Page 1 Commercial Heat Loss and Heat Gain Calculation 6/05/2018 <br /> Report Prepared By: <br /> Fudin Construction LLC <br /> For: HIBACHI EXPRESS <br /> 7306 GALL BLVD <br /> ZEPHYRHILLS FL 33541 <br /> Design Conditions: TAMPA Latitude: 28; Time 7:00 P UI <br /> Indoor: <br /> Outdoor: <br /> Summer temperature: 75 Summer temperature: 92 <br /> Winter temperature: 72 Winter temperature: 40 <br /> Relative humidity: 50 Summer grains of moisture: 95 <br /> Daily temperature range: 70 <br /> Building Component Sensible Latent Total Total <br /> Gain Gain Heat Gain Heat <br /> Loss <br /> (BTUH) (BTUH) (BTUH) (BTUH <br /> Floor 3000 sq.ft. 0 0 0 7585 <br /> S Wall 322 sq.ft. 394 0 394 676 <br /> Door 40 sq.ft. 1782 0 1782 1848 <br /> Leakage Summer 90 cfm 5752 5725 8326 0 <br /> Leakage Winter 160 cfm 0 0 0 14784 <br /> NW Wall 902.5 sq.ft. 1,060 0 1.060 1,895 <br /> SE Wall 347.5 sq.ft. 333 0 333 730 <br /> Door 40 sq.ft 292 0 292 940 <br /> Leakage Summer 30 cfm 858 1918 2776 0 <br /> Leakage Winter 55 cfm 0 0 0 5082 <br /> Partition 4000 sg.ft. 7519 0 7519 0 <br /> Ceiling 3000 sq.ft. 2203 0 2203 2520 <br /> People/Vent 55 people 15125 15125 30250 0 <br /> Ventilation 3000 cfm 42900 95340 138780 46260 <br /> Lights 4000 watts 16399 0 16399 0 <br /> Total 210114 <br /> 17.5 Ton <br /> HVAC-Calc Commercial 4.0 by HVAC Computer Systems Ltd. 888 736-1101 <br /> Load calculations are estimates only,actual loads may vary due to weather and construction differences. <br />