Single Family Dwelling <br /> Pl <br /> an Review Comments <br /> 1. F.F.E. shall be a minirnum of.8"above the road elevation and an engineered site plan. <br /> I. 'Lots"shall be-graded.to comply with R401.3 of the F.B.C. <br /> 3. Compaction-test required.if 24" or more of fill dirt is brought in at any one place: <br /> 4:. :Tie in survey required before pouring concrete.. <br /> . .. 5. "Driveways:require a R.-O.W. use permit: All.4 sides of driveway."thru the sidewalk shall have <br /> expansion material.. <br /> 6. All setbacks shall be met... . <br /> .7. All property markers"shall be,uncovered and marked at time of first:inspection: <br /> 8: " All A.D.A:requirements shall be met.:'- <br /> 9.. "No electric;plumbing,-mechanical; or-framing shall b,e covered without an-inspection.and <br /> :approval first. . <br /> l0.All Garages shall comply with section R302:6.of the F.B.C...(Fire Separation). <br /> 11.Appliances"shall not:be installed in a location where subject to"rechanical darriage unless <br /> protected:by approved barriers. "M303.4 of the F.B.C. <br /> 12. Water heaters shall comply with section P607.3 of the F.B.C: <br /> 13. Foundation supports for'A/C.units shall be raised at least 37 above finished grade..' M13-08.i. <br /> 14. Return air in all,bedrooms.T.B.C. M1620.4,. . <br /> 15. Smoke detectors'are.to-be installed:in accordance with:R313:.1 of the F.B.C. <br /> 16.-All_glazing requirements are:.to be m accordance-with R308.4,of the.F.B.C. <br /> 17. All means of egress are to.be in accordance with.R311'6f the RB.C..:: <br /> 18.-`,'Green gypsum board"-shall not be used:as.a backer.in:showers or tubs. R702.4.2 F.B.C. <br /> 19. Combination-t ype AFCI breakers are required_at all locations re.quirm n AFCI-type Breaker: <br /> 20. Carbon monoxide alarms"will be required in.now:construction that uses fossil-burniri e'atin <br /> or appliances"or an attached garage: They shall be,installed in accordance"with_the F;B.C. <br /> 21. All plumbing;mechanical,"and electrical shall be separate from unit to unit: This includes all. <br /> underground plumbing and electric: - <br /> 22. All2008 N".E:C: Codes.will.'be enforced. <br /> 23. Tamper-Resistant Receptacles in accordance with 406.11 of"the 2"008 N.E:G <br /> .24. In"accordance:.with the Land.Development:Code;.lots shall be sodded before final at least 10 <br /> feetaround the.structure: <br /> 25.A.copy of the energy cacls shall be.with permit at all times. <br /> .26..Copy of final insulation report shall be.provided with.permit_before.lnah . <br /> F:F:E.-Finished Floor Elevation <br /> F.B.C-_Florida Building Code"5 . Edition <br /> R.O.W.-Right of Way <br /> A.D.A.-Americans with Disabilities Act NI.C.-National Electric Code(2008) : - <br />