Laserfiche WebLink
BuildingAnalysis Job: 4259AB sf ADS <br /> Y Date: 9/2712017 <br /> lower floor By: Dave Aldrich <br /> Bayonet Plumbing Heating and Cooling <br /> 8950 New York ave,Hudson <br /> Project • • <br /> For: Lennar Homes <br /> Design Conditions <br /> Location: Indoor: Heating Cooling <br /> Tampa International AP, FL, US Indoor temperature(OF) 70 75 <br /> Elevation: 10 ft Design TD (OF) 39 16 <br /> Latitude: 28°N Relative humidity(%) 50 50 <br /> Outdoor: Heating Cooling Moisture difference(gr/lb) 34.7 54.7 <br /> Dry bulb(OF) 31 91 Infiltration: <br /> Daily range(OF) - 14 ( L ) Method Simplified <br /> Wet bulb(OF) - 77 Construction quality Semi-tight <br /> Wind speed(mph) 15.0 7.5 Fireplaces 0 <br /> i <br /> Component Btuh/ft2 Btuh % of load <br /> Walls 5.6 7481 29.9 ucts <br /> Glazing 21.6 5185 20.7 <br /> Doors 23.5 466 1.9 wan nfiltraton <br /> Ceilings 2.9 73 0.3 <br /> Floors 3.5 6649 26.6 <br /> Infiltration 1.9 3055 12.2 <br /> Ducts 2088 8.4 <br /> Piping 0 0 Floors <br /> Humidification 0 0 Glazing <br /> Ventilation 0 0 other <br /> Adjustments 0 <br /> Total 24996 100.0 <br /> I <br /> Component Btuh/ft2 Btuh % of load <br /> Walls 2.8 3721 18.7 <br /> Glazing 38.8 9328 47.0 Walls Internal Gains <br /> Doors 18.4 365 1.8 <br /> Ceilings 3.5 88 0.4 <br /> Floors 0 0 0 Ducts <br /> Infiltration 0.4 661 3.3 <br /> Ducts 2396 12.1 <br /> Ventilation 0 0 Infiltration <br /> Internal gains 3290 16.6 other <br /> Blower 0 0 <br /> Adjustments 0 Glazing <br /> Total 19850 100.0 <br /> Latent Cooling Load=2394 Btuh <br /> Overall U-value= 0.143 Btuh/ft2-°F <br /> Data entries checked. <br /> - 1- wrightsoft9 2017-Sep-27 06:59:52 <br /> Right-Suite®Universal 2017 17.0.23 RSU05714 Page 1 <br /> ..A27UHE AH's\4259AB sf ADS template 2.5-2ton.rup Calc=MJB Front Door faces:SE <br />