENTILATION: Make-up air cfm. 18 301 668 <br /> 10. RETURNAIR LOAD: Lighting+ plenum (net) 0 - <br /> 11. RETURN DUCT 0 - <br /> 12. TOTAL LOADS ON EQUIPMENT 3086 668 <br /> HEATING LOAD <br /> 13. DESIGN CONDITIONS Mult: 1.0 i <br /> Inside: 70 °F Outside: 43 °F TD: 27 °F � <br /> 14. TRANSMISSION LOSSES 0 � <br /> Walls: 0 - ' <br /> Glass: 0 - <br /> Doors: 0 - <br /> Fartitions: 0 - <br /> Floors: 0 - � � <br /> Ceilings: 0 - <br /> 15. INFILTRATION: Outside air cfm: 0 0 <br /> 16. SUBTOTAL: Space load 0 � <br /> Envelope 0 - I <br /> Less external 0 - i <br /> Less transfer 0 - � <br /> Redistribution 0 - � <br /> 17. SUPPLY DUCT: 0 <br /> 18. VENTILATION: Make-up air cfm: 18 543 � <br /> 19. HUMIDIFICATION 221 ; <br /> Piping 0 � <br /> 20. RETURN DUCT 0 <br /> 21. TOTAL HEATING LOAD ON EQUIPMENT 764 <br /> WI'1 �'ItSOft° 2017-Jan-1115:47:56 <br /> g Right-SuiteQ�l Universal 2017 17 0.10 RSU07440 Page 10 <br /> 1C0117003-Sunrise Manufacturing\C0117003b.rup Calc=MN5 House Front faces:SE , <br />