Page 1 Commercial Heat Loss and Heat Gain Calculation 2/16/2018 <br /> Report Prepared By: <br /> W Barnett Enterprises, Inc <br /> For. LAKESIDE PHARMACEY[Copy 1] <br /> 38101 5TH AVENUE <br /> ZEPHERHILLS, FLORIDA 33542 <br /> Design Conditions: Lakeland; Latitude:28; Time 10:00 AM <br /> Indoor. Outdoor. <br /> Summer temperature: 75 Summer temperature: 91 <br /> Winter temperature: 72 Winter temperature: 41 <br /> Relative humidity: 50 Summer grains of moisture: 113 <br /> Daily temperature range: 17 <br /> Total Cooling Load: 94,876 BTU H 8 tons <br /> Sensible: 47,937 <br /> Latent: 46,939 <br /> Total Heating Load: 43,735 BTUH <br /> HVAC-Calc Commercial 4.0 by HVAC Computer Systems Ltd. 888 736-1101 <br /> Load calculations are estimates only,actual loads may vary due to weather and construction differences. <br />