Laserfiche WebLink
Page I Commercial Heat Loss and Heat Gain Calculation, 2/16/2018 <br /> Report Prepared By: <br /> W Barnett Enterprises, Inc <br /> For LAKESIDE PHARMACEY[Copy 1] <br /> 38101 5TH AVENUE <br /> ZEPHERHILLS, FLORIDA 33542 <br /> Design Conditions: Lakeland; Latitude:28; Time 10:00AM <br /> Indoor. Outdoor. <br /> Summer temperature: 75 Summer temperature: 91 <br /> Winter temperature: 72 Winter temperature: 41 <br /> Relative humidity: 50 Summer grains of moisture: 113 <br /> Daily temperature range: 17 <br /> Building Component Sensible Latent Total Total <br /> Gain Gain Heat Gain Heat Loss <br /> (BTUH) (BTUH) (BTUH) (BTUH) <br /> People 11,550 19,950 31,500 0 <br /> Lights 26,384 0 26,384 0 <br /> Ventilation . 2,772 20,992 23,764 21,483 <br /> Door Leakage792 5,997 6,789 10,912 <br /> Walls 1,726 0 1,726 4,984 <br /> Duct 1,396 0 1,396 2,083 <br /> Ceilings 1,283 0 1,283 2,604 <br /> Windows 952 0 952 826 <br /> Doors 832 0 832 843 <br /> Miscellaneous 250 0 250 0 <br /> Infiltration 0 0 0 0 <br /> Skylights 0 0 0 0 <br /> Partitions 0 0 0 0 <br /> Floors 0 0 0 0 <br /> Whole Building-All Components 47,937 46,939 94,876 43,735 <br /> 8 tonss <br /> HVAC-Calc Commercial 4.0 by HVAC Computer Systems Ltd. 888 736-1101 <br /> Load calculations are estimates only,actual loads may vary due to weather and construction differences. <br />