Laserfiche WebLink
Single. Family Dwelling <br /> Plan Review.ComrrientS <br /> 1: F.F.E. shall be.a minimum:of.8".above.the road elevation-and an engineered.site plan. ;: <br /> 2. Lots shall be-graded to.comply with R401.3 of theF.B.C: <br /> 3. :Compaction test required if 24" or more of fill dirt is brought-in:at any one place: <br /> .4:. :Tie in surveyrequiredbefore pouring concrete. <br /> 5.. Driveways:require a R.O.W. use permit.' AII.4:sides of driveway thru the sidewalk sliall_liave. <br /> expansion material:. . . <br /> .. . <br /> 6.. All setbacks.shall be met:.- <br /> 7._ All property markers shall be uni covered and marked at time'of first inspection: <br /> 8: :All A.D.A.requirements shall'be met. . <br /> 9.. No:electric.plumbing,mechanical. or framing shall be covered without an inspection and <br /> approval first. . . <br /> 10. All. Garages shall,comply.-with-section R302.6,of.the.F.B.C::(Fire Separation). <br /> 11:Appliances shall iiot be installed in a location'where subiectto mechanical damage unless <br /> .protected by approved barriers: M303.4'of.the F.B.0 <br /> 12. Water heaters shall comply with section.P607.3 'of the F.B:C. <br /> 13. Foundation supports Tor A/C units steal"1 be raised at least 3" above nished grade.. M1308.1. <br /> 14. Return air in all b.edrooms..F.B.C. 1VL1620.4 <br /> 15: Smoke detectors'are.to be installed:in accordance.withi R313:1 of the F.B.C. <br /> 16.All glazing requirements are:16 be in accordance with R308.4.of the F.B.C. <br /> 17. All means of egress are to be in accordance with R311.:of the F;B.C.- <br /> 18. "Green gypsum.board"shall not be used-as.a backer in showers or tubs. R702.4:2,F.B.C. <br /> 19. Combination-f ype AFCI breakers are.required:at all locations requiring an AFCI type breaker: . . :. . - <br /> 20: Carbon monoxide,alarms will.be re uired in'riew constr 'etionthat uses fossil-burnin heating <br /> .. q . - . g:. g <br /> or appliances or an attached garage:, They shall be installed in accordance'with the F.B.C. <br /> 21. All plumbing,mechanical, and electrical shall:be separate from unit to unit: This includes all = <br /> underground plumbing and electric: <br /> 22.. All pO11:N:E:C: CO*des p ill be enforced:.' <br /> .23. Tam er-' Resistant Rece tacles in accordance with 406.11 of the 2011 N:E:C <br /> .24::Iri accordance:.with the Land:Development Code. lots shall be,sodded before final at least 10 <br /> feetaround the structure <br /> 2S.A.copy of the energy cacls shall be with permit at all times. <br /> 26 Copy of final insulatioiz report shall be.provided with.permit-before.finaL <br /> F.F.E:-Finished Floor,Elevation <br /> F.B:C=Florida Building Code 6 'Edition: <br /> R.O.W.-Right'of Way <br /> A.D.A.-'Americans with.-Disabilities Act N.E.C:-National.Electric.Code(2011): - <br />