Laserfiche WebLink
Manual S Compliance Report Job: 1551B1 sf ADS Carrier <br /> Date: 511/2018 <br /> Entire House By: Dave <br /> BAYONET PLUMBING COOLING HEATING <br /> Project Information <br /> For: Lennar Homes <br /> Cooling Equipment <br /> Design Conditions <br /> Outdoor design DB: 91.3°F Sensible gain: 18777 Btuh Entering coil DB: 75.7°F <br /> Outdoor design WB: 77.3°F Latent gain: 2492 Btuh Entering coil WB: 62.8°F <br /> Indoor design DB: 75.0°F Total gain: 21269 Btuh <br /> Indoor RH: 50% Estimated airflow: 800 cfm <br /> Manufacturer's Performance Data at Actual Design Conditions <br /> Equipment type: SplitASHP_ <br /> Manufacturer: Carrier Model: 25HBC524A00300+FB4CNP025L <br /> Actual airflow: 800 cfm <br /> Sensible capacity: 20400 Btuh 109% of load <br /> Latent capacity: 3600 Btuh 144% of load <br /> Total capacity: 24000 Btuh 113% of load SHR: 85% <br /> Heating Equipment <br /> Design Conditions <br /> Outdoor design DB: 30.8°F Heat loss: 21794 Btuh Entering coil DB: 69.6°F <br /> Indoor design DB: 70.0°F <br /> Manufacturer's Performance Data at Actual Design Conditions <br /> Equipment type: SplitASHP <br /> Manufacturer: Carrier Model: 25HBC524A00300+FB4CNP025L <br /> Actual airflow: 800 cfm <br /> Output capacity: 18304 Btuh 84% of load Capacity balance: 30 OF <br /> Supplemental heat required: 3490 Btuh Economic balance: -99 OF <br /> Backup equipment type: Elec strip <br /> Manufacturer: n/a Model: n/a+n/a <br /> Actual airflow: 800 cfm <br /> Output capacity: 0 kW 0% of load Temp. rise: 0 OF <br /> Meets all requirements of ACCA Manual S. <br /> - wrightso ® 2018-May-01 08:12:20 <br /> M�� ftAv���a� --- ---- Right-Suiteral Universal 2018 18.0.16 RSU05714 <br /> Page 1 <br /> ...equipment\1551 sf ADS template 2ton Carrierrup Calc=MJB Front Door faces:NW <br />